0388 SFN 5640 J 003 A - Control Building Illumination System Calculation


(Emergency)
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
0388 SFN 5640 J 003 A - Control Building Illumination System Calculation (Emergency) / Table of contents

Table of contents
0388 SFN 5640 J 003 A - Control Building Illumination System Calculation (Emergency)
San Francisco Control Building
Building 1
Ground Floor
Cable Gallery
Views............................................................................................................................................................................. 3
Cable Gallery / Perpendicular illuminance (adaptive).................................................................................................... 4
Second Floor
Auxillary Room
Views............................................................................................................................................................................. 5
Auxillary Room / Perpendicular illuminance (adaptive)..................................................................................................6
Battery Room
Views............................................................................................................................................................................. 8
Battery Room / Perpendicular illuminance (adaptive)....................................................................................................9
Control Room
Views............................................................................................................................................................................11
Control Room / Perpendicular illuminance (adaptive)..................................................................................................12
Relay and Communication Room
Views........................................................................................................................................................................... 14
Relay and Communication Room / Perpendicular illuminance (adaptive)................................................................... 15

Page 2
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Ground Floor / Cable Gallery / Views

Cable Gallery

Cable Gallery

Page 3
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Ground Floor / Cable Gallery / Cable Gallery / Perpendicular illuminance
(adaptive)

Cable Gallery / Perpendicular illuminance (adaptive)

Cable Gallery: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 103 lx (Target: ≥ 100 lx), Min: 9.18 lx, Max: 279 lx, Min/average: 0.089, Min/max: 0.033
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 300

False colours [lx]

Scale: 1 : 300

Value grid [lx]

Scale: 1 : 300

Page 4
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Auxillary Room / Views

Auxillary Room

Auxillary Room

Page 5
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Auxillary Room / Auxillary Room / Perpendicular
illuminance (adaptive)

Auxillary Room / Perpendicular illuminance (adaptive)

Auxillary Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 103 lx (Target: ≥ 100 lx), Min: 0.36 lx, Max: 324 lx, Min/average: 0.003, Min/max: 0.001
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 75

Page 6
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Auxillary Room / Auxillary Room / Perpendicular
illuminance (adaptive)

False colours [lx]

Scale: 1 : 75

Value grid [lx]

Scale: 1 : 75

Page 7
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Battery Room / Views

Battery Room

Battery Room

Page 8
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Battery Room / Battery Room / Perpendicular illuminance
(adaptive)

Battery Room / Perpendicular illuminance (adaptive)

Battery Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 107 lx (Target: ≥ 100 lx), Min: 46.9 lx, Max: 201 lx, Min/average: 0.44, Min/max: 0.23
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 75

Page 9
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Battery Room / Battery Room / Perpendicular illuminance
(adaptive)

False colours [lx]

Scale: 1 : 75

Value grid [lx]

Scale: 1 : 75

Page 10
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Control Room / Views

Control Room

Control Room

Page 11
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Control Room / Control Room / Perpendicular illuminance
(adaptive)

Control Room / Perpendicular illuminance (adaptive)

Control Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 181 lx (Target: ≥ 100 lx), Min: 1.11 lx, Max: 345 lx, Min/average: 0.006, Min/max: 0.003
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 100

Page 12
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Control Room / Control Room / Perpendicular illuminance
(adaptive)

False colours [lx]

Scale: 1 : 100

Value grid [lx]

Scale: 1 : 100

Page 13
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Relay and Communication Room / Views

Relay and Communication Room

Relay and Communication Room

Page 14
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Relay and Communication Room / Relay and
Communication Room / Perpendicular illuminance (adaptive)

Relay and Communication Room / Perpendicular illuminance


(adaptive)

Relay and Communication Room: Perpendicular illuminance (adaptive) (Surface)


Light scene: Light scene 1
Average: 158 lx (Target: ≥ 100 lx), Min: 0.001 lx, Max: 384 lx, Min/average: 0.000, Min/max: 0.000
Height: 0.800 m, Wall zone: 0.000 m

Isolines [lx]

Scale: 1 : 115

Page 15
0388 SFN 5640 J 003 A - Control Building 7/29/2019
Illumination System Calculation
(Emergency)
San Francisco Control Building / Building 1 / Second Floor / Relay and Communication Room / Relay and
Communication Room / Perpendicular illuminance (adaptive)

False colours [lx]

Scale: 1 : 115

Value grid [lx]

Scale: 1 : 115

Page 16