Professional Documents
Culture Documents
Fuzzy Logic For Developments and Applications of Unbalance Three-Phase Fuzzy Feeder Models
Fuzzy Logic For Developments and Applications of Unbalance Three-Phase Fuzzy Feeder Models
Fuzzy Logic For Developments and Applications of Unbalance Three-Phase Fuzzy Feeder Models
toward the use of fixed (crisp) values for the input data.
Abstract--Based on the fuzzy set theory, this study
This assumption is in clear contrast to the real-life
introduces three novel three-phase fuzzy feeder models for situation in which the uncertainty of input data is
fast distribution system calculations. These fuzzy models are always present. Namely, in the planning stage of
formulated using three lumped individual phase loads to distribution systems, the decision maker is faced with
represent single-phase, three-phase unbalanced, and the low precision and/or fuzziness of data. Fuzzy set
nonuniformly distributed loads along a feeder. The proposed theory derives from the fact that almost all natural
voltage-drop and line-loss fuzzy models are developed to classes and concepts are fuzzy rather than crisp in
accurately simulate the total series voltage drop at the end nature [6].
and the total copper loss of a given feeder, respectively. A A novel method based on the fuzzy logic control to
hybrid fuzzy model is then developed to simulate both solve the feeder modelling problem is presented.
voltage drop and line loss accurately. The proposed fuzzy Instead of the general assumption that discrete
models are applied to a physical feeder. Simulation results distributed tapped-off loads and feeder segment are
show that it is possible to simplify complicated feeders to known exactly [2]-[5], they are treated here as fuzzy
simple equivalent models in the calculations of voltage variables. The proposed three-phase fuzzy feeder
profiles and line losses with negligible error, even if there models use individual phase equivalent length Leqk
are various transformer connection schemes in the feeder. and equivalent load Seqk of each tapped-off load point
Keywords: Distribution system, Feeder model, Fuzzy set as crisp input data of a designed fuzzy feeder
theory, Three-phase system. modelling controller (FFMC). Along a feeder, the
individual phase voltage drop vk at each tapped-off
1. Introduction load point is considered to be crisp out data. Once
Generally, in a modern distribution system various vk has been computed, the proposed fuzzy models
transformer connections are used to meet the can be generated using lumped loads to represent
requirements of different customers and to optimize discretely distributed tapped-off loads along a feeder.
system operation. These transformer connections
could be single-phase, open delta-open delta, open 2. Implementation of Fuzzy Feeder
wye-open delta, Scott and three-phase connections.
Three-phase power flow programs, instead of Modelling Controller (FFMC)
traditional power flow programs, should be used to A single-line diagram, shown in Fig. 1, illustrates a
analyze distribution systems [1], [2]. Therefore, it is general three-phase feeder segment. There are n
important to develop three-phase feeder models for discrete loads distributed along the feeder, and the
distribution system planning, operation, and
distribution automation and control (DAC). transformer impedance and resistance values are all
The early studies on feeder modeling for total series represented in per units on their own KVA ratings.
voltage drop and copper loss calculations are A distribution transformer and its loads can be
concerned with uniformly distributed load [2]. Then, integrated and simply represented by its equivalent
three simplified feeder models dealing with discrete loads [7]. Hence, the sample feeder can be redrawn as
distributed tapped-off loads were introduced [3]. Fig. 2. In Fig. 2, the individual phase equivalent length
These feeder models introduced are unidirectional, Leqk and equivalent load Seqk of the tapped-off load
that is, the feeder models are accurate only if power is “k”are defined by
fed at the same end as specified in the model. Three
n
bi-directional feeder models are developed [4]. These
qk Li
Lφe a, b, c; k 1,2
,n (1)
models simulate the feeders, laterals and feeder i k
segments accurately, even when the power infeeds of
given feeders or feeder segments are changed from
one end to the other. Therefore, no data input need be Lateral (or Feeder Segment)
changed when the system configuration is changed to be modelled
under service restoration and system reconfiguration. Bus
The simplified models mentioned above are all Ln Ln-1 . . . L2 L1
based on the assumption that the discrete loads are KVA n KVAn-1 KVA2 KVA1
Zn Z n-1 Z2
equally distributed on the three phases along the Rn Rn-1 R2
Z1
R1
feeder. This is usually not the case in a physical
distribution system because distribution systems are Sn S n-1 S2 S1
inherently unbalanced. Three three-phase single-
feeding-end feeder models introduced in [5].
A common trend for the feeder modelling in
distribution systems in previous approaches has been Fig.1: General feeder.
Bus
...
use a decision table (Table II). Using fuzzy set
Ln L n-1 L2 L1
a notations, the decision table can be converted into a
b
c fuzzy relation matrix (Table III).
2.3. Determine the membership function of output
San Scn San-1 Scn-1 Sa2 Sc2 Sa1 Sc1 data
S bn Sbn-1 S b2 S b1 Use the composition rule of fuzzy set theory to
determine the membership function of the output data.
Fig.2: Simplified sample feeder for modeling.
φa i 1
Where
Lt is the total length of the feeder S apS bp S cp
Pt is the total active load along the feeder Fig. 6: Three-phase line-loss fuzzy feeder model.
Qt is the total reactive load along the feeder
Once the individual phase voltage drop ( vk ) at 3.3. Three-phase hybrid fuzzy feeder model
each of the tapped-off load point has been computed, A hybrid model was developed to accurately
along a feeder, each of the discrete load is considered represent both the total series voltage drop and total
to be an incremental load at its incremental distance as copper loss of the given feeder. The model shown in
shown in Fig. 4. For per unit system, the incremental Fig. 7 combines the two foregoing models. For the
current is assumption of balanced feeder, the proportion of the
I φj(PφjjQ φj)/( 1 Δv φj) split line length can be shown as [5]
a, b, c; j 1,2
,n (6) Lt L p Lv 2
K (11)
Li I
i V
j I
i-1 L i-1 Lt 2 2 Lt Lv Lt
Lp