EDMT341410B

FXDQ-PB / FXDQ-NB
Slim Ceiling Mounted Duct Type
(Standard Series)

1. Specifications ......................................................................................136
1.1 FXDQ-PB .............................................................................................136
1.2 FXDQ-NB .............................................................................................137
2. Dimensions .........................................................................................138
2.1 FXDQ-PB .............................................................................................138
2.2 FXDQ-NB .............................................................................................140
3. Piping Diagrams..................................................................................144 8
4. Wiring Diagrams..................................................................................145
5. Electric Characteristics........................................................................147
6. Safety Devices Setting ........................................................................148
7. Capacity Tables ..................................................................................149
7.1 Cooling Capacity for Te: 6°C................................................................149
7.2 Cooling Capacity for Te: 9°C................................................................149
8. Fan Performances...............................................................................150
8.1 FXDQ-PB .............................................................................................150
8.2 FXDQ-NB .............................................................................................151
9. Sound Levels ......................................................................................152
9.1 FXDQ-PB .............................................................................................152
9.2 FXDQ-NB .............................................................................................154
10.Centre of Gravity .................................................................................156
10.1 FXDQ-PB .............................................................................................156
10.2 FXDQ-NB .............................................................................................157
11.Accessories.........................................................................................158
11.1 Optional Accessories (for Unit).............................................................158
11.2 Optional Accessories (for Controls)......................................................158

FXDQ-PB / FXDQ-NB 135


Specifications EDMT341410B

1. Specifications
1.1 FXDQ-PB

Slim ceiling mounted duct type (Standard series) <700 mm width type>
with a drain pump FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
Model
without a drain pump FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 1,900 2,400 3,100
1 2 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620 200×700×620 200×700×620
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 62×1 62×1 62×1
Number of units
Fan m³/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Airflow rate (HH/H/L) l/s 133/120/106 133/120/106 133/120/106
cfm 282/254/226 282/254/226 282/254/226
3 External static pressure Pa 30-10 30-10 30-10
Drive Direct drive Direct drive Direct drive
Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
Temperature control
for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene Foamed polyethylene
Air filter Removal / Washable / Mildew proof Removal / Washable / Mildew proof Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections
VP20 VP20 VP20
Drain pipe mm (External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20)
Mass kg 23 23 23
4 5 6 Sound pressure level (HH/H/L) dB(A) 28/26/23 28/26/23 28/26/24
Safety devices Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Operation manual. Operation manual.
Installation manual. Installation manual. Installation manual.
Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps.
Standard accessories Washers. Insulation for fitting. Washers. Insulation for fitting. Washers. Insulation for fitting.
Clamp metal. Washer fixing plate. Clamp metal. Washer fixing plate. Clamp metal. Washer fixing plate.
Screws for duct flanges. Air filter. Screws for duct flanges. Air filter. Screws for duct flanges. Air filter.
(Product quality certificate 7) (Product quality certificate 7) (Product quality certificate 7)
Specification C: 3D060921C C: 3D060921C C: 3D060921C
Drawing No.
Sound level C: 4D090841 C: 4D090842 C: 4D090844

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. kcal/h=kW×860
Btu/h=kW×3412
3. External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard static pressure”. cfm=m³/min×35.3
(Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.) l/s=m³/min×1000/60
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
5. Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
6. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
7. FXDQ20 / 25 / 32PBVE only.
8. Refer to Electric Characteristics for the power input.

136 FXDQ-PB / FXDQ-NB


EDMT341410B Specifications

1.2 FXDQ-NB

Slim ceiling mounted duct type (Standard series) <900 / 1,100 mm width type>
with a drain pump FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Model
without a drain pump FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 3,900 4,800 6,100
1 2 Cooling capacity Btu/h 15,400 19,100 24,200
kW 4.5 5.6 7.1
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×900×620 200×900×620 200×1,100×620
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 62×1 130×1 130×1
Number of units
Fan m³/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Airflow rate (HH/H/L) l/s 175/158/141 208/183/166 275/241/216
cfm 371/335/300 441/388/353 583/512/459
3 External static pressure Pa 44-15 44-15 44-15
Drive Direct drive
Microprocessor thermostat
Direct drive
Microprocessor thermostat
Direct drive
Microprocessor thermostat
8
Temperature control
for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene Foamed polyethylene
Air filter Removal / Washable / Mildew proof Removal / Washable / Mildew proof Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ15.9 (Flare connection)
connections
VP20 VP20 VP20
Drain pipe mm
(External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20)
Mass kg 27 28 31
4 5 6 Sound pressure level (HH/H/L) dB(A) 30/28/26 33/30/27 33/31/29
Safety devices Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Operation manual. Operation manual.
Installation manual. Installation manual. Installation manual.
Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps.
Standard accessories Washers. Insulation for fitting. Washers. Insulation for fitting. Washers. Insulation for fitting.
Clamp metal. Washer fixing plate. Clamp metal. Washer fixing plate. Clamp metal. Washer fixing plate.
Screws for duct flanges. Air filter. Screws for duct flanges. Air filter. Screws for duct flanges. Air filter.
(Product quality certificate 7) (Product quality certificate 7) (Product quality certificate 7)
Specification C: 3D060921C C: 3D060921C C: 3D060921C
Drawing No.
Sound level C: 4D090843 C: 4D090845 C: 4D090846

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. kcal/h=kW×860
Btu/h=kW×3412
3. External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard static pressure”. cfm=m³/min×35.3
(Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.) l/s=m³/min×1000/60
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
5. Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
6. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
7. FXDQ40 / 50 / 63NBVE only.
8. Refer to Electric Characteristics for the power input.

FXDQ-PB / FXDQ-NB 137


Dimensions EDMT341410B

2. Dimensions
2.1 FXDQ-PB

FXDQ20PBVE / FXDQ25PBVE / FXDQ32PBVE (with a drain pump)


Unit: mm

3D049799C

138 FXDQ-PB / FXDQ-NB


EDMT341410B Dimensions

FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET (without a drain pump)


Unit: mm

3D050732B
8

FXDQ-PB / FXDQ-NB 139


Dimensions EDMT341410B

2.2 FXDQ-NB

FXDQ40NBVE / FXDQ50NBVE (with a drain pump)


Unit: mm

3D045494D

140 FXDQ-PB / FXDQ-NB


EDMT341410B Dimensions

FXDQ63NBVE (with a drain pump)


Unit: mm

3D045496E
8

FXDQ-PB / FXDQ-NB 141


Dimensions EDMT341410B

FXDQ40NBVET / FXDQ50NBVET (without a drain pump)


Unit: mm

3D049701B

142 FXDQ-PB / FXDQ-NB


EDMT341410B Dimensions

FXDQ63NBVET (without a drain pump)


Unit: mm

3D049702B
8

FXDQ-PB / FXDQ-NB 143


Piping Diagrams EDMT341410B

3. Piping Diagrams
FXDQ20PBVE / FXDQ25PBVE / FXDQ32PBVE / FXDQ40NBVE / FXDQ50NBVE / FXDQ63NBVE
FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET / FXDQ40NBVET / FXDQ50NBVET / FXDQ63NBVET

4D060927B

„ Refrigerant pipe connection port diameters


(mm)
Model Gas Liquid
FXDQ20PBVE / FXDQ25PBVE / FXDQ32PBVE / FXDQ40NBVE / FXDQ50NBVE
φ12.7 φ6.4
FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET / FXDQ40NBVET / FXDQ50NBVET
FXDQ63NBVE
FXDQ63NBVET φ15.9 φ9.5

144 FXDQ-PB / FXDQ-NB


EDMT341410B Wiring Diagrams

4. Wiring Diagrams
FXDQ20PBVE / FXDQ25PBVE / FXDQ32PBVE / FXDQ40NBVE / FXDQ50NBVE / FXDQ63NBVE
(with a drain pump)

3D060547B
8

FXDQ-PB / FXDQ-NB 145


146
A1P PRINTED CIRCUIT BOARD
C1 CAPACITOR (M1F)
F1U FUSE (F5A/250V)
Wiring Diagrams

HAP LIGHT EMITTING DIODE


(SERVICE MONITOR GREEN)
M1F MOTOR (INDOOR FAN)
R1T R2T R3T
(without a drain pump)

Q1M THERMAL PROTECTOR (M1F EMBEDDED)


R1T THERMISTOR (AIR) t˚ t˚ t˚
R2T THERMISTOR (COIL-1) POWER A1P
SUPPLY X1M NOTE) 5
R3T THERMISTOR (COIL-2)
~220-240V~220V PNK T2 INPUT FROM
T1R TRANSFORMER (220V/22V) X13A X12A X11A X16A Z1C
50Hz 60Hz WHT T1 OUTSIDE
V1TR PHASE CONTROL CIRCUIT N=3
X2M YLW F2 TRANSMISSION
F1U X30A WIRING CENTRAL
X1M TERMINAL BLOCK L RED
L ORG F1
X2M TERMINAL BLOCK REMOTE CONTROLLER
N N BLU BLU P2 P2 R1T NOTE) 3
Y1E ELECTRONIC EXPANSION VALVE P1
X31A BLK P1
Z1C · Z2C NOISE FILTER (FERRITE CORE) GRN SS1
WIRED REMOTE CONTROLLER /YLW WIRED REMOTE
R1T THERMISTOR (AIR) X18A Z2C CONTROLLER
X1A T1R N=3
SS1 SELECTOR SWITCH (MAIN/SUB) X3A
t˚ X27A
CONNECTOR FOR OPTIONAL PARTS
GRY
X16A CONNECTOR (ADAPTOR FOR WIRING) PRP
X18A CONNECTOR (WIRING ADAPTOR M BLU
FOR ELECTRICAL APPENDICES) C1

Y1E
V1TR
YLW
WHT

X7A
X18A X16A RED M
~
BLK Q1M
X4A M1F
A1P HAP

X1M C1 X2M
Z1C
T1R
Z2C
NOTES) CONTROL BOX
1. : TERMINAL
, : CONNECTOR
2. : FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN
FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET / FXDQ40NBVET / FXDQ50NBVET / FXDQ63NBVET

C: 3D060548
EDMT341410B

FXDQ-PB / FXDQ-NB
EDMT341410B Electric Characteristics

5. Electric Characteristics
FXDQ20PBVE / FXDQ25PBVE / FXDQ32PBVE / FXDQ40NBVE / FXDQ50NBVE / FXDQ63NBVE
FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET / FXDQ40NBVET / FXDQ50NBVET / FXDQ63NBVET

4D060922

FXDQ-PB / FXDQ-NB 147


Safety Devices Setting EDMT341410B

6. Safety Devices Setting

Model FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE


FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
Printed circuit board fuse 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A
Fan motor thermal fuse °C – – – – – –
OFF: 130±5 OFF: 130±5 OFF: 130±5 OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON : 83±15 ON : 83±15 ON : 83±15 ON : 83±15 ON : 83±15 ON : 83±15
C: 4D060926D

148 FXDQ-PB / FXDQ-NB


EDMT341410B Capacity Tables

7. Capacity Tables
7.1 Cooling Capacity for Te: 6°C
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20PBVE 20 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.2 1.8 2.3 1.6 2.3 1.7
FXDQ20PBVET
FXDQ25PBVE 25 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 2.8 2.1 2.9 2.0 3.0 1.9
FXDQ25PBVET
FXDQ32PBVE
FXDQ32PBVET 32 2.4 1.9 2.9 2.2 3.4 2.4 3.6 2.6 3.6 2.4 3.7 2.4 3.8 2.4

FXDQ40NBVE
40 3.0 2.5 3.6 2.8 4.2 3.2 4.5 3.3 4.6 3.1 4.7 3.0 4.8 3.1
FXDQ40NBVET
FXDQ50NBVE 3.1 4.5 3.5 5.2 3.9 5.6 4.0 5.7 3.9 5.8 3.8 5.9 3.5
FXDQ50NBVET 50 3.8

FXDQ63NBVE
63 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.2 4.6 7.4 4.6 7.5 4.6
FXDQ63NBVET

TC: Total capacity: kW


SHC: Sensible heat capacity: kW 8
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

7.2 Cooling Capacity for Te: 9°C


When a mixed combination of VRV and
residential indoor units is connected

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20PBVE
20 1.0 1.0 1.2 1.2 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.4 2.0 1.5
FXDQ20PBVET
FXDQ25PBVE
25 1.3 1.2 1.6 1.6 2.0 1.8 2.2 1.8 2.2 1.8 2.4 1.8 2.6 1.7
FXDQ25PBVET
FXDQ32PBVE
FXDQ32PBVET 32 1.7 1.5 2.0 1.8 2.6 2.0 2.8 2.2 2.8 2.0 3.0 2.1 3.2 2.1

FXDQ40NBVE
FXDQ40NBVET 40 2.0 2.0 2.5 2.3 3.2 2.7 3.5 2.8 3.7 2.7 3.9 2.6 4.1 2.8

FXDQ50NBVE
FXDQ50NBVET 50 2.6 2.4 3.1 2.9 3.9 3.3 4.4 3.4 4.6 3.3 4.8 3.4 5.1 3.1

FXDQ63NBVE
FXDQ63NBVET 63 3.2 2.9 4.0 3.5 5.1 4.1 5.6 4.2 5.8 4.0 6.2 4.1 6.5 4.1

TC: Total capacity: kW


SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

FXDQ-PB / FXDQ-NB 149


Fan Performances EDMT341410B

8. Fan Performances
8.1 FXDQ-PB
FXDQ20PBVE / FXDQ25PBVE FXDQ32PBVE
FXDQ20PBVET / FXDQ25PBVET FXDQ32PBVET

C: 3D052156D C: 3D052157D

Notes:
1. The remote controller can be used to switch between “HH”, “H” and “L”.
2. The airflow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” by the remote controller.

150 FXDQ-PB / FXDQ-NB


EDMT341410B Fan Performances

8.2 FXDQ-NB
FXDQ40NBVE FXDQ50NBVE
FXDQ40NBVET FXDQ50NBVET

C: 3D046299F

C: 3D046300F

FXDQ63NBVE
FXDQ63NBVET

C: 3D046301F

Notes:
1. The remote controller can be used to switch between “HH”, “H” and “L”.
2. The airflow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” by the remote controller.

FXDQ-PB / FXDQ-NB 151


Sound Levels EDMT341410B

9. Sound Levels
9.1 FXDQ-PB

FXDQ20PBVE
FXDQ20PBVET

4D090841
FXDQ25PBVE
FXDQ25PBVET

4D090842

152 FXDQ-PB / FXDQ-NB


EDMT341410B Sound Levels

FXDQ32PBVE
FXDQ32PBVET

4D090844
8

FXDQ-PB / FXDQ-NB 153


Sound Levels EDMT341410B

9.2 FXDQ-NB

FXDQ40NBVE
FXDQ40NBVET

4D090843
FXDQ50NBVE
FXDQ50NBVET

4D090845

154 FXDQ-PB / FXDQ-NB


EDMT341410B Sound Levels

FXDQ63NBVE
FXDQ63NBVET

4D090846
8

FXDQ-PB / FXDQ-NB 155


Centre of Gravity EDMT341410B

10. Centre of Gravity


10.1 FXDQ-PB

FXDQ20PBVE / FXDQ25PBVE / FXDQ32PBVE


FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET
Unit: mm

4D049300L

156 FXDQ-PB / FXDQ-NB


EDMT341410B Centre of Gravity

10.2 FXDQ-NB

FXDQ40NBVE / FXDQ50NBVE
FXDQ40NBVET / FXDQ50NBVET
Unit: mm

4D043886Q

FXDQ63NBVE
FXDQ63NBVET
Unit: mm

4D043887P

FXDQ-PB / FXDQ-NB 157


Accessories EDMT341410B

11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item FXDQ20PBVE FXDQ20PBVET
FXDQ40NBVE FXDQ40NBVET
FXDQ25PBVE FXDQ25PBVET FXDQ63NBVE FXDQ63NBVET
FXDQ32PBVE FXDQ32PBVET FXDQ50NBVE FXDQ50NBVET

Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63


C: 4D060939C

11.2 Optional Accessories (for Controls)


Refer to page 822.

158 FXDQ-PB / FXDQ-NB


EDMT341410B

FXDQ-SP
Slim Ceiling Mounted Duct Type
(Compact Series)

1. Specifications ......................................................................................160
2. Dimensions .........................................................................................162
3. Piping Diagrams..................................................................................165
4. Wiring Diagrams..................................................................................166
5. Electric Characteristics........................................................................167
6. Safety Devices Setting ........................................................................168
7. Capacity Tables ..................................................................................169
7.1 Cooling Capacity for Te: 6°C................................................................169
7.2 Cooling Capacity for Te: 9°C................................................................169 9
8. Fan Performances...............................................................................170
9. Sound Levels ......................................................................................175
10.Centre of Gravity .................................................................................178
11.Accessories.........................................................................................180
11.1 Optional Accessories (for Controls)......................................................180

FXDQ-SP 159
Specifications EDMT341410B

1. Specifications
Slim ceiling mounted duct type (Compact series) <700 mm width type>

Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1

Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
kcal/h 1,900 2,400 3,100
1 2 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×450 200×700×450 200×700×450
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 62×1 62×1 62×1
Number of units
m³/min 8.7/7.6/6.5 9.0/8.0/7.0 10.0/9.0/8.0
Fan
Airflow rate (HH/H/L) l/s 145/127/108 150/133/117 167/150/133
cfm 307/268/229 318/282/247 353/318/282
3 External static pressure Pa 30-10 30-10 30-10
Drive Direct drive Direct drive Direct drive
Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
Temperature control
for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene Foamed polyethylene
Air filter — 4 — 4 — 4
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections
VP20 VP20 VP20
Drain pipe mm
(External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20)
Mass kg 17 17 17
5 6 7 Sound pressure level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30
Safety devices Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Operation manual. Operation manual.
Installation manual. Installation manual. Installation manual.
Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps.
Standard accessories
Washers. Insulation for fitting. Washers. Insulation for fitting. Washers. Insulation for fitting.
Metal clamp. Washer fixing plate. Metal clamp. Washer fixing plate. Metal clamp. Washer fixing plate.
Screws for duct flanges. Screws for duct flanges. Screws for duct flanges.
Specification C: 3D090324A C: 3D090324A C: 3D090324A
Drawing No.
Sound level C: 4D090507A C: 4D090508A C: 4D090509A

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 5m, level difference: 0m.
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. kcal/h=kW×860
Btu/h=kW×3412
3. External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory cfm=m³/min×35.3
setting is 10 Pa for FXDQ20-32SP models and 20 Pa for FXDQ40-63SP models.) l/s=m³/min×1000/60
4. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6. Values are based on the following conditions: FXDQ20-32SP: external static pressure of 10 Pa; FXDQ40-63SP: external static pressure of
20 Pa.
7. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
8. Refer to Electric Characteristics for the power input.

160 FXDQ-SP
EDMT341410B Specifications

Slim ceiling mounted duct type (Compact series) <900 / 1,100 mm width type>

Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1

Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
kcal/h 3,900 4,800 6,100
1 2 Cooling capacity Btu/h 15,400 19,100 24,200
kW 4.5 5.6 7.1
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×900×450 200×900×450 200×1,100×450
Type Sirocco fan Sirocco fan Sirocco fan
Motor output ×
W 130×1 130×1 130×1
Number of units
m³/min 15.0/13.0/10.5 15.0/13.0/10.5 20.0/16.0/12.5
Fan
Airflow rate (HH/H/L) l/s 250/217/175 250/217/175 333/267/208
cfm 530/459/371 530/459/371 706/565/441
3 External static pressure Pa 50-20 50-20 40-20
Drive Direct drive Direct drive Direct drive

Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat


for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene Foamed polyethylene
Air filter — 4 — 4 — 4
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ9.5 (Flare connection)
Piping
connections
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ15.9 (Flare connection) 9
VP20 VP20 VP20
Drain pipe mm (External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20) (External dia. 26, Internal dia. 20)
Mass kg 20 20 23
5 6 7 Sound pressure level (HH/H/L) dB(A) 35/33/31 35/33/31 37/35/33
Safety devices Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Operation manual. Operation manual.
Installation manual. Installation manual. Installation manual.
Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps.
Standard accessories Washers. Insulation for fitting.
Washers. Insulation for fitting. Washers. Insulation for fitting.
Metal clamp. Washer fixing plate. Metal clamp. Washer fixing plate. Metal clamp. Washer fixing plate.
Screws for duct flanges. Screws for duct flanges. Screws for duct flanges.
Specification C: 3D090326A C: 3D090326A C: 3D090326A
Drawing No.
Sound level C: 4D090510A C: 4D090510A C: 4D090511A

Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 5m, level difference: 0m.
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. kcal/h=kW×860
Btu/h=kW×3412
3. External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard”. (Factory cfm=m³/min×35.3
setting is 10 Pa for FXDQ20-32SP models and 20 Pa for FXDQ40-63SP models.) l/s=m³/min×1000/60
4. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method (gravity method)
50% or more.
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
6. Values are based on the following conditions: FXDQ20-32SP: external static pressure of 10 Pa; FXDQ40-63SP: external static pressure of
20 Pa.
7. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
8. Refer to Electric Characteristics for the power input.

FXDQ-SP 161
Dimensions EDMT341410B

2. Dimensions
FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1
Unit: mm

3D071829D

162 FXDQ-SP
EDMT341410B Dimensions

FXDQ40SPV1 / FXDQ50SPV1
Unit: mm

3D071831D
9

FXDQ-SP 163
Dimensions EDMT341410B

FXDQ63SPV1
Unit: mm

3D071830D

164 FXDQ-SP
EDMT341410B Piping Diagrams

3. Piping Diagrams
FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 / FXDQ63SPV1

4D090514

„ Refrigerant pipe connection port diameters


(mm)
Model Gas Liquid
FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 φ12.7 φ6.4
FXDQ63SPV1 φ15.9 φ9.5

FXDQ-SP 165
Wiring Diagrams EDMT341410B

4. Wiring Diagrams
FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 / FXDQ63SPV1

3D089813B

166 FXDQ-SP
EDMT341410B Electric Characteristics

5. Electric Characteristics
FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1 / FXDQ40SPV1 / FXDQ50SPV1 / FXDQ63SPV1

4D090515

FXDQ-SP 167
Safety Devices Setting EDMT341410B

6. Safety Devices Setting

Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1


Printed circuit board fuse A1P 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A
Fan motor thermal fuse °C – – – – – –
OFF: 130±5 OFF: 130±5 OFF: 130±5 OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C
ON : 83±15 ON : 83±15 ON : 83±15 ON : 83±15 ON : 83±15 ON : 83±15
4D043861U

168 FXDQ-SP
EDMT341410B Capacity Tables

7. Capacity Tables
7.1 Cooling Capacity for Te: 6°C
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20SPV1 20 1.1 1.0 1.5 1.3 2.0 1.5 2.2 1.6 2.4 1.7 2.9 1.8 3.4 1.9
FXDQ25SPV1 25 1.5 1.3 2.0 1.6 2.5 1.9 2.8 2.0 3.1 2.1 3.7 2.3 4.4 2.5
FXDQ32SPV1 32 1.9 1.7 2.5 2.1 3.2 2.5 3.6 2.6 4.0 2.8 4.8 3.0 5.6 3.2
FXDQ40SPV1 40 2.3 2.2 3.2 2.7 4.0 3.2 4.5 3.4 5.0 3.5 5.9 3.8 6.9 4.0
FXDQ50SPV1 50 3.0 2.7 4.0 3.3 5.0 3.9 5.6 4.1 6.1 4.3 7.3 4.6 8.5 4.9
FXDQ63SPV1 63 3.8 3.3 5.0 4.1 6.4 4.8 7.1 5.1 7.8 5.3 9.3 5.7 10.9 6.1

TC: Total capacity: kW


SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

7.2 Cooling Capacity for Te: 9°C


9
When a mixed combination of VRV and
residential indoor units is connected

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20SPV1 20 0.8 0.8 1.0 1.0 1.5 1.3 1.7 1.4 1.9 1.5 2.4 1.6 2.9 1.7
FXDQ25SPV1 25 1.1 1.0 1.4 1.3 1.8 1.6 2.1 1.7 2.4 1.8 3.0 2.0 3.7 2.2
FXDQ32SPV1 32 1.3 1.3 1.7 1.7 2.4 2.1 2.7 2.2 3.1 2.4 3.9 2.6 4.7 2.9
FXDQ40SPV1 40 1.6 1.6 2.2 2.2 3.0 2.7 3.4 2.9 3.9 3.0 4.9 3.3 5.8 3.6
FXDQ50SPV1 50 2.1 2.1 2.7 2.7 3.7 3.3 4.3 3.5 4.8 3.7 6.1 4.0 7.2 4.4
FXDQ63SPV1 63 2.6 2.5 3.4 3.3 4.8 4.0 5.5 4.3 6.2 4.5 7.7 5.0 9.3 5.4

TC: Total capacity: kW


SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.

FXDQ-SP 169
Fan Performances EDMT341410B

8. Fan Performances
FXDQ20SPV1

3D072697C

170 FXDQ-SP
EDMT341410B Fan Performances

FXDQ25SPV1

3D072698C
9

FXDQ-SP 171
Fan Performances EDMT341410B

FXDQ32SPV1

3D090527

172 FXDQ-SP
EDMT341410B Fan Performances

FXDQ40SPV1 / FXDQ50SPV1

3D072702C
9

FXDQ-SP 173
Fan Performances EDMT341410B

FXDQ63SPV1

3D090542

174 FXDQ-SP
EDMT341410B Sound Levels

9. Sound Levels
FXDQ20SPV1

4D090507A
9

FXDQ25SPV1

4D090508A

FXDQ-SP 175
Sound Levels EDMT341410B

FXDQ32SPV1

4D090509A
FXDQ40SPV1 / FXDQ50SPV1

4D090510A

176 FXDQ-SP
EDMT341410B Sound Levels

FXDQ63SPV1

4D090511A
9

FXDQ-SP 177
Centre of Gravity EDMT341410B

10. Centre of Gravity


FXDQ20SPV1 / FXDQ25SPV1 / FXDQ32SPV1

Unit: mm

4D072718G

FXDQ40SPV1 / FXDQ50SPV1

Unit: mm

4D072719G

178 FXDQ-SP
EDMT341410B Centre of Gravity

FXDQ63SPV1

Unit: mm

9
4D072720H

FXDQ-SP 179
Accessories EDMT341410B

11. Accessories
11.1 Optional Accessories (for Controls)
Refer to page 822.

180 FXDQ-SP

You might also like