Professional Documents
Culture Documents
Group4 Electricalplanpart2
Group4 Electricalplanpart2
Group4 Electricalplanpart2
10.00
1.65
1
S S 2
3.70
S2 S
5.00
3
10.00
S
10.00
4
3.10
5
5.00
S3W
6 S
3.20
1.65
7
3.00 3.80 3.20
10.00
B E
LIGHTING LAYOUT
SCALE 1 : 100 m
1
R
1.65
WP WP
3
2
3.70
5.00
3
2
10.00
10.00
4
3.10
5
5.00
3.20
1.65
7
3.00 3.80 3.20
10.00
B E
POWER LAYOUT
SCALE 1 : 100 m
1.65
2
3.70
5.00
WALL MOUNTED
AC CONDENSER
2
2
CB
2ACP 3
10.00
10.00
4 1ACP
3.10
CB
AC CONDENSER
WALL MOUNTED
1
AC CONDENSER
3
WALL MOUNTED
3
CB
1
3ACP
5
5.00
3.20
WALL MOUNTED
AC CONDENSER
1.65
4
4
CB
7 4ACP
10.00
B E
A/C UNIT LAYOUT
SCALE 1 : 100 m
This Electrical Design is good only for the above connected loads.
Any additional electrical load connection in the future is not allowed,
Except redesign of electrical load system will be done.
PANEL: MDP CABLE: 3-14.0 sq. mm THNN + 1- 5.5 sq. mm THW MAIN: 90AT, 100AF, 3P, 230V, MCCB
CONDUIT: 25 mm dia. PVC PIPE ENCLOSURE: NEMA 1
PHASE: THREE MOUNTING: SURFACE
VOLTS: 230 LOCATION: KITCHEN, GROUND FLOOR
LOAD IN RATING CIRCUIT Size of Conductor
PROTECTION Size Of
CIRCUIT NO OF
CIRCUIT DESCRIPTION Conduit in
NO. OUTLET Volt- AMPERES CIRCUIT BREAKER SQ. MM Color Code
VOLT RATING SQ. MM THHN THW(G) MM ø
Amp AB BC CA
1 Lighting Outlet (6 F.L. + P.L.) 10 1000 230 4.35 15A,2P,230V, MCCB 2 – 2.0 PVC, 20 1R, 1B
2 Convenience Outlet 14 2520 230 10.96 20A,2P,230V, MCCB 2 – 3.5 + 2.0 (G) PVC, 20 1B, 1Y, G
3 Refrigerator Outlet (1.5 HP) 1 2300 230 10 40A,2P,230V, MCCB 2 – 3.5 + 2.0 (G) PVC, 20 1R, 1B, G
4 ACU Outlet (2 HP) 1 2760 230 12 50A,2P,230V, MCCB 2 – 5.5 + 3.5 (G) PVC, 20 1R, 1B, G
5 ACU Outlet (2 HP) 1 2760 230 12 50A,2P,230V, MCCB 2 – 5.5 + 3.5 (G) PVC, 20 1B, 1Y, G
6 ACU Outlet (2 HP) 1 2760 230 12 50A,2P,230V, MCCB 2 – 5.5 + 3.5 (G) PVC, 20 1Y, 1R, G
7 ACU Outlet (2 HP) 1 2760 230 12 50A,2P,230V, MCCB 2 – 5.5 + 3.5 (G) PVC, 20 1Y, 1R, G
8 SPARE 15A,2P,230V, MCCB
9 SPARE 20A,2P,230V, MCCB
10
TOTAL 16,860 230 26.35 22.96 24 90AT, 100AF, 3P, 3 – 14.0 + 5.5 (G) PVC, 25 1R,1B, 1Y,
230V, MCCB G
MAIN FEEDER and CURRENT PROTECTION COMPUTATION:
I FL = (26.35 x 1.732) + (25% x 12) = 48.638 Amperes
I CB = (26.35 x 1.732) + (250% x 12) = 75.638 Amperes
use: 3-14.0 sq. mm THNN + 1- 5.5 sq. mm THW in 25 mm dia, PVC PIPE
NOTE:
use: 90AT, 100AF, 3P, 230V, MCCB
G- Means Ground Wire
1R- Color RED
1B- Color BLUE
1Y- Color YELLOW
1G- Color GREEN
This Electrical Design is good only for the above connected loads.
Any additional electrical load connection in the future is not allowed,
Except redesign of electrical load system will be done.
EEUTI 130 – Engineering Utilities 1
Accomplishment Report
Group No: 4
Team Leader: Maglunog, Franchesca Lorren M.