HP compressor - Warnings:
NB: no starting torque check - motor data not available !
NB: please notice min. load discharge temperature (max 150 deg.C)
NB: Compressor weight incorrect - data missing.
NB: All data valid for fixed speed drive only !
NB: design limits check OK
The tolerance of all performance data issued for the products is according to EN-12900.
Measurement tolerances according to EN13771.
Data subject to change without notice.
Sabroe
Refrigeration Plant Computation
Version 33.00-2020/05/12
Operating conditions
suction pressure 3.48 bar_a
suction temperature -5.5 deg.C
suction specific volume 0.3528 m3/kg
enthalpy difference 1068.40 kJ/kg
(ref)
suction-side massflow 0.2175 kg/s
swept volume 332.51 m3/h
discharge pressure 15.77 bar_a
discharge temperature 122.2 deg.C
discharge temperature 155.4 deg.C
at min load
discharge specific 0.1155 m3/kg
volume
condenser subc. liq. 579.5 kg/m3
density
evaporator sat. liq. 645.4 kg/m3
density
pressure ratio (p2/p1) 4.53
cover cooling water 0.34 m3/h
flow
Sabroe
Refrigeration Plant Computation
Version 33.00-2020/05/12
SOUND DATA
PLANT DATA