Professional Documents
Culture Documents
Density/Area Method.: Dr. Awni Alkhazaleh
Density/Area Method.: Dr. Awni Alkhazaleh
a worst-case scenario would be to make the designer calculate all of the sprinklers
on the remote branch line. However, at a certain point, the fire is much more
likely to spread to areas under adjacent branch lines than to spread entirely under
one branch line. Part of the rationale behind design areas is an attempt to predict
where heat from a fire will travel. To provide an even greater factor of safety,
some insurance companies require the longer side of the design area to have a
dimension of 1.4√A. This more conservative approach, however, is not considered
necessary by NFPA 13.
The design area needs to start in the northwest corner of the building (most
remote from the water supply) and continue to the east, picking up all sprinklers
that cover territory within 40.25 ft (12.3 m) of the corner, as shown in Exhibit 22.5.
Note that the design area has to include the five sprinklers labeled as A, B, C, D, and
E. Using the S ×L rules of 8.5.2, dimension S for sprinkler E is 10 ft (3.05 m), allowing
sprinkler E to cover up to 5 ft (1.5 m) to its east, which, in this case, it will, adding a
safety factor along the branch line, resulting in a design area with a distance along
the branch line of 43 ft (13.1 m).
Sprinkler G covers an area of 66 ft2 (6.13 m2) and can be eliminated from the
design area, leaving a total design area of 1181 ft2 (109.7 m2). Sprinkler H in Exhibit
22.7 covers much more area than sprinkler G and cannot be eliminated, because it
would decrease the area to below 1125 ft2 (104.25 m2).
Gridded Systems
To determine the appropriate design area, 22.4.4.4 requires that an initial design
area be selected and that two additional areas be considered on either side of the
initially selected area. This approach results in three separate design areas that
overlap each other, as illustrated in Figure A.22.4.4.4. Design area A2 represents the
initially chosen design area. Hydraulic calculations for each of the three design
areas are required to determine the most demanding area. If the initially chosen
area (A2) is determined not to be the most demanding, then an additional area (A4)
adjacent to the area with the highest demand of the three (either A1 or A3) needs
to be calculated to verify that A4 is not more demanding. This technique is typically
referred to as “peaking the system.”
o Where sprinklers are installed under a sloped ceiling, the area shall be
calculated on a horizontal plane below the sprinklers.
o These tests are conducted at a minimum flow of 15 gpm (57 L/min) per
sprinkler. The pressure required to produce this flow through sprinklers with
a nominal K-factor of K-5.6 is approximately 7 psi (0.5 bar), as illustrated in
the equation that follows.