CONTROL SCHEMATIC DIAGRAM

FOR GENERATOR TRANSFORMER


18 MVA, 6.3/69kV, Dyn11

DAIHEN ELECTRIC CO.,LTD.

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
SH. DESCRIPTION DRAWING NO. REV.1 REV.2 REV.3 REV.4 REV.5

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
1. CONSTRUCTION OF CONTROL CABINET ( PANEL)
3.3 WIRING METHOD
(1) Internal wiring Duct or bundle wiring
EQUIPMENT TERMINAL BOX
(2) Interconnection wiring Conduit wiring
OUTDOOR TYPE
INSTALLATION
TRANSFORMER MOUNTING TYPE
4. CIRCUIT DISCRIMINATION
NATURAL VENTILATION (IP54)
TYPE 4.1 COLOR OF WIRE INSULATION
VERMIN PROOF , RAIN PROOF
CIRCUIT COLOR
(1) OUTSIDE BOARD / 3.2 mm.
DC. CIRCUIT GRAY (G)
THICKNESS OF SHEET STEEL (2) INNER PANEL / 3.2 mm.
(3) DOOR / 3.2 mm. AC. CIRCUIT 1 O BLACK (K)
AC. POWER, PT, CT PHASE 1 RED (R)
AC. POWER, PT, CT PHASE 2 YELLOW (Y)
2. PAINTING COLOR AC. POWER, PT, CT PHASE 3 BLUE (B)
AC. POWER, PT, CT NEUTRAL GREEN (GN)
EQUIPMENT TERMINAL BOX
CONNECTION TO EARTH GREEN/YELLOW (GY)
OUTSIDE SURFACE OF CABINET RAL7033
INSIDE SURFACE OF CABINET RAL7033 4.2 COLOR DISCRIMINATION OF PHASE OR POLE
SURFACE OF PANEL RAL7033
COLOR APPLIED FOR
RED (R) FIRST PHASE IN AC.
3. WIRING
YELLOW (Y) SECOND PHASE IN AC.
3.1 WIRING CONDUCTOR, THIRD PHASE IN AC.
BLUE (B)
All wiring will be made with stranded copper 600 V.
GREEN (GN) NEUTRAL PHASE IN AC.
grade polyvinyl chloride insulated wire. (Type IV)
WHITE (W) POSITIVE POLE IN DC.
3.2 WIRING CONDUCTOR SIZE
BLACK (K) NEGATIVE POLE IN DC.
CIRCUIT OF WIRING PLACE CABLE SIZE CLEAR (-) UNKNOWN PHASE

CT. CIRCUIT 4.0 sq.mm.


AC. POWER SOURCE LINE 4.0 sq.mm. 5. CONTROL POWER SUPPLY
DC. POWER SOURCE LINE 4.0 sq.mm. - AC.400/230V, 3∅, 4Wire, 50Hz.
- DC.125V.
WIRING TO EARTHING 4.0 sq.mm.

CONTROL CIRCUIT AND OTHER 2.5 sq.mm.

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
Handle with a key lock and key cover

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
GRAPHICAL SYMBOLS FOR ELECTRICAL ENGINEERING DIAGRAM DESCRIPTION IN THE SCHEMATIC DIAGRAM

DETAIL OF WIRE END

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
-26D
OIL TEMP. INDICATOR

OIL TEMP.
O/P PT100

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
BCT. FOR LV.NEUTRAL PROTECTION
PHASE N
CONNECTION RATIO CLASS BURDEN
S1n - S2n 100/1A 5P20 10VA

U2 U1
V2 V1
W2 W1
n

P.Nuttapol
P.Nuttapol
P.Panuwat
P.Panuwat
TB01 TB02 TB03
(26P) (26P) (9P)

NOTE : TB01-TB02 USED TERMINAL TYPE TX20,


TB03 USED TERMINAL TYPE URTK/S