TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0974


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy Fortune Marikina City Bank/Phase TR #1


Serial 836004291 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.5 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 26.6 D971
5. Neutralization Number mg KOH/g 0.0233 D974
6. Dielectric strength, 2.5mm gap kV 54.70 D877
7. Water Content ppm 20 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.025 D924
9. Dielectric constant 2.227 D924
10. Resistivity TΩ-m 0.51 D1169
11. Conductivity pS/m 1.97 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0974
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Rtemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004291

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 1ppm
Methane CH4 1
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 2
Acetylene C2H2 0
Carbon Monoxide CO 36
Carbon Dioxide CO2 775
Nitrogen N2 38676 EST. TCG (%) 0.06
Oxygen 02 18013 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 41 is calculated from the solubility factor of the gases
Total Gas Content 57504 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.52 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.43 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 8.42 CODE = 2 - Data is not definable using Roger’s Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.05

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 41ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0975


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #2


Serial 836004290 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 29.3 D971
5. Neutralization Number mg KOH/g 0.0251 D974
6. Dielectric strength, 2.5mm gap kV 46.00 D877
7. Water Content ppm 4 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.025 D924
9. Dielectric constant 2.225 D924
10. Resistivity TΩ-m 0.48 D1169
11. Conductivity pS/m 2.10 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0975
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Rtemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004290

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 3ppm
Methane CH4 0
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 2
Acetylene C2H2 0
Carbon Monoxide CO 86
Carbon Dioxide CO2 822
Nitrogen N2 46136 EST. TCG (%) 0.12
Oxygen 02 19434 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 90 is calculated from the solubility factor of the gases
Total Gas Content 66482 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.00 CODE = 5 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = -- CODE = 1 indicate below is considered less significant.
C2H4/C2H6 = -- CODE = 0 - Data is not definable using Roger’s Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.10 -CO/CO2>0.1 Higher than normal temperature is solid insulation

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 90ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0976


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL Mineral Oil
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #3


Serial 00079797 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 2.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 32.1 D971
5. Neutralization Number mg KOH/g 0.00425 D974
6. Dielectric strength, 2.5mm gap kV 36.66 D877
7. Water Content ppm 6 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.878 D924
9. Dielectric constant 2.140 D924
10. Resistivity TΩ-m 6.30 D1169
11. Conductivity pS/m 0.16 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0976
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Mineral Oil
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 00079797

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 234ppm
Methane CH4 37
Ethane C2H6 7 *Combustible gases

Ethylene C2H4 3
Acetylene C2H2 0
Carbon Monoxide CO 174
Carbon Dioxide CO2 1803
Nitrogen N2 73886 EST. TCG (%) 0.64
Oxygen 02 20028 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 455 is calculated from the solubility factor of the gases
Total Gas Content 96172 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.16 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.18 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 0.48 CODE = 0 - Normal Operation.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.10

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 455ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0977


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #4


Serial 836002961 kVA 500
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 35.2 D971
5. Neutralization Number mg KOH/g 0.00791 D974
6. Dielectric strength, 2.5mm gap kV 54.40 D877
7. Water Content ppm 8 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.011 D924
9. Dielectric constant 2.214 D924
10. Resistivity TΩ-m 0.80 D1169
11. Conductivity pS/m 1.24 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0977
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp.
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 500 SERIAL NO. 836002961

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 3ppm
Methane CH4 2
Ethane C2H6 2 *Combustible gases

Ethylene C2H4 2
Acetylene C2H2 0
Carbon Monoxide CO 62
Carbon Dioxide CO2 1813
Nitrogen N2 48001 EST. TCG (%) 0.09
Oxygen 02 17198 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 71 is calculated from the solubility factor of the gases
Total Gas Content 67084 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.94 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.94 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 0.67 CODE = 0 - Normal Operation.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.03

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 71ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0978


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #5


Serial 836004289 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 2.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 35.8 D971
5. Neutralization Number mg KOH/g 0.00974 D974
6. Dielectric strength, 2.5mm gap kV 41.50 D877
7. Water Content ppm 4 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.007 D924
9. Dielectric constant 2.218 D924
10. Resistivity TΩ-m 1.17 D1169
11. Conductivity pS/m 0.85 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0978
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004289

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 44ppm
Methane CH4 159
Ethane C2H6 61 *Combustible gases

Ethylene C2H4 0
Acetylene C2H2 0
Carbon Monoxide CO 56
Carbon Dioxide CO2 1818
Nitrogen N2 54658 EST. TCG (%) 0.24
Oxygen 02 19752 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 321 is calculated from the solubility factor of the gases
Total Gas Content 76548 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane >80ppm. Possible local overheating
Ethane >35ppm. Possible Overheating, Possible low energy spark.
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 3.60 CODE = 2 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.38 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 0.00 CODE = 0 - Slight Overheating <150C.
C2H2/C2H4 = -- CODE = 0
CO/CO2 = 0.03

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 321ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0979


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #6


Serial 836004322 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.5 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 36.2 D971
5. Neutralization Number mg KOH/g 0.0229 D974
6. Dielectric strength, 2.5mm gap kV 46.00 D877
7. Water Content ppm 3 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.013 D924
9. Dielectric constant 2.222 D924
10. Resistivity TΩ-m 0.92 D1169
11. Conductivity pS/m 1.09 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0979
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004322

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 0ppm
Methane CH4 2
Ethane C2H6 1 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 27
Carbon Dioxide CO2 699
Nitrogen N2 44276 EST. TCG (%) 0.04
Oxygen 02 20158 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 31 is calculated from the solubility factor of the gases
Total Gas Content 65165 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = -- CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.40 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 1.19 CODE = 1 - General Conductor overheating.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.04

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 31ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0980


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #7


Serial 836004227 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 4.0 D1500
2. Visual Examination Dark D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 34.3 D971
5. Neutralization Number mg KOH/g 0.0129 D974
6. Dielectric strength, 2.5mm gap kV 38.60 D877
7. Water Content ppm 4 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.014 D924
9. Dielectric constant 2.225 D924
10. Resistivity TΩ-m 0.82 D1169
11. Conductivity pS/m 1.23 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0980
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 8360043227

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 3ppm
Methane CH4 1
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 21
Carbon Dioxide CO2 594
Nitrogen N2 36687 EST. TCG (%) 0.04
Oxygen 02 16311 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 25 is calculated from the solubility factor of the gases
Total Gas Content 53618 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.27 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.00 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = -- CODE = 0 - Normal Operation.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.03

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 25ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0981


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #8


Serial 836002139 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 4.0 D1500
2. Visual Examination Dark D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 34.1 D971
5. Neutralization Number mg KOH/g 0.0161 D974
6. Dielectric strength, 2.5mm gap kV 38.30 D877
7. Water Content ppm 3 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.062 D924
9. Dielectric constant 2.234 D924
10. Resistivity TΩ-m 0.32 D1169
11. Conductivity pS/m 3.15 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0981
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836002139

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 0ppm
Methane CH4 0
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 21
Carbon Dioxide CO2 378
Nitrogen N2 35014 EST. TCG (%) 0.04
Oxygen 02 16534 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 23 is calculated from the solubility factor of the gases
Total Gas Content 51948 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = -- CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.00 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = -- CODE = 0 - Normal Operation.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.06

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 23ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0982


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #9


Serial 836004252 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.5 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 35.6 D971
5. Neutralization Number mg KOH/g 0.00582 D974
6. Dielectric strength, 2.5mm gap kV 39.60 D877
7. Water Content ppm 7 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.015 D924
9. Dielectric constant 2.219 D924
10. Resistivity TΩ-m 0.69 D1169
11. Conductivity pS/m 1.45 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0982
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004252

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 2ppm
Methane CH4 1
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 4
Acetylene C2H2 0
Carbon Monoxide CO 96
Carbon Dioxide CO2 2182
Nitrogen N2 40473 EST. TCG (%) 0.15
Oxygen 02 15222 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 104 is calculated from the solubility factor of the gases
Total Gas Content 57980 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.63 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.33 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 10.21 CODE = 2 - Data is not definable using Rogers Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.04

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 104ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0983


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #10


Serial 836002137 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.5 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 36.5 D971
5. Neutralization Number mg KOH/g 0.00589 D974
6. Dielectric strength, 2.5mm gap kV 41.70 D877
7. Water Content ppm 8 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.009 D924
9. Dielectric constant 2.214 D924
10. Resistivity TΩ-m 0.89 D1169
11. Conductivity pS/m 1.13 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0983
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836002137

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 2ppm
Methane CH4 0
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 36
Carbon Dioxide CO2 575
Nitrogen N2 32250 EST. TCG (%) 0.08
Oxygen 02 14753 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 39 is calculated from the solubility factor of the gases
Total Gas Content 47617 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.00 CODE = 5 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = -- CODE = 1 indicate below is considered less significant.
C2H4/C2H6 = -- CODE = 0 - Data is not definable using Rogers Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.06

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 39ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0984


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #11


Serial 836002962 kVA 500
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 4.0 D1500
2. Visual Examination Dark D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 22.7 D971
5. Neutralization Number mg KOH/g 0.0401 D974
6. Dielectric strength, 2.5mm gap kV 48.20 D877
7. Water Content ppm 4 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.033 D924
9. Dielectric constant 2.230 D924
10. Resistivity TΩ-m 0.374 D1169
11. Conductivity pS/m 2.74 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0984
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 500 SERIAL NO. 836002962

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 10ppm
Methane CH4 9
Ethane C2H6 4 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 144
Carbon Dioxide CO2 3410
Nitrogen N2 73520 EST. TCG (%) 0.15
Oxygen 02 17810 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 169 is calculated from the solubility factor of the gases
Total Gas Content 94910 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.91 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.47 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 0.20 CODE = 0 - Normal Operation
C2H2/C2H4 = 0.33 CODE = 0
CO/CO2 = 0.04

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 169ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0985


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL Mineral
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #13


Serial 836004192 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 0.5 D1500
2. Visual Examination Clear & Bright D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 34.0 D971
5. Neutralization Number mg KOH/g 0.00308 D974
6. Dielectric strength, 2.5mm gap kV 34.19 D877
7. Water Content ppm 17 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.122 D924
9. Dielectric constant 2.111 D924
10. Resistivity TΩ-m 9.12 D1169
11. Conductivity pS/m 0.11 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0985
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Mineral Oil
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004192

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 0ppm
Methane CH4 1
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 0
Acetylene C2H2 0
Carbon Monoxide CO 22
Carbon Dioxide CO2 673
Nitrogen N2 62045 EST. TCG (%) 0.02
Oxygen 02 30287 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 23 is calculated from the solubility factor of the gases
Total Gas Content 93028 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = -- CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.00 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = -- CODE = 0 - Normal Operation
C2H2/C2H4 = -- CODE = 0
CO/CO2 = 0.03

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 23ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0986


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #A


Serial 836004193 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.5 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 19.0 D971
5. Neutralization Number mg KOH/g 0.0502 D974
6. Dielectric strength, 2.5mm gap kV 45.30 D877
7. Water Content ppm 4 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.023 D924
9. Dielectric constant 2.228 D924
10. Resistivity TΩ-m 0.49 D1169
11. Conductivity pS/m 2.04 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0986
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004193

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 14ppm
Methane CH4 0
Ethane C2H6 4 *Combustible gases

Ethylene C2H4 2
Acetylene C2H2 0
Carbon Monoxide CO 315
Carbon Dioxide CO2 3395
Nitrogen N2 293450 EST. TCG (%) 0.08
Oxygen 02 79724 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 335 is calculated from the solubility factor of the gases
Total Gas Content 376904 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.00 CODE = 5 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = -- CODE = 1 indicate below is considered less significant.
C2H4/C2H6 = 0.60 CODE = 0 - Data is not definable using Roger’s Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.09

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 335ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0987


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #B


Serial 836002138 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 4.5 D1500
2. Visual Examination Dark D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 35.0 D971
5. Neutralization Number mg KOH/g 0.0287 D974
6. Dielectric strength, 2.5mm gap kV 52.80 D877
7. Water Content ppm 3 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.034 D924
9. Dielectric constant 2.209 D924
10. Resistivity TΩ-m 0.34 D1169
11. Conductivity pS/m 2.92 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0987
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836002138

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 2ppm
Methane CH4 2
Ethane C2H6 1 *Combustible gases

Ethylene C2H4 4
Acetylene C2H2 0
Carbon Monoxide CO 88
Carbon Dioxide CO2 3210
Nitrogen N2 61135 EST. TCG (%) 0.09
Oxygen 02 22901 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 96 is calculated from the solubility factor of the gases
Total Gas Content 87342 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.85 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.41 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 4.80 CODE = 2 - Data is not definable using Roger’s Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.03

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 96ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0988


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #E


Serial 836004226 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 2.5 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 34.7 D971
5. Neutralization Number mg KOH/g 0.00950 D974
6. Dielectric strength, 2.5mm gap kV 50.30 D877
7. Water Content ppm 3 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.020 D924
9. Dielectric constant 2.224 D924
10. Resistivity TΩ-m 0.50 D1169
11. Conductivity pS/m 2.02 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0988
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836004226

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 5ppm
Methane CH4 4
Ethane C2H6 3 *Combustible gases

Ethylene C2H4 4
Acetylene C2H2 0
Carbon Monoxide CO 56
Carbon Dioxide CO2 1182
Nitrogen N2 47749 EST. TCG (%) 0.09
Oxygen 02 13213 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 71 is calculated from the solubility factor of the gases
Total Gas Content 62216 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.68 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.81 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 1.24 CODE = 1 - General Conductor Overheating.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.05

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 71ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0989


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL RTemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #F


Serial 836002240 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 2.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 34.0 D971
5. Neutralization Number mg KOH/g 0.00409 D974
6. Dielectric strength, 2.5mm gap kV 44.70 D877
7. Water Content ppm 4 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.011 D924
9. Dielectric constant 2.213 D924
10. Resistivity TΩ-m 0.78 D1169
11. Conductivity pS/m 1.28 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0989
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL RTemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 836002240

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 1ppm
Methane CH4 0
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 50
Carbon Dioxide CO2 700
Nitrogen N2 41889 EST. TCG (%) 0.08
Oxygen 02 14561 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 52 is calculated from the solubility factor of the gases
Total Gas Content 57202 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.00 CODE = 5 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = -- CODE = 1 indicate below is considered less significant.
C2H4/C2H6 = 2.96 CODE = 1 - Data is not definable using Roger’s Ratio.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.07

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 52ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0990


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL Biotemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #RC


Serial 12JC62704001 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 22.8 D971
5. Neutralization Number mg KOH/g 0.0526 D974
6. Dielectric strength, 2.5mm gap kV 49.00 D877
7. Water Content ppm 50 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.430 D924
9. Dielectric constant 3.090 D924
10. Resistivity TΩ-m 0.032 D1169
11. Conductivity pS/m 30.86 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0990
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Biotemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 12JC62704001

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 7ppm
Methane CH4 4
Ethane C2H6 3 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 90
Carbon Dioxide CO2 1742
Nitrogen N2 68524 EST. TCG (%) 0.10
Oxygen 02 15765 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 105 is calculated from the solubility factor of the gases
Total Gas Content 86136 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.58 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.67 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 0.26 CODE = 1 - Normal Operation.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.05

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 105ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0991


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL Biotemp
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR #RD


Serial 12JC62704002 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 3.0 D1500
2. Visual Examination Clear D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 2.9 D971
5. Neutralization Number mg KOH/g 0.0447 D974
6. Dielectric strength, 2.5mm gap kV 44.60 D877
7. Water Content ppm 55 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.349 D924
9. Dielectric constant 3.089 D924
10. Resistivity TΩ-m 0.039 D1169
11. Conductivity pS/m 25.77 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0991
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Biotemp
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. 12JC62704002

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 5ppm
Methane CH4 7
Ethane C2H6 5 *Combustible gases

Ethylene C2H4 1
Acetylene C2H2 0
Carbon Monoxide CO 113
Carbon Dioxide CO2 1738
Nitrogen N2 55826 EST. TCG (%) 0.15
Oxygen 02 11736 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 131 is calculated from the solubility factor of the gases
Total Gas Content 69431 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 1.32 CODE = 1 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.69 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = 0.29 CODE = 0 - Slight Overheating <150C.
C2H2/C2H4 = 0.00 CODE = 0
CO/CO2 = 0.07

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 131ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which
the sample was taken. The analysis, opinions, or interpretations contained in this report are based upon materials and information supplied by the client.

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

TRANFORMER OIL TESTING LABORATORY


OIL QUANTITY TEST REPORT

CUSTOMER PMFTC, INC. SAMPLE NO. 22-0992


ADDRESS PLANT C&D Champaca St. Brgy TYPE OF OIL Silicone
Fortune Marikina City
CONTACT PERSON Engr. Jansean Jaylo CONTAINER 1 liter bottle
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED O4/30/22
SITE & NAMEPLATE DATA

Location Brgy. Fortune Marikina City Bank/Phase TR-F-TD-C


Serial PA10002 kVA 1000
Make Oil Temp.
Year Built Notes
Main/LTC
TEST DESCRIPTON UNITS RESULT ASTM METHOD
1. Color L 0.5 D1500
2. Visual Examination Clear & Bright D1524
3. Turbidity NTU D6181
4. Interfacial Tension dynes/cm 36.5 D971
5. Neutralization Number mg KOH/g 0.00265 D974
6. Dielectric strength, 2.5mm gap kV 43.62 D877
7. Water Content ppm 55 D1533B
8. Oil Power Factor @60Hz, 25℃ % 0.001 D924
9. Dielectric constant 2.634 D924
10. Resistivity TΩ-m 13.8 D1169
11. Conductivity pS/m 0.072 Calculated
12. Oil Power Factor @60Hz, 100℃ % D924
13. Oxidation inhibitor content % D2668
14. Dissolved Decay Products Abs/nm D6802
15. Specific Gravity D1298
16. Viscosity 40℃ cSt 3D445
17. Viscosity 100℃ cSt D445
18. Oxidation stability, 72hours
• Total acid number mg KOH/g D2440
• Sludge content by mass %
19. Corrosive sulfur D1275B
20. Flash point ℃ D92
21. Pour point ℃ D97
22. 2-Furfuraldehyde in oil µg/I D5837
23. Est. Ave. Degree of Polymerization DP Chendong

Certified by:

Richard Sy

PLANT & OFFICE ADDRESS: Lot 8, Block 2, Alcantara St., Monte Vista Subdivision, San Jose, Rodriguez Rizal
TELAFAX: (02) 997-4239/942-4835, EMAIL: headoffice@electromechtech.ph WEBSITE: www.electromechtech.ph
•TRANSFORMER •GENERATOR •REWINDING •INSTALLATION •DESIGN

LABORATORY RESULT

NAMEPLATE DATA:
CUSTOMER PMFTC, INC. SAMPLE NO. 22-0992
ADDRESS PLANT C&D Champaca St. Brgy Fortune TYPE OF OIL Silicone
Marikina City
CONTACT Engr. Jansean Jaylo CONTAINER 1-LITER BOTTLE
PERSON
PROJECT Comprehensive Dissolve Gas Analysis DATE TESTED 04/30/2022
KVA 1000 SERIAL NO. PA10002

All detection limits are less than 1ppm Note: Interpretations and diagnostics developed using mineral oil.
DISSOLVE GAS RESULTS – ASTM D 3612

Sampling date 00/00/00


Hydrogen H2 4ppm
Methane CH4 4
Ethane C2H6 0 *Combustible gases

Ethylene C2H4 0
Acetylene C2H2 0
Carbon Monoxide CO 205
Carbon Dioxide CO2 2250
Nitrogen N2 136421 EST. TCG (%) 0.10
Oxygen 02 43689 Estimated Total Combustible Gas (TCG) if
transformer has a gas space over the oil. This value
Total Diss. Comb. Gas TDCG 213 is calculated from the solubility factor of the gases
Total Gas Content 182572 involved.

Interpretive or Key Gas Method (Present sample only) indicates:


Hydrogen within normal limits (<1500ppm)
Methane within normal limits (<80ppm)
Ethane within normal limits (<35ppm)
Ethylene within normal limits (<150ppm)
Acetylene within normal limits (<7ppm)
Carbon Monoxide within normal limits (<1000ppm)
Carbon Dioxide within normal limits (<1000ppm)

Rogers’ Ratios (present sample only) indicates:


CH4/H2 = 0.89 CODE = 0 - since TOTAL TDCG <500ppm, the Rogers’ Ratio
C2H6/CH4 = 0.00 CODE = 0 indicate below is considered less significant.
C2H4/C2H6 = -- CODE = 0 - Normal Operation
C2H2/C2H4 = -- CODE = 0
CO/CO2 = 0.09

IEEE/ANSI C57.104 Guideline (Requires TDCG Level from Previous Sample) suggests:
TDCG Level: 213ppm Rate----- ppm/day
➢ Sample interval:-------
➢ Operating Interval:
➢ No Prior Sample Found for this Sample. Therefore, cannot perform Guideline.
Note: our test result relate only to the sample tested. We do not imply that the contents of the sample received by this lab are the same as all such materials in the environment from which