1. PURPOSE
The purpose of this calculation is to verify the cable size selected considering load
current, steady state voltage drop limitation, short circuit current and motor starting
voltage drop limitation for THE SOUTH PARS FIELD DEVELOPMENT PHASES 4&5
ONSHORE FACILITIES PROJECT at ASSALUYEN, IRAN.
48 VDC, unearthed
Page 4 of 11
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
IRAN - South Pars Gas Field - Phase 4 & 5
Doc. N. NC 2017 120 1630 004 Rev. 2
Where two or more cables are connected in parallel in the same phase or pole of the
system, measures shall be taken to ensure that the load current is shared equally
between them.
3.5.2 Armour
Armour shall mechanically protect the cable and shall be made up of double galvanised
steel tape or steel wire armour. Non magnetic armour shall be used for single core
cables.
3.5.3 Conductor
Conductor shall be stranded. Conductor shall be class 2 for cables for fixed
installations and class 5 for flexible cables feeding mobile equipment.
3.5.4 Oversheath
All cables shall be aliphatic hydrocarbon, sunlight resistant, flame retardant and low
density of smoke according to IEC 332 and IEC 1034.
Circuits for safety requirements shall be compulsorily fire resistant. Fire resisting
cables shall withstand to a 1000℃ temperature during 30 minutes (with test
procedure requirement of the IEC 331) and shall continue to conduct electric power
during this period.
Page 5 of 11
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
IRAN - South Pars Gas Field - Phase 4 & 5
Doc. N. NC 2017 120 1630 004 Rev. 2
4. BASIS OF CALCULATION
4.1 Basis
A cable selection shall be carried out with respect to the most stringent of the following
criteria.
For XLPE or EPR core insulation, maximum core temperature is 90℃ and the current
carrying capacities are the following :
4.3.2 Rating factor for Soil thermal resistivity .(Refer attachment #5)
On the basis of IEC-287 9.6.1 the site conditions of soil thermal resistivity is applied as
2.5 K.m/W
Admissible ampacities are given for 2.5 K.m/W in para. 4.2.1. The cables shall then
be overrated by : KSL = 1.0
Page 6 of 11
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
IRAN - South Pars Gas Field - Phase 4 & 5
Doc. N. NC 2017 120 1630 004 Rev. 2
- LV cables (0.4kV)
Table 52-E4 of IEC 364-5-523, installation method L – 3 ladders with
vertical spacing between ladder of 300 mm - over 9 touching cables in
single layer formation on each cable ladder. (Attachment #6)
KLA = 0.70
Page 7 of 11
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.