Professional Documents
Culture Documents
EASYTRONIC 2 Controller 000110062 - 23!09!14
EASYTRONIC 2 Controller 000110062 - 23!09!14
EASYTRONIC 2 Controller 000110062 - 23!09!14
Rotar Plus
30-40 TF
STANDARD EQUIPMENT
Your compressor is delivered with the following accessories:
users guide
anti-vibration elements
key to open panels / electric box Allen wrench to remove the back panel
oil/condensate exhaust tube
Check that standard equipment is supplied with the machine. No claims after delivery will be accepted.
Danger! Hot gas or harmful gas within working Prohibited! Do not use water on electric
area equipment to extinguish fire.
PRODUCT IDENTIFICATION
The compressor Your have purchased has its own CE plate showing the following data:
1) Manufacturers data
2) CE mark year of manufacture
3) TYPE = name of the compressor
CODE = compressor code
SERIAL NO. = serial number of the compressor You have purchased (to be always mentioned when calling for technical
assistance)
4) air delivered by the compressor expressed in (l/min) and (cfm)
5) max. operating pressure (bar and PSI) compressor noise level in dB(A)
6) electric data: voltage (V/ph), frequency (Hz), absorption (A) - power (HP and kW), rotations per minute (Rpm).
7) other approvals
TECHNICAL DATA
"+ ."# . "+ ."# .
4' >4 4' >4
!" #!$ $"
%&'()")* ++ "$! "+ #)" +! +)"
(,
(, - . @ @
- / )) )+
0 1 231 "# ) "
4- 5 61 ++! ++!
( 1 6 # #
788 ) A"=+= ) A=+A=
5 29 "" +
5 29 " +)
788 8 8 &
8 4 4
4 8 #+ +
' ))+ )
'. 1 / ) )
/
: )%;&:7<0(* =%* "
8 / )) ))
>1 / . .
>1 8 . "@# ++
'- )# )#
'. 581 )@ )@
' 581 )+@ )+@
2- 581 .@ .@
? )) ))
) )
)) ))
91 2 + #
8 82- 0 +#B +#B
WORKING TIMES
Automatic mode
The compressor operation is controlled by the pressure transducer, which stops the machine when the max. pressure
value is reached and starts it again after the pressure has decreased to the min. set value.
However, the machine stop is of the delayed type, that is it does not occur exactly at the same time when the max. pressure
value is reached but after a certain time, during which no air is taken (see no. 7 of above paragraph).
Standard setting is 20 seconds, but it is recommended to check that number of start-ups per hour does NOT exceed max
number of 10. Should it be a higher value, it is recommended to set longer loadless operation time (see no. 7, Modifiable
parameters).
PRESSURE REGULATOR
The User should install a pressure regulator downstream of the compressor to set the power line according to his/her needs.
REMOTE ON/OFF
The compressor can also be switched on or off using the remote control optional software (remote control will be active
only if the control unit at the machine is set to ON).
This function can also be managed through the remote terminal on the terminal box. In such case, manual controls will
be excluded. If the compressor starts up unexpectedly, persons happening to be nearby could be harmed or injured. With this
in mind, THIS USE IS GENERALLY NOT RECOMMENDED. The manufacturer will not be liable for any damages.
Any change must be carried out by a qualified technician.
MODIFIABLE PARAMETERS
Pressing the key with the machine OFF, the operating parameters menu will be displayed; in certain cases a password
is required in order to make changes. The menu is scrolled using the keys and .
0) control unit ID (service password): selects the identification code of the control unit; if several compressors are connected
to the same RS485 line, multiple IDs can be selected.
1) Pre-alarm time lapse (service password): each hour of operation clocked by the machine is counted down automatically;
when the count reaches 0, the control unit trips a Maintenance alarm.
The count, preceded by a minus sign (-), indicates how many hours have elapsed since the last maintenance alarm; the keys
and can be used to set a new value (entering the new value has the effect of overriding the previous alarm).
STANDARD SETTINGS
MODIFIABLE PARAMETERS Min. Max. Standard Min. Max. Standard
Oil temperature pre-alarm (differential) °C 0 20 5 Maximum permissible pressure bar 0 15 11
Maximum oil temperature °C 0 150 110 Maximun alarm pressure bar 0 16 13
Minimum oil temperature °C -14 0 -7 Load (CHARGED) delay sec. 0 200 10
No-load (EMPTY) time sec. 1 250 20 Internal phase sequence control YES NO YES
Maintenance pre-alarm Ore 0 32768 4000 Language ITA
Fan temperature °C 0 150 80 Display contrast level 1 20 5
Automatic start YES NO NO Enable RS485 SI NO SI
Pressure sensor YES NO YES
PSI/BAR PSI BAR BAR
No-Load/operating pressure set point bar 0 15 10
Load/pressure differential set point bar 0 15 8,5
The oil reaches the compressor (4) mixing with the intake air and creating an air/oil mixture which ensures the seal and the
lubrication of the moving parts of the compressor.
The air/oil mixture returns to the tank (6) where the air is pre-separated through spinning and is finally separated from the
oil by the oil separator filter (13).
As a result, the tank (6) will deliver only air to radiator (11) through tube (15). Air is then conveyed to mains through a cut-
off cock (16).
START-UP
FIRST START-UP
Before starting the machine up for the first time, make sure that:
the mains voltage is the same as the voltage on the CE plate;
the electric connections have been made using cables of proper cross-section;
the (wall) main power switch has suitable fuses;
the oil level is over the minimum level - top up with the same type of oil if necessary;
the air outlet cock is completely open.
Only specialized technicians can start the compressor (on-site testing) for the first time.
If the machine does not start and the display shows the alarm message Wrong direction of rotation, proceed as
follows:
break power supply through the wall switch;
open the electric box door and reverse the two phases in the terminal board;
close the door, power on and start the machine.
Display status at start (shown for 5 seconds) Display status during normal operation
compressor
status
Press the key to see hours and minutes operation; the information is displayed for 20 seconds.
Maintenance table
The maintenance operations indicated in bold type must be performed at least once a year, even if the machine has
not been run for the amount of hours prescribed for such maintenance.
In order to assure the correct functioning of the compressor, the following items must be checked after the first one
hundred hours of operation:
Oil level: refill, if needed, with the same type of oil.
Make sure that the screws are still tightly screwed: in particular those of the high voltage electrical contacts.
Check to make sure, visually, that all of the connecting parts are still firmly in place.
Check the air temperature of the immediate area.
CLEAN RADIATORS
For cleaning, proceed as follows:
remove back and upper panel from compressor cabinet;
place a protective plastic sheet under radiator fins;
spray (spray gun + solvent) from the outside towards the inside;
check that air flows freely through radiator.
10
CHANGE OIL (FIG. 7)
When the compressor is still warm, i.e. over 70°C.
Always blow off air from the oil separator tank before topping up: slowly
unscrew the cock (A) until all air has blown off and then screw it again.
Unscrew the plug of the filler (D), connect the hose to the cock (C) and let
all oil flow into a collection container. When finished, disconnect the hose.
Pour fresh oil through the filler (D) - quantity for complete filling: 6 liters.
Fit the plug.
Power the machine on.
Start the machine and wait for 5 minutes, then stop the machine.
V 400 / Hz 50 V 400 / Hz 60
Rotar Plus 3008 3010 3013 3008 3010
frequency (Hz) 68 71 71 72 72
Rotar Plus 4008 4010 4013 4008 4010
frequency (Hz) 87 81 81 78 79
REPLACE HOSES
Loosen hose fittings, replace the hose and then tighten the fittings.
Then follow last steps for oil change.
Thermostat radiator oil tube
Radiator thermostat oil tube
Thermostat oil separator tank oil tube
Min. pressure valve radiator air tube
Screw compressor oil separator tank air tube
Motor stop due to thermal relay Voltage too low Check voltage, press Reset and start once again
tripping
Overtemperature Check motor absorption and check relay settings. If absorption is
OK, press Reset and start once again
High oil consumption Defective drainage Check oil drainage tube and non-return valve
Oil level too high Check oil level and drain some, if necessary
Oil leakage from suction filter Suction regulator does not close Check regulator and solenoid valve
Safety valve open Pressure too high Check setting of pressure switch
Suction regulator does not close Check regulator and solenoid valve
at the end of the cycleI
Thermostat faulty Replace thermostat, press Reset and start once again
Low compressor efficiency Belt is slack Stretch the belt, press Reset and start once again
The compressor is running but Regulator is closed and does not Remove the suction filter and check if regulator can be manually
does not compress air open because it is dirty opened. Remove and clean, if necessary.
Regulator is closed and does not Ensure that signal between pressure switch and solenoid valve is
open because it receives no available. Replace part, if damaged.
command signal
The compressor compresses air Regulator is open and does not Remove the regulator and clean
beyond set max. pressure close because it is dirty
Regulator is open and does not Ensure that signal between pressure switch and solenoid valve is
close because it receives no available. Replace part, if damaged.
command signal
Compressor does not restart Oil separator filter clogged Change oil separator filter
Min. pressure valve does not Remove and clean the valve. Replace the seal, if necessary
close perfectly
Oil inside cabinet Leakage from tubes Tighten fittings and/or replace damaged tubes
Plus 30 Plus 40
230V 400V 230V 400V
TC1 Transformer pr.0/230/400 sec.0/230/0/24 100/150/200VA
TC2 Transformer pr.0/230/400 sec.0/6
SB Emergency button + n.2 NC 230V 10A
FU1-FU2 Fuses6,3x32 GF 4A 500V
FU3 Fuses 6,3x32 GF 1,6A 500V
FU4-FU5-FU6 Fuses 6,3x32 GF 1A 500V
FU7 Fuses 6,3x32 GF 500 mA 500V
KM1 Line contactor 230V 50/60Hz 22 kW * 15kW * 30kW * 18,5 kW *
KM2 Delta contactor 230V 50/60Hz 22 kW * 15kW * 30kW * 18,5 kW *
KM3 Star contactor 230V 50/60Hz 22 kW * 15kW * 30kW * 15kW *
FR Thermal relay reset MAN/AUT - 1L+1R (40-50) (22-32) (45-63) (28-40)
YV Solenoid valve 220/230/VAC 50/60 Hz 15VA
SP1 Minimum pressure switch 1NC 250VAC
SP2 Pressure switch for oil separator filter 1NC 250VAC
SP3 Pressure switch for air filter 1NC 250VAC
BP Pressure transducer 0-16 bar 4-20 mA
D Electronic controller Easytronic II 24VAC
ST Thermal feeler for electronic controller
Motor cable cross-section (sq mm) 7x16 7x6 7x25 7x10
(*) = 400V AC3