1.Scope of supply
* High Voltage Reactor YKTZ-7000kVA/350kV
* Excitation Transformer EVT-200kVA/0.5kV
* Double Shielded Isolation Transformer DSIT-200kVA/0.38kV
* Double Shielded Isolation Transformer DSIT-10kVA/0.22kV
* High Voltage Filter HVF—350kV/40A
* Calibration Injection Capacitor CIC—350kV/100pF
* Low Voltage Filter LVF-400A/0.5kV
* Low Voltage Filter LVF-50A/0.22kV
*Control Filter CPF-25 *1A/0.22kV
* Voltage Regulator TDG-200kVA/0.5kV
* Digital Partial Discharge Detector DPD-2007
* Power Separation Filter CVD-350/1000
* Computer Control Desk PDTD-7000kVA/350kV
* Cable Test Oil Termination CT-100,CT-35
* Cable Test Water Termination CT-350
*Water Treatment Equipment TD-MB-Ⅲ
* Cooling Water Equipment KT-03A
* Shield Room SR—20×10×7(h)
* Control Room and insulate base
* Discharge bar
2.System Description
* Input:200kVA ,380V,526A,50Hz,
* Output:Tap 1:7000kVA,350kV, 20A
For the routine test of 220 kV cable max cross 1500mm2 , longest length
1000 meter.
Tap 2: 6000kVA, 200kV, 30A
For the routine test of 110kV cable max cross 1000mm2 , longest length
2000 meter.
Tap 3: 4000kVA, 100kV, 40A
For the routine test of 35kV cable max cross 630mm2 , longest length 3000
meter.
* The max noise: <80dB(four meter from reactor)
* Character Factor Q:≥ 40
* Accuracy of Voltage measurement:≤±3%(From 10%-100% range according to
IEC-60060-1)
* Accuracy of PD measurement: ≤±l0%
* Accuracy of PDSL:≤±2.5 meter or≤±1% of cable length ,
* System PD leve1:< 2pC after HV Filter,at 80% rated output voltage
* Attenuation effect of PD shielded room: from 15kHz-1MHz,>60dB(one meter
inside the main door)
* Insulate resistance of insulate base:>1000MΩ
* Load capacity:one hour on, one hour off, 8 times one day
* Circumstance condition:temperature : 0℃-40℃
Humidity: less than 85% at 20℃
Altitude: less 1000 meter
Indoor
* The power supply of the test system should be separated from the power supply of
other equipments in the factory
* The ground resistance of the test system should be under 1Ω
3. Technology Specifications
* High Voltage Reactor
YKTZ-7000kVA/350kV
YKTZ-7000kVA/350kV high voltage
reactor is the main transformer of this system.
HV reactor and test cable constitute series
resonant circuit. HV reactor is made of high
quality silicon steel, precision ball bearing pole. It has the specification of low loss,
high Q value, low PD level. The mail specification is as follow:
Rated output: Tap1: 350kV,7000kVA,0.01-0.18μf
Tap2: 200kV, 6000kVA,0.02-0.47μf Tap3
: 100kV, 4000kVA,0.06-1.27μf
Mechanical driven system: precision ball bearing pole
Character factor Q:≥40
With a PD free HV switch of 350kV-200kV-100kV
Parallel tap function for short length cable test
Rated voltage:220V;
Rated current:1A;
Work channel:25 lane;
Attenuation effect: from 15kHz-1MHz≥60dB;