Professional Documents
Culture Documents
MS550-13481 Atlantis Marine Power 3069-62836
MS550-13481 Atlantis Marine Power 3069-62836
Technical Manual
Vessel Specifications
ClearCommand Specifications:
Table of Figures
Figure 1 - Processor 4
Figure 2 – Harness Connector Plugs 6
Figure 3 – Power Source 6
Figure 4 - Processor Dimensions 7
Figure 5 - Plug Removal and Cable Grip Installation 9
Figure 6 - Terminal Connection 10
Figure 7 - Start Interlock Connections 11
Figure 8 - Control Head Connections for Remote Stations Facing Aft 14
Appendix A
Parts List
Control Head Sheets
Watertight Enclosure
Bonding
References
Parts Source
Checkout Sea Trial Report
Appendix B
Trouble Shooting
Appendix C
System Drawing 11247, 3 pages
Page iii
Page iv
1. INTRODUCTION
1.1 THIS MANUAL
The purpose of the ClearCommand System manual is:
Ø Operation (Section 2) Ø Adjustments (Section 6)
Ø Installation (Section 5) Ø Trouble Shooting Reference
(Appendix B)
Keep this Manual on the vessel for future reference.
Page 1
Ø One Two-conductor electric Ø One Serial
cable for Start Interlock Communication Wire
connection Harness (Twin Screw) and
Ø One Throttle Wire Harness One Triple Screw Serial
for Processor engine interface Communication Wire
connection Harness (Triple Screw) for
Processor to Processor
interconnection
During Installation and Testing, take special care to verify all
wiring is to specifications, terminations are correct, and that
all Notes in Appendix C Drawing Notes are followed.
2. OPERATOR INSTRUCTIONS
2.1 DC POWER ON
When control system DC power is turned ON:
Ø Intermittent tone will sound at all remote stations
indicating that no station has command. (refer to Section
2.4)
To take command at a remote station:
Ø All remote station Control Head lever(s) must be in the
Idle position. Refer to Control Head Sheet of the System
Drawing.
Ø Operator must depress the station transfer button on one
of the Control Heads for at least 1/2 second.
The tone will stop at all remote stations and the red indicator
light will be lit at the Station-in-Command.
NOTE: Only one remote station has command at a time.
Page 2
2.3 STATION TRANSFER
When transferring command from one remote station to
another:
A) Leave all of Control Heads levers of the Station-in-
Command in any position.
B) Place all of the Control Heads levers of the station taking
command into the Idle position.
C) At the station taking command depress and hold for one
second one of the station transfer buttons.
Ø The red indicator will light on the Control Heads
indicating the station has taken command.
Ø The Control System will remain unchanged for one
second after the red indicator lights to allow the
operator time to move the Control Heads levers to a
position approximately matching the last command
setting.
2.4 CONTROL HEAD TONES
Ø Low Repetition Rate Tone is normal when DC power is first
applied to ClearCommand. This tone indicates the Processor
is in Idle, and the operator can take command at a remote
station.
If this tone occurs during operation, refer to Appendix
B Trouble Shooting Section.
Low Repetition Rate Tone is also heard during Setup
Mode. During the Setup procedure when the station transfer
button is depressed to gain command at a remote station to
aid in the adjustment setting.
If this tone occurs during operation, refer to Appendix
B Trouble Shooting Section.
Ø Steady Tone signals a voltage problem or a component has
failed. Confirm the voltage is steady between 12 and 24
volts DC, and that there is not a momentary voltage drop.
If tone continues, refer to the Appendix B Trouble
Shooting.
Ø Repetitive Signal - Three Short - One Long is used to
indicate a Control Head is dysfunctional due to loose or
unconnected cable connections.
Page 3
Refer to Appendix B Trouble Shooting Section.
2.5 SYNCHRONIZATION (TRIPLE SCREW)
The Control Head levers are in the synchronization range
when the Processors are commanding:
Ø At least 10 percent of the speed range
Ø The commanded throttles are within 10 percent of
equal RPM
The Processor’s throttle signals are compared and then
matched. The Serial Communication Wire Harnesses
interconnect the Processors, which exchanges the data
necessary to allow all the engines to synchronize.
A green indicator light located on the Control Head of the
Station-in-Command indicates engine synchronization:
Ø When the green light is BLINKING, system is working
to synchronize.
Ø When the green light is OFF, no synchronization.
Ø When the green light is ON, synchronization.
When in the Synchronization Mode:
Ø Both Control Head levers have full command of
throttle
Ø Synchronization can be disabled while in the
synchronization range by depressing for one-second
one of the transfer buttons at the Station-in-
Command.
Ø Synchronization can be re-enabled by matching all of
the Control Heads levers and then depressing one of
the transfer buttons for one-second again.
3. REQUIRED PARTS AND TOOLS
3.1 PROCESSOR
Ø One Processor required per engine
(refer to Figure 1)
Ø Mounting Hardware is installer
supplied.
Ø Included with the Processor:
[ Wago Tool 11008-
Ø Saw (appropriate type of saw for cutting material Control Head will be mounted on)
Recommendations:
10.71
Ø Refer to Figure 4 for (272mm)
Processor dimensions.
Ø Processors are spray proof, 6.70
(170,2mm)
but must not be immersed.
Ø An engine room location of
the Processor is preferred.
ü If the engine room is too 3.20
small, locate in any area (81,3mm)
Page 7
4.2 REMOTE CONTROL HEAD LOCATION
Refer to Control Head sheet of the System Drawing for
mounting specifications.
When properly mounted on a console, the Control Head is
watertight from the top. An adhesive gasket must be used to
seal the Control Head to the mounting surface. However,
below the mounting surface the Control Head needs
protection from water or spray.
NOTE: If a Control Head is mounted weather exposed from the underside, consider
using a Watertight Enclosure. Reference Appendix A Watertight Enclosure
for specific information.
5. INSTALLATION
NOTE: Before starting the actual installation of ClearCommand, make sure you have
the correct parts and tools on hand. See Section 3. Read ALL the
instructions pertinent to each part before beginning the installation of that
part.
Page 8
When installing the eight-conductor cable, support the cables
using clamps or straps not more than 18 inches (0,5m) apart,
unless contained in a conduit.
Install each cable so it is protected from physical damage.
5.2 PROCESSOR
A) Secure the Processor using 1/4 inch or M6 fasteners.
B) Remove the Processor cover.
C) Connect the wrist strap to your person, and the ground
connector to the Processor frame.
CAUTION: When not working on the Processor, keep the cover in place to prevent
damage to circuits.
Cable Hole
Plug Entrance
Body 11010-
DC Power Seal
Cable Cable Grip Push
Body
Watertight
Cable Grip
Page 9
D) (9,5mm) on each wire.
Locate the WAGO Tool that is taped to the relay on the
G)
Terminal 8 on the station terminal strip.
The shielding drain wire MUST NOT touch any other components.
NOTE: Bring the other station's eight-conductor cables in the same way, and
Appendix C)
Power Cable
When connecting the DC power cable to the Processor be sure the
power is OFF.
Page
B) Install the power cable grip in the Processor enclosure.
(refer to Figure 5)
C) Connect the two-conductor cable to the Processor.
Refer to the Drawing in Appendix C for power
connection points.
D) Feed through a little slack cable and tighten the cable
grip.
E) Tie wrap the power cable to the Processor frame.
NOTE: Repeat for all Processors. Ensure all connections are as indicated on the
Drawing in Appendix C.
Repeat for all Processors. Ensure all connections at the Processor are as
indicated on the Drawing in Appendix C.
S COMMUNICATION IRE H
For applications with multiple Processors a Serial
Communication Wire Harness needs to interconnect the
B)
this application (refer to the Notes page of the System
Drawing).
Throttle Wire Harness
Page 12
Connect the plug end of the Throttle Wire Harness
CAUTION: When connecting the plugs, ensure that the release buttons are
plugs, the release buttons MUST be depressed and held until plug is
disconnected. Refer to Figure 2, page 6.
12345678 12345678
Astern
Orange
Orange
Yellow
Brown
Yellow
Brown
Green
Green
Black
Black
Blue
Blue
Red
Red
Fore Ahead
Violet Violet
10987
For dual lever Control Head remote stations that have the
user facing aft:
Ø Reverse connections 5 and 7.
Ø If the synchronization option is being used, ensure
the violet wire is connected on the Control Head side
that is commanding the Starboard Processor.
For single lever Control Head remote stations that have
the user facing aft and the single Control Head lever on
the user’s right, reverse connections 5 and 7.
5.7 ENGINE STOP SWITCH
The Installer supplies the Stop Switches. Refer to the
information supplied with the Stop Switches for installation
specifications.
Page 14
WARNING: Each remote station must have some method to stop the engine.
Warranty canceled if requirement not followed.
Page 16
Ensure after all Adjustments have been completed that
the Dip Switches are all placed in the Safe State as
indicated on the System Drawing in Appendix C.
6.3.3 Single/Twin Screw (or more) Selection
The Processors are set at the Factory for Single Screw
operation.
Select Twin Screw (or more) by setting the Dip Switches
on the Processor Main Circuit Boards using the following
steps:
A) Take command at a Remote Station.
B) Leave the Control Head lever in the Neutral position.
C) Enable Setup Mode by closing Jumper 2 on the Main
Circuit Board. (Refer to System Drawing for
location and setting.)
Ø A three-second tone will be heard indicating
Setup Mode is enabled.
Ø If motor control relay is clicking refer to Section
6.3.1 before continuing with Step D)
D) Refer to the System Drawing for the Dip Switch
settings and the location of the switches.
NOTE: All the Dip Switches are preset and placed in the Off position at the Factory.
Page 17
Ø If another adjustment setting is not necessary,
continue with the next step
H) Remove Jumper 2.
Ø A low repetitious rate tone is heard indicating that
the Control System is out of Setup Mode and no
Remote Station is in command.
I) Take command at the Remote Station. The LED
should light; indicating Station is in command.
CAUTION: The switches on all Processors Main Circuit Boards MUST be set the
same for Multiple Screw applications.
Page 18
G) Place the Control Head lever into the Full Throttle
position.
H) Rotate Potentiometer R7 clockwise until minimum
throttle voltage is achieved.
Ø Use a voltmeter to measure the output voltage.
Ø Refer to System Drawing for R7 location.
I) Store the value by depressing SW1 located on the
Auxiliary Board. (Refer to the System Drawing for
location of SW1)
Ø The motor control relay (located next to the
Power Supply Terminal Block) will click once to
confirm the value has been stored.
J) Reset all of the Dip Switches to the Off position
(Safe State).
K) Return Control Head lever to the Idle position.
Ø If another adjustment setting is necessary,
continue with Step D) of the appropriate
adjustment instruction Section.
Ø If another adjustment setting is not necessary,
continue with the next step
L) Remove Jumper 2.
Ø A low repetitious rate tone is heard indicating that
the Control System is out of Setup Mode and no
Remote Station is in command.
M) Take command at a Remote Station. The LED
should light, indicating Station is in command.
CAUTION: The switches on all Processors Main Circuit Boards MUST be set the
same for Multiple Screw applications.
Page 19
B) Leave the Control Head lever in the Idle position.
C) Enable Setup Mode by closing Jumper 2 on the Main
Circuit Board. (Refer to System Drawing for
location and setting.)
Ø A three-second tone will be heard indicating
Setup Mode is enabled.
Ø If motor control relay is clicking refer to Section
6.3.1 before continuing with Step D)
D) Take command at the Remote Station again.
Ø Verify a tone is heard when depressing the
station transfer button. The Control Head LED
will not be lit, but the Control Head will be active
for setup procedures.
E) Refer to the Notes page of the System Drawing for
the Dip Switch settings of Throttle Maximum.
F) Place the appropriate Dip Switches On. (Highest
numbered Dip Switch first to Lowest numbered Dip
Switch last)
G) Place the Control Head lever into the Full Speed
position.
H) Rotate Potentiometer R7 clockwise until maximum
throttle voltage is achieved.
Ø Use a voltmeter to measure the output voltage.
Ø Refer to System Drawing for R7 location.
I) Store the value by depressing SW1 located on the
Auxiliary Board. (Refer to the System Drawing for
location of SW1)
Ø The motor control relay (located next to the
Power Supply Terminal Block) will click once to
confirm the value has been stored.
J) Reset all of the Dip Switches to the Off position
(Safe State).
K) Return Control Head lever to the Idle position.
Ø If another adjustment setting is necessary,
continue with Step D) of the appropriate
adjustment instruction Section.
Page 20
Ø If another adjustment setting is not necessary,
continue with the next step
L) Remove Jumper 2.
Ø A low repetitious rate tone is heard indicating that
the Control System is out of Setup Mode and no
Remote Station is in command.
M) Take command at a Remote Station. The LED
should light, indicating Station is in command.
CAUTION: The switches on all Processors Main Circuit Boards MUST be set the
same for Multiple Screw applications.
WARNING: Do not attempt to continue tests until Engine Stop Switches function
correctly.
7. ADJUSTMENTS UNDERWAY
WARNING: DO NOT attempt to operate ClearCommand away from the dock with any
system abnormality. Verify that all the above tests are completed and
are correct.
CAUTION: Start slowly and learn to appreciate that the ClearCommand System
provides a light touch that is fast and accurate.
Page 21
7.1.2 Milli-amperes
The Processor is pre-calibrated to provide a 4-20 mA
command to the main engine, based on Control Head
lever position. No adjustments required.
7.1.3 PWM
The Processor is pre-calibrated to provide an 8 percent to
92 percent PWM Duty Cycle to the main engine, based on
Control Head lever position. No adjustments required.
7.2 ENGINE RPM
A) Warm-up the engine(s).
B) In open water gradually move the Control Head lever to full-
speed. Engine(s) should be running at full rated RPM.
NOTE: For Voltage Systems refer to Section 6.3.5 for Throttle Maximum Voltage if
adjustment of Throttle Maximum is required.
Page 24
Appendix A
Table of Contents
PARTS LIST ...............................................................................1
WATERTIGHT ENCLOSURE....................................................... .....3
BONDING....................................................................................5
REFERENCES...............................................................................7
PARTS SOURCE............................................................................8
CHECKOUT & SEA TRIAL REPORT...................................................9
PARTS LIST
PART NO. DESCRIPTION
CABLE (Electric)
180 8-Cond. Shielded Cable Per/ft
350 8-Cond. Shielded Cable 500' Spool
11811 8-Cond. Shielded Cable 1000’ Spool
212 2-Cond. Power Cable Per/ft
349 2-Cond. Power Cable 250' Spool
183 2-Cond. Start Interlock Cable Per/ft
355 2-Cond. Start Interlock Cable 250' Spool
WIRE HARNESS (Plug)
13480 Serial Communication (Twin Screw) 3’ Length
13221 Serial Communication (Twin Screw) 10’ Length
13354 Serial Communication (Multiple Screw) 10’ Length
13222 Throttle, Voltage 20’ Length
13486 Throttle, mA 20’ Length
13410 Throttle, PWM 20’ Length
13401 Tach Sensor Cable without Sensor Plug 20’ Length
13223 Tach Sensor Cable with Sensor Plug 20’ Length
13224 SS-4 Sensor with Plug 20’ Length
13225 Clutch Harness 20’ Length
13403 Clutch/Troll Harness 20’ Length
Page 1
Page 2
WATERTIGHT ENCLOSURE
• Deck Mount or Exposed Mount
• Ideal for outside Weather Mount
• To prevent internal condensation and moisture build up
the mount is drilled to allow air circulation.
• Part No. 12110
Page 1 of 1 MMC-279
1/97
BONDING A.B.Y.C. 46 CFR 111.05
All boats equipped with a permanently installed electrical system
shall also be equipped with a bonding system. The negative
terminal of all batteries should be connected at only one point, the
DC common, and from DC common to bond system or hull.
Metal - Hull Vessels
The hull of a metal - hull vessel may serve as the common bonding
conductor. Any item to be bonded not in contact with the hull
requires a bonding conductor to the hull.
Page 5
Page 6
REFERENCES
AMERICAN BOAT & YACHT COUNCIL
(ABYC)
Box 806
Amityville, NY 11701
E-1 Bonding of Direct Current Systems
E-3 Wiring Identification on Boats
E-9 DC Electrical Systems on Boats
H-2.4e or 32.4g Ambient Temp. 50 degrees C
UNDERWRITERS LABORATORIES
Page 7
PARTS SOURCE
Anti-Static Wrist Strap Part No. 517 [Thomas & Betts (Part No. AWCC)]
Fuse Part No. 1030 [Bussman (Part No. GDC-1A)]
WAGO Tool Part No. 397 [WAGO (Part No. 236-332)]
Page 18
Mathers Controls, Inc.
675 Pease Road
MicroCommander/ClearCommand Burlington WA 98233-3103
U.S.A.
Checkout &Trial Report Tel: 360-757-6265
Fax: 360-757-2500
e-mail: mathers@matherscontrols.com
Owners Name:
Address:
Tel/Fax/e-mail:
Contact Name:
APPLICATION:
A: Boat Builder Model Size Year
Original Equipment Retrofit Type of Controls Replaced
B: Single or Twin Screw
Engine Make Model
Horsepower RPM Engine Hours
Reduction Gear/Drive Model/Ratio Trolling? Yes No
Type of Service (Pleasure, Fishing, Rental, Etc)
C: Number of Control of Stations
Port Actuator/Control Starboard Actuator/
Processor: Model S/N Control Processor: Model S/N
Trolling Actuator:
Model S/N
Synchronizer: Yes No Type of Input Signal (tach gen, mag pick-up, etc.)
Control Station Location(s) and Model(s)
Before Running Engine: Port Stbd
1. Voltage at the Battery Terminals. VDC VDC
2. Voltage at the Actuator/Control Processor. VDC VDC
3. Warm-up Indicator Light blinks in 'Ahead'. All Stations. Yes No Yes No
4. Electric Cables are supported every 18 inches. Yes No Yes No
5. Cable connections are tight at the Actuator/Control Processor and
Control Heads. Yes No Yes No
6. Engine Shutdown Switches at EACH Remote Station are
operational. Yes No Yes No
7. Check push-pull cable match. Disconnect push-pull cables at the
clutch and throttle. Check that cables travel in the correct
direction. Check the cable movement, insure that it matches
clutch and throttle. Yes No Yes No
F-226 Rev-
1/99
Dock Side Tests (Running): Port Stbd
1. Voltage at the Battery Terminals. VDC VDC
2. Does Engine 'Start' when Controls are 'OFF'? Yes No Yes No
3. Low Idle RPM. RPM RPM
4. High Idle RPM (optional). RPM RPM
5. Check Warm-Up Mode. Yes No Yes No
6. Check shift in both directions. Yes No Yes No
Sea Trials: Port Stbd
1. Check that Twin Screw Levers match position and RPM
throughout speed range. Yes No Yes No
2. Set maximum engine RPM as required. RPM RPM
3. Adjust Full Speed Reversal Delay. SEC. SEC.
4. Is Synchronizer operational? Yes No Yes No
5. Is Trolling Valve operational? Yes No Yes No
SW 1 Switch Settings:
PORT STBD
1 2 3 4 5 6 7 1 2 3 4 5 6 7
ON ON
OFF OFF
PORT JMPR 3 STBD JMPR 3
PUSH PULL PUSH PULL
JMPR 4 JMPR 4
PUSH PULL PUSH PULL
Comments (Please use additional paper as necessary):
General Installation Condition:
Any Irregularities:
1. TROUBLESHOOTING
The ClearCommand Control System consists of Control Heads
located at the vessel’s remote stations, connected to Control
Processor(s) located in the engine room area.
Before beginning troubleshooting, review the Drawings in Appendix
C. Become familiar with the component configuration on your
vessel.
Carefully inspect the following:
Ø DC Power Source
Ø Component Location
Ø Component Condition
Ø Interconnecting Wiring
Ø Wire Termination’s
A key in troubleshooting the ClearCommand System is identifying
the problem as:
Ø DC Power Source
Ø Interconnection wiring or termination
Ø Component Calibration
Ø Component Failure
The ClearCommand System has Station-in-Command indicator
lights on each Dual Control Head, as well as audible tone indicators.
These indicators will assist in troubleshooting and control system
status.
When contacting an authorized Mathers Controls servicing dealer, or
Mathers Controls Service Department, please be ready with the
Control Processor Part Number and Serial Number.
CAUTION: Static electricity can destroy electronic components. Any time the
Control Processor cover is off, wear the wrist strap provided and
connect it to the Processor frame. This will drain any static charge you
may have on your person.
NOTE: Always check the other remote stations, to see if the symptom can be
repeated.
Page 3
Appendix B
Page 4
Appendix B
Remedy:
a) Verify the power source to the Processor.
b) Connect the red wire to the terminal labeled ‘ + ‘ and the
black wire to the terminal labeled ‘ - ‘.
c) Measure the battery voltage at the Processor. It is
MANDATORY to correct power source if voltage can
exceed 40 volts under any condition. Replace the fuse
with the spare, which is taped to the relay on the
Processor circuit board. If the fuse again blows, the
circuit board needs repair or replaced with a Circuit Board
Kit.
1.10 Symptom - THE ENGINE STARTS TO TURN OVER WHILE
STARTING AND THEN STOPS. A SLOW REPETITIVE AUDIBLE TONE
FROM ALL CONTROL HEAD STATIONS.
Cause:
a) The voltage to the Processor has dropped too low, due to
the starters current requirements.
b) Battery charge is low.
Remedy:
a) Supply power to the Processor from a battery other then
the starting battery.
b) Recharge or replace the battery.
1.11 Symptom - THE ENGINE WILL NOT START.
Cause:
a) ClearCommand does not have power turned ON.
b) ClearCommand does not have a remote station in
command.
c) All the Control Head levers at the Station-in-Command
are not in the Idle position.
d) Low battery voltage.
e) Faulty start interlock circuit in the Processor.
f) Faulty wire or component in the starting system.
g) System is in Setup Mode (Jumper 2 Closed)
Page 6
Appendix B
Remedy:
a) Turn power ON to the ClearCommand System.
b) Take command at a remote station.
c) Place all of the Control Head levers into the Idle position
and depress the station transfer button.
d) Check the battery voltage. If the voltage is low, charge
or replace the battery.
e) Connect the two start interlock wires (yellow with red
stripe) at the Processor to the same terminal. If the
engine starts, have the Processor repaired.
f) Take the System out of Setup Mode and remove Jumper
2.
1.12 Symptom - THREE SHORT - ONE LONG TONE FROM ALL
CONTROL HEAD STATIONS.
Cause:
Control Head is dysfunctional because of loose or
unconnected cable connections.
Remedy:
Verify that the cable connections at the Control Head are
secure and correct as shown on the System Drawing in
Appendix A.
If connections are tight and correct, replace the Control
Head or install a Control Head Repair Kit.
1.13 Symptom - CANNOT GET ANY SPEED ABOVE IDLE.
Cause:
a) Gear oil pressure switch is not closing, or is incorrectly
wired.
b) The gear oil pressure switch not installed and jumper is
removed from the circuit board.
Remedy:
a) Replace the pressure switch or correct wiring.
Page 7
Appendix B
Page 8
Appendix B
Page 9
Appendix B
Page 10
Appendix C