"Cluster-Mode" (C-Mode) C-Mode: Clustershell
"Cluster-Mode" (C-Mode) C-Mode: Clustershell
README FIRST
This AP has been updated to include commands for systems running "Cluster-Mode" (C-Mode) ONTAP.
● The login name for C-Mode systems is "admin", not "root".
● The ONTAP version and mode is listed in your dispatch!
● C-Mode: Has two console command shells, clustershell and nodeshell. The default shell is clustershell.
IF clustershell, the console prompt includes a double colon ( :: ). Ex(1): cluster ::> Ex(2): cluster ::storage>
● To switch from clustershell to nodeshell, enter 'run local' at the ::> prompt, then the double colons (::) are
removed. To exit nodeshell, enter 'exit' or Ctrl-D.
● From clustershell, nodeshell commands can be entered by prefacing the 7-Mode command with “run local".
Ex: cluster::> run local sysconfig -v Note, all 7-Mode commands are not supported in C-Mode.
No "Failed" Disks can exist in the target node in a HA config or the disk reassign will not execute. The AP covers this.
If this is a V-Series system with a 3rd party storage array or has SAN attached Tape drives, confirm a storage admin is
available to update the LUN Masking and/or switch zoning if the internal FC adapters are connected to the array.
Pre-ONTAP 8.2 Known Bugs/Issues - Skip IF ONTAP 8.2, otherwise refer to the Bug Table and Notes Below
Bug Description First Fixed Release
TSB-1110-04 is an internal Bulletin: When the disk reassign is performed on the
TSB-1110-
1 partner (HA-takeover) the GB must be immediately performed, a TO/GB from the See Note 1
04 repaired node is required to sync the system-IDs.
Note: For ONTAP 8.0.5 or higher and 8.1.3 or higher the console message to perform an additional TO/GB can be ignored.
(The bugs listed in the TSB are fixed in ONTAP releases 8.0.5 and 8.1.3 and higher, but the console message was not
removed.)
590488 2 In “disruptive” MB w/NVMEM replacements, a TO/GB from the repaired node is req'd. See Note 2
489060 3 NDMP, Qtree-SnapMirror, Vol-SnapMirror or SnapVault processes can hang TO/GB See Note 3
459379 4 Diags report a false error on the NVRAM test in a HA Config. Diag version 5.6.1 and >
Bug Notes:
1 In some versions of ONTAP when the 'disk reassign' command is executed from the partner, ONTAP may print out a
warning that states 2 things.
(i) The giveback must be done right way - IF a GB will not be immediately performed, the disk reassign needs to be
post-poned.
(ii) A second TO/GB should be performed from the repaired node. This is covered in the AP. (TSB-1110-04)
2 IF this system has a partner AND the partner did NOT takeover this controller, it is still necessary to sync the new system-ids
by executing a TO/GB from the repaired node although no console message is displayed. This is covered in the AP.
3 The AP will cover asking the customer if they are running these processes. If so, there is a link how to disable them.
4 Bug- ERROR DNH0500: The AP will cover checking for the diag version and how to work around it.
PS-2 AC
Switch
B
AC Power
Fig 3 PCI - 1
4 PCI slots
0a, 0b 0c, 0d
IOIOI Fibre Channel Ports
(Console) Ethernet Ports: RLM
Port e0a, e0b Port
The NVMEM D87 LED will start flashing through the grill, reference Fig 3, when power is removed
STOP !! from the controller if the system is "waiting for giveback", or the system was not shutdown properly
(uncommitted data). Follow the steps in Section V carefully.
5. FC port configuration, disk list and the system date are captured prior to
removing the original Controller.
6. Many parts need to be moved from the Original Controller to the Replacement
Controller Module.
Page 3 of 28
AC Power
LOADER-A>
Page 4 of 28
b) Disable the auto-giveback option if enabled from the partner node. (copy-n-paste)
Cluster-Mode
Cluster-Mode (Run
(Run in
in clustershell)
clustershell)
cluster::>
cluster::> sto
sto fa
fa modify
modify -node
-node local
local -auto-giveback
-auto-giveback false
false
2 The date and time is stored in the system PROM in Greenwich Mean Time, (GMT) also known as Universal Time Clock, (UTC).
At the LOADER> prompt, enter: show date Record on paper the system's GMT time and the local time to determine the
number of hours (and minutes) the local time is ahead or behind GMT.
LOADER-A>
LOADER-A> show
show date
date
Current
Current date
date && time
time is:
is: 06/12/2011
06/12/2011 15:59:10
15:59:10 Step
Step 2):
2): Enter
Enter:'show
show date'
date
3 Enter: printenv This command displays (and captures) all boot environmental variables.
LOADER-A>
LOADER-A> printenv
printenv STEP
STEP 3):
3): Enter
Enter:printenv
printenv
An example of a "printenv" output is here > printenv-C-all.pdf
4 Follow steps 4A-C if this a V-series Filer (V3100). If not , go to step 5.
A. Open up the console log.
B. Use the "Find" function to search for variables prefixed with: "fc-no" - Do not rely on a visual search.
C. Identify these variables from the printenv output in the console log:
(i) fc-non-array-adapter-list,
(ii) fc-no-mgmt-ports OR fc-no-mgmt? NOTE - Only one of these two variables may be used.
An example of "printenv" output highlighting the variables is here > printenv-C-all.pdf
5 Continue with Section IV on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 5 of 28
7 From the > *> prompt enter fcadmin config to log the configuration of the integrated FC host adapters.
a) Note the "0a-0d" Adapter ports to see if configured as a "target" adapter. If so, it will need to be configured later.
15 Go to Section V, "Remove the cables, Cable Management Tray and extract the Controller Module" on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 7 of 28
V. V-FAS3100 Family: Remove the cables, Cable Management Tray and extract the Controller Module
Step Action Description
If TWO controllers modules are installed, DO NOT shut off the power supplies to replace the controller card, BUT DO
NOTE
shut off both power supplies if only ONE controller card is installed .
1 On the controller to be serviced, loosen the red thumbscrew, ref Fig 2 & 3; pull down on the cam lever and slide the controller
module towards you a few inches or until it stops.
*
HA (Active-Active) Configuration : If the red NVMEM Status D87 LED starts flashing ref Page-1, Fig 3,
STOP! when the controller is extracted from the chassis:
(i) Confirm from end-user or NGS that the partner controller had a clean takeover, or if this controller was "waiting for
and giveback", the flashing LED can be ignored.
(ii) If a non-successful takeover, the flashing LED indicates uncommitted customer data - Contact NGS
READ *
Non-HA Configuration : If the red NVMEM Status D87 LED is flashing, the system was not 'halted' properly:
(i) Ask end-user if controller was properly "halted". If not, re-insert controller and if the system does not autoboot, enter
this 'bye ' at the LOADER-A|B> prompt . If the system boots to the login prompt, login and then enter 'halt' to properly
shutdown. Engage NGS if questions.
CAUTION
* The node configuration should have been determined by following Section III.
NOTE For detail on the locations of the two NVRAM LEDs click here >> FAS3100-NVRAM-LEDs
2 Before proceeding further the state of the NVMEM LED should be resolved if it's valid by reading caution above.
3 Label each cable connector with its port number and then unplug the cabling from the connector.
NOTE If possible keep the cables in the cable clips on the cable tray to keep them in the correct position for reconnection.
4 Remove the cable management tray, Fig 6a-b, by pushing in the sides of the tray at the arrows and lifting it up.
Fig 6a
Fig 6b
Optional Cable
Management Trays Cable Management
Tray Mounting Hooks
5 Push in on the blue release latch on the left side of the tray as shown in Fig 7 and firmly grip the tray on each side as you extract
it.
Fig 7
6 Go to Section VI, "Move onboard SFPs - Remove PCI Cards and the Riser" on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 8 of 28
VI. V-FAS3100 Family: Move onboard SFPs - Remove PCI Cards and the Riser
Step Action Description
1 Remove each SFP/GBIC one at a time inserted in the original Controller Module's on-board Ethernet and FC ports and install into
the same port location in the replacement Module. (Do not mix them up!)
2 Loosen the thumbscrew on the controller module side panel and swing the side panel open until it comes off the controller
module. Ref Fig 8a.
3 Label each card with it's PCI slot number and slide out of PCI Riser, Fig 8b.
4 Loosen the PCI card riser thumbscrew and pull the riser up and out of the socket. Ref Fig 8c.
5 Attach and close the side panel of the System Tray.
Fig 8b)
Fig 8a)
Fig 9a
Fig 9b
2 Insert the RLM into the replacement controller module by pressing it completely into the socket .
3 Go to Section VIII, "Exchange the CompactFlash Cards" on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 9 of 28
CompactFlash Slot
Fig 11a
NOTE The FAS3140 has two system DIMMs. The FAS3160 has four DIMMs and the FAS3170 shown, has eight DIMMs
2 Continue with Section IX on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 10 of 28
Fig 12
NVRAM DIMM
Fig 13a
Fig 13b
XI. V-FAS3100 Family: Install PCI Riser and Cards (if any)
Step Action Description
1 Loosen the thumbscrew on the new controller module side panel and swing the side panel open until it comes off the controller
module.
2 Align the PCI riser removed from the original controller module with the guide slots on the replacement controller module, and
then push down to seat it completely in the socket and tighten the riser thumbscrew.
3 Install the PCI cards removed from the original controller module into correct slots on the replacement controller module.
XII. V-FAS3100 Family: Partially Reinsert the Replacement Controller and Reconnect the cables
Step Action Description
1 Partially insert the controller into the slot so that the cables can be attached- DO NOT engage the backplane yet.
2 Re-attach the Cable Management Tray if removed. (Reference pictures in Section V)
Do not re-connect the FC cables for ports 0a-0d as the "maintenance mode" boot or the Fibre Channel Diags may fail. A "step"
STOP
has been added after the FC ports are configured in Section XV to reconnect these cable(s).
3 Fully insert all other cables that were removed to their proper port until each clicks in. Test by pulling on them.
4 Go to Section XIII, "Set date and time" on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 12 of 28
4 IF you miss the window to abort the autoboot, look for this message: "Press CTRL-C for boot menu" and complete steps
4a-4c, otherwise if at the "LOADER" prompt, skip to step 5 .
a. Immediately Press ^C (CTRL-C) to access the "Boot menu".
b. If a 'System ID mismatch' warning message below is displayed, answer : y
.......
.......
*******************************
* *
* Press Ctrl-C for Boot Menu. *
* *
******************************* STEP 4a:
^C Press CTRL-C
Boot Menu will be available.
Restoring /var from /cfcard/x86/freebsd/varfs.tgz
WARNING: System id mismatch. This usually occurs when replacing CF or NVRAM cards!
Override system id? {y|n} [n] y
STEP 4b: Enter: y
N If the replacement MB fails to boot to the Maintenance menu, confirm the memory DIMMS and all PCI cards are
O
T
properly seated. Also was the original Boot Device (CF Card) moved from the original MB to the replacement?
E Engage NGS for assistance.
If the system reports the NVRAM battery is not detected, re-check the battery cable connection. If the system
reports the battery voltage is too low or a critical failure, do NOT proceed - Do NOT bypass the system stop.
STOP Engage NGS and ask if this motherboard is being replaced due to a battery issue. If so, a new battery needs to
be installed before continuing.
Do NOT bypass the system halt on a NVRAM battery voltage issue. Controller giveback will fail.
c. Next, drop to the LOADER prompt from the Boot Menu following the linked proceshere
5 Continue with Section XIII on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 13 of 28
7 The original motherboard's GMT time and local time should have been recorded in Section IV. If you don't have it, you can obtain
the GMT time from the partner node, or another NetApp appliance or any Unix Server using: date -u (The "-u" option displays
the time in GMT/UTC) The new motherboard's Real Time Clock (RTC) must be set within 2 minutes of the time displayed (which
is GMT time) for users to be able to re-connect to this appliance.
NOTE Detailed instructions for another method of obtaining the time in GMT and setting the date and time is here RTC Check
8 To set the time issue: set time hh:mm:ss Set the time in GMT using 24 hour format - Do not set the time to local time.
NOTE If this maintenance period spans across the midnight hour in GMT time, the DATE will also need to be set.
9 To change the date, issue: set date mm/dd/yyyy (mm = 2-digit month, dd = 2-digit Day, yyyy = 4-digit Year)
10 If the date or time was changed, issue: show date again to verify the GMT date and time are correct.
11 Update Firmware on the Replacement Controller Module:
At the LOADER-A|B> prompt, Enter : update_flash to copy the firmware on the Compact Flash card to the motherboard's flash
PROM.
NOTE If a message displays that states: "Current firmware version is newer than provided image", skip to step 12.
LOADER-A> update_flash
New BIOS Version: 4.4.0 Step 11: At the LOADER-A|B> prompt, enter:
New Loader Version: 1.8 update_flash to update the flash PROM
Saving Primary Image to Secondary
Updating Secondary Boot Flash
Programming .+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+.+ done. 2097152
bytes written
Updating Primary Boot Flash
Programming .+.+.+.+.+.+.+.+.+.+.+.+.+.+ done. 917504 bytes written
LOADER-A>
XIV. FAS3100 Family: Run Diagnostics (20-45 minutes depending on model and expansion options)
Step Action Description
1 Test the Replacement Tray with diagnostics by entering boot_diags at the "LOADER-A|B>" prompt.
STOP There is a bug in older versions of the diags. The diag version is highlighted below - Read the NOTE Text box.
2 Check the Diagnostic version in the Menu and enter the proper test sequence below:
IF Diag version is 5.6.1 or higher enter: run mb mem cf-card
IF Diag version is lower than 5.6.1 enter: run mem cf-card
These diagnostics tests are basic confidence tests for the new motherboard, memory and CompactFlash. IF any single test
FAILs, then the next diag test will not be started. Contact NGS for test failure. IF error can be skipped, run remaining test(s)
individually, ex: run mem or run cf-card, etc
LOADER-A> boot_diags
Loading x86_64/diag/diag.krn:...0x200000/12601344 0xe04800/4664888 0x1277638/8 Entry at
0x00202018
Starting program at 0x00202018 STEP 1: Enter: boot_diags
Commands:
Config (print a list of configured PCI devices)
Default (restore all options to default settings)
Exit (exit diagnostics)
Help (print this commands list)
Options (print current option settings)
Version (print the diagnostic version)
Run <diag ... diag> (run selected diagnostics)
NOTE: (2 different RUN Command options)
Options:
Count <number> (loop selected diagnostic(s) (number) of passes)
Loop <yes|no> (loop selected diagnostic(s)) IF any Comprehensive test FAILs, then the next
Status <yes|no> (print status messages) diag test will not be started
Stop <yes|no> (stop-on-error / keep running)
Xtnd <yes|no> (extended tests / regular tests)
Mchk <auto|off|on|halt> (machine check control)
Cpu <0|1|2|3> (default cpu)
Seed <number> (random seed (0:use machine generated number))
Enter Diag, Command or Option: run mem cf-card Diag version is lower than 5.6.1
STEP 6:
STEP 6:
Testing : 1592 MB (start=1c000000, end=7f800000) Note: PLEASE CONFIRM
CONFIRM
Testing : 14336 MB (start=100000000, end=480000000) Note: PLEASE
V-FAS3140 should total~4GB
V-FAS3140 should total ~4GB
Total Memory Size : 16376 MB
Main Memory Diagnostic
V-FAS3160 should total
V-FAS3160 should total ~8GB~8GB
---------------------- V-FAS3170 should
V-FAS3170 shouldtotal
total~16GB
~16GB
..... Outputisisfrom
Output froma aFAS3170
FAS3170
****** Comprehensive Memory test ................ PASSED
7 Firmly re-connect any FC cables that were left disconnected to adapters '0a, 0b, 0c or 0d' now. They must completely click in.
8 Continue with Section XV on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 19 of 28
Page 20 of 28
Page 21 of 28
Disk ownership will be updated on all disks previously belonging to Filer with
sysid 1573753606. 7-Mode only: A console message will be displayed for
Would you like to continue (y/n)? y Enter: y each disk changing ownership (System ID)
If the console messages stated that the giveback must be completed immediately, do not enter any other commands
STOP
on the partner node until "after" the disk ownership on the down node is verified and the giveback is completed.
A10 Continue with step 2 on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 22 of 28
IF the system reports: "Partner node must not be in Takeover mode during disk reassignment
from maintenance mode. Serious problems could result!!.
The system sees controller as a HA configuration.
CAUTION
(i) Confirm with the end-user that the partner did not takeover and continue with step B3 OR
(ii) IF the partner did takeover, enter the appropriate response to "Abort/Cancel" the disk reassignment and
then follow Procedure-A on previous page.
B2 IF Single Controller configuration, follow steps (i)-(ii). IF the partner did NOT takeover, skip to step B3.
(i) Enter: y to question "Would you like to continue (y/n)?"
(ii) Skip to step 2.
2 From the console port on "target" controller on which you replaced the MB (in maintenance mode):
a) Enter: disk show -s <old-sysID> No disks or V-Series LUNs should be listed as shown in console window below.
(The "-s old-sysID" was specified in the disk reassign step1)
IF any disks/V-LUNs are listed, a reservation may not have released, continue with step 2(b). IF no output, skip to step 3.
b) Not all disks re-assigned: Re-issue the disk reassign, from the node it was entered on, to see if the reservation releases.
Then repeat the disk show -s command in step 2(a). IF disks/V-LUNs are still listed in the output, call Support.
3 Continue with Section XVII on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 23 of 28
5 If this is a V-Series (V3200), perform the below Additional Steps. If not , skip to step 6.
The "disk show -v" command displays the connectivity to the third party array and any (optional) NetApp disks.
S If the storage listing is missing or incomplete:
T (i) Confirm all FC connections are in the correct HA port and firmly seated on the NetApp controller.
O (ii) If the connections are correct and firmly seated, confirm the WWPNs were correctly entered by end-user
by reviewing the output of the "fcadmin channels" command BEFORE and AFTER the MB swap -
P Engage NGS for assistance.
6 At the maintenance mode prompt: " * >", enter: halt to exit to LOADER-A|B.
7 Go to Section XVIII, "Boot PROM Variable Checks" on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 24 of 28
Step System Type & Configuration Variable name and Value to be validated
A) IF HA: partner-sysid xxxxxxxxxx
Verify this variable is set with correct partner sys-id value.
B) IF C-Mode: bootarg.init.boot_clustered true
Verify this variable is set to true.
C) IF V-Series:
fc-non-array-adapter-list is only required if the V-Series is also fc-non-array-adapter-list <fc-adapter-list>
hosting NetApp multipath shelves.
fc-no-mgmt-ports <fc-adapter-list>
One of these two variables "may" be set if the storage
OR (only one of these two may be set)
switches are McData.
fc-no-mgmt? true
3 If any of the variables are missing or values are not set correctly, set them now one by one by following steps a-d below.
a) Open the console log file that was previously captured from the old MB and scroll to the "printenv" output listing.
b) Use the "Find" function and search for the variable required and its value. Sample "printenv" output ishere
c) Once identified, copy them using "Ctrl-C", then at the LOADER prompt enter:
setenv <(CTRL-V)to paste the variable and value>
d) Enter: savenv to save the variable and value.
STOP PROM will accept improper variable names. Recheck they were entered properly by issuing printenv again.
4 Go to Section XIX, "Boot the Operating System - 'giveback' if applicable" on next page.
Controller Module Replacement for the V-FAS3100 Family
For NetApp Authorized Service Engineers
Page 25 of 28
4 Login into the PARTNER node (7-Mode=root , C-Mode=admin ). Engage end-user for password.
5 Check takeover status by entering the appropriate command shown for the specified ONTAP Mode. If "partner not ready" may
have to wait 2-4 minutes for the NVRAMs to synchronize.
7-Mode Cluster-Mode
partner(takeover)> cf status cluster::> run local cf status
6 IF Pre-ONTAP 8.2 and 7-Mode: Ask the customer if there are any heavy NDMP, SnapMirror or SnapVault processes running. If
Yes, they should be disabled due to bug 489060. The procedure to disable the processes is here.
7 Enter the proper controller giveback command(s) based on the mode running as follows:
A giveback cannot be completed due to: "a failed disk" or "Open CIFS sessions" or "partner not ready" .
IF FAILED disk: Physically dis-engage the failed disk (Leave the disk in the slot till replacement is received).
NOTE IF Open CIFS sessions: Check with customer how to close out CIFS sessions. Terminating CIFS can cause loss of data.
IF partner "not ready": Wait 5 minutes for the NVMEMs to snychronize.
Giveback fails due to any other reason? contact NGS.
7-Mode Cluster-Mode
partner(takeover)> cf giveback cluster::> storage failover giveback -fromnode local
Page 26 of 28
XIX. V-FAS3100 Family: Boot the Operating System - 'giveback' if applicable (cont.)
Step Action Description
9 Wait! 90 seconds for 7-Mode or 3 minutes for Cluster-Mode after giveback reported complete.
Check controller failover status by entering the appropriate command shown for the specified ONTAP Mode.
7-Mode Cluster-Mode
partner> cf status cluster::> storage failover show
Controller Failover enabled, Follow step (a)
XYZ is up.
Look for failover enabled
a) IF Cluster-Mode: Confirm the "giveback" status of the storage, refer this doc > ONTAP 8 failover show
If the "giveback" is incomplete, wait 2 minutes and re-check. If still not complete after 10 minutes, contact Support.
NOTE
Do not proceed to next step if 'incomplete or partial giveback'!
10 IF Motherboard was Replaced and the partner printed out the following highlighted message after the "disk reassign" command
was executed, go to Step 11. If no message reported, skip to step 12 on next page.
disk reassign: A giveback must be done immediately following a reassign of partner disks.
After the partner node becomes operational, do a takeover and giveback of
this node to complete the disk reassign process.
IF this system has a partner controller, but the partner did not takeover, (Disks were assigned in maintenance mode) continue
STOP with step 10a (Ref Internal TSB-1209-02). Note, the console message above is not displayed when disks are reassigned in
maintenance mode.
a) Login to the "repaired node" (target) and re-enable "controller failover" using proper command syntax below (copy-and-
paste).
7-Mode (1st cmd is for 2-node clusters ONLY, 2nd cmd is for 3 or more node clusters)
target> cf enable cluster::> cluster ha modify -configured true
OR
cluster::> storage failover modify -node local -enabled true
11 From the "repaired node", execute a takeover using the proper command below to sync the sys-IDs.
a) Wait! 60 seconds for 7-Mode or 90 seconds for Cluster-Mode after takeover reports complete- Then check takeover
status by entering the appropriate command shown for the specified ONTAP Mode.
7-Mode Cluster-Mode
b) After the appropriate Wait period in step 11a) and the cf status reports: "Ready for giveback" , enter the proper
"giveback" command below. This is the final synchronization of the system-Ids across the HA pair.
7-Mode Cluster-Mode
XIX. V-FAS3100 Family: Boot the Operating System - 'giveback' if applicable (cont.)
Step Action Description
d) Wait Again! This time 90 seconds for 7-Mode or 3 miniutes for Cluster-Mode and then check giveback status by entering
the appropriate command below for the proper ONTAP mode. For 7-Mode look for failiover enabled , for Cluster-Mode
follow step (i).
7-Mode Cluster-Mode
target> cf status cluster::> storage failover show
Controller Failover enabled,
XYZ is up. Follow step (i).
(i) For ONTAP Cluster Mode, storage failover show should not show any "partial" givebacks. If there are, wait
another 60 seconds and recheck. Some large systems may take up to 10 minutes to complete.
Click > ONTAP 8 failover show to see examples of output. Issues? Call NGS.
12 IF Cluster-Mode: Follow steps (a-b) below, otherwise skip to Step 13.
a) From the clustershell on each node, enter the command below to list the logical interfaces that are not on their home
server and port.
Cluster-Mode
cluster::> net int show -is-home false
XX. V-FAS3100 Family: Controller registration, Enable options, Submit logs and Part Return
Step Action Description
NOTE Service entitlements break when the MB is swapped because the new motherboard changes the system serial number.
1 IF NDMP, SnapMirror or SnapVault options were disabled, enable them now. Refer to page 2 of doc > > here
2 C-Mode Only: Re-enable "auto-giveback" options if they were disabled on either node. C-Mode command here
3 Ask customer if using Operations Manager? If so, can they still access the controllers?
Bug SNMP v3 access may fail despite the user existing with the correct permissions after a takeover or giveback.
583160 WORKAROUND: Change the password or re-add the user. Engage Customer to step through the Work-around.
4 Ask end-user if using "AutoSupport"? If YES, perform step 4(a). If NO, perform step 4(b).
a) ASUP Enabled System: Request end-user to send NetApp an ASUP Message from the target node so the configuration
setup can be verified and the new system serial number can be registered by NGS. If the target system is not UP, send
ASUP from its partner. Use the corresponding command for the mode of ONTAP running. Enter your dispatch's 7-digit
FSO number (begins with 5).
7-Mode Cluster-Mode
filer> options autosupport.doit 5xxxxxx cluster::> invoke * -type all -message 5xxxxxx
b) If ASUP is disabled: Call NGS CSR and provide the new MB serial number so they can register it as the new system s/n.
5 Email the console log with the NetApp Reference Number in the Subject Line to xdl-tpm-console-logs@netapp.com
6 Place the defective part in the antistatic bag and seal the box.
7 Follow the return shipping instructions on the box to ship the part(s) back to NetApp’s RMA processing center. If the
shipping label is missing see process to obtain a shipping label here > Missing Shipping Label?
8 Verify with customer that the system is OK and if working with NGS ask them if it is OK to be released.
9 Close dispatch per Rules of Engagement.