9-5. INTERNAL SWITCH FUNCTION TABLE


PUMY-P100VHM PUMY-P125VHM PUMY-P140VHM
PUMY-P100VHMA PUMY-P125VHMA PUMY-P140VHMA
Operation in Each Switch Setting
Switch Step Function Remarks
ON OFF When to Set
<Initial Setting>
Rotary switch

SWU1 901 901


1st digit 901 901

78

78
23

23
Before turning

78

78
23

23
45 6 45 6
45 6 45 6

SWU2 the power on


SWU2 SWU1 SWU2 SWU1
2nd digit (2nd digit) (1st digit) (2nd digit) (1st digit)

Can be set <Initial Setting>


SW1 Digital
ON either during
Display 1~8 ON
OFF operation or not.
Switching OFF
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

With centralized Without centralized


1 Selects operating system startup controller controller Before turning the <Initial Setting>
2 Connection Information Clear Switch Clear Do not clear power on
OFF to ON any time after ON
SW2 3 Abnormal data clear switch input Clear abnormal data Normal the power is turned on. OFF
Function 4 Pump down During compressor 1 2 3 4 5 6
Run adjustment mode. Normal running
Switching Before turning
5 Auto change over from Remote controller Enable Disable
the power on
6 — — — —
1 ON/ OFF from outdoor unit ON OFF
SW3 Trial Any time after the <Initial Setting>
power is turned on. ON
Outdoor unit

operation OFF
2 Mode setting Heating Cooling
1 2
MODELS SW4 <Initial Setting>
ON
PUMY-P100 OFF Set for each capacity.
SW4 1 2 3 4 5 6
Before the power
Model 1~6 ON
is turned on.
PUMY-P125 OFF
Switching 1 2 3 4 5 6

ON
PUMY-P140 OFF 1 2 3 4 5 6

1 Pressure limitation value change Enable Normal


<Initial Setting>
Change the indoor unit's LEV opening at Enable Can be set when off
2 Normal or during operation ON
start
OFF
3 Fixing the indoor units linear expansion 1 2 3 4 5 6 7 8
SW5 Fix Normal
valve opening
Function OFF to ON during com-
switching 4 Fix the operation frequency Fix Normal pressor running.
Change the indoor unit's LEV opening Enable
5 Normal Can be set when off
at defrost or during operation
6 Switching the target sub cool. Enable Normal
During the FAN or COOL mode, and thermo-OFF
7 or stop in heating operation, set the opening of Active Inactive
linear expansion valve on indoor unit w1
During the FAN or COOL mode, and thermo-OFF
8 in heating operation, set the opening of linear ex- Active Inactive
pansion valve on indoor unit w2

w1 SW5-7 Refrigerant shortage amount is measured during heating operation.


(Refrigerant piping is long etc.)
w2 SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.