7100 When connected total models of the 1) Connecting total models of the 1 Check the total models of connected
indoor units exceed the specified level indoor unit exceed the specified indoor unit.
(130% of the outdoor unit models), error level.
code <7100> is displayed. · PUMY-P100 ( ~ code 26) 2 Check the model code registration
· PUMY-P125 ( ~ code 33) switch (indoor controller board SW2)
· PUMY-P140 ( ~ code 38) of connected indoor unit.
50
OC376B--2.qxp 08.1.17 1:15 PM Page 51
1 234 567 8
Code of indoor unit No.2 on
1 234 567 8
Code of indoor unit No.3 on
1 234 567 8
Code of indoor unit No.4 on
1 234 567 8
Code of indoor unit No.5 on
1 234 567 8
Code of indoor unit No.6 on
1 234 567 8
Code of indoor unit No.7 on
1 234 567 8
Code of indoor unit No.8 on
When the number of connecting unit Number of connecting unit exceeds Check whether the connecting unit
exceeds limitations, error code <7102> limitations. It is assumed abnormality exceeds a number of limitations or
is displayed. excluding the following cases; not.
1) The indoor unit can be totally
Even if the indoor unit is not connected,
connected up to 6(P100)/8(P125,
becomes <7102> is display.
140) units.
7111 Remote controller sensor When an old type remote controller for Replace the remote controller to
M-NET is used, the remote controller M-NET remote controller.
In the case of M-NET remote controller,
sensor is specified (SW1-1 is ON).
it is an abnormality when incapable
response returns from the M-NET remote
controller during the operation.
51