Dry Type Reactor


Model - 7-2

Dry Type Starting Reactor Specification

1. According to the standard: IEC 60076-6


2. Efficiency: Designed according to customer demand efficiency
3. Voltage level: 36kV/24kV/12kV and below
4. Number of phases: three phase
5. Frequency: 50Hz or 60Hz
6. Material: copper-copper
7. Rated starting time: 60, 90, 180 seconds
8. Tap type (standard tap) 50% -60% -80% (full pressure start is 100%)
9. Choice of rated time:
Rated time ≦ (starting time of the motor) X number of continuous starts
(Note: continuous start is limited to 2 times)
10. Starting current and torque comparison

Note:(1) S: starting current, Ts: starting torque


(2) Reactors have similar characteristics to resistors.

11. Features: high mechanical strength, low noise, long life, high efficiency, good
moisture resistance, smooth starting torque.
12. Uses: limit motor starting current
13. Test: Before leaving the factory, the transformer performs in-plant testing and
submits a test report..
14. Warranty: Store for 18 months after delivery or run for 12 months under normal
use.
15. Factory Certification: ISO 9001, ISO 14001, OHSAS 18001, UL 1561, TAF17025
Laboratory
16. Delivery method: Domestic - truck up to the ground / Foreign – CIF