CRE, CRIE, CRNE, SPKE, MTRE, MTHE, CME
Table of contents
English (GB)
Installation and operating instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Български (BG)
Упътване за монтаж и експлоатация. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Čeština (CZ)
Montážní a provozní návod. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Deutsch (DE)
Montage- und Betriebsanleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Dansk (DK)
Monterings- og driftsinstruktion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Eesti (EE)
Paigaldus- ja kasutusjuhend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
Español (ES)
Instrucciones de instalación y funcionamiento . . . . . . . . . . . . . . . . . . . . . . . . 435
Suomi (FI)
Asennus- ja käyttöohjeet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
Français (FR)
Notice d'installation et de fonctionnement. . . . . . . . . . . . . . . . . . . . . . . . . . . . 579
Ελληνικά (GR)
Οδηγίες εγκατάστασης και λειτουργίας . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 651
Hrvatski (HR)
Montažne i pogonske upute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 723
Magyar (HU)
Telepítési és üzemeltetési utasítás. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 795
Italiano (IT)
Istruzioni di installazione e funzionamento . . . . . . . . . . . . . . . . . . . . . . . . . . . 868
Lietuviškai (LT)
Įrengimo ir naudojimo instrukcija . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 940
Latviešu (LV)
Uzstādīšanas un ekspluatācijas instrukcija. . . . . . . . . . . . . . . . . . . . . . . . . . 1012
Nederlands (NL)
Installatie- en bedieningsinstructies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1084
Polski (PL)
Instrukcja montażu i eksploatacji . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1156
Português (PT)
Instruções de instalação e funcionamento . . . . . . . . . . . . . . . . . . . . . . . . . . 1228
2
CRE, CRIE, CRNE, SPKE, MTRE, MTHE, CME
Table of contents
Română (RO)
Instrucţiuni de instalare şi utilizare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1300
Srpski (RS)
Uputstvo za instalaciju i rad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1372
Русский (RU)
Руководство по монтажу и эксплуатации . . . . . . . . . . . . . . . . . . . . . . . . . 1445
Svenska (SE)
Monterings- och driftsinstruktion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1521
Slovensko (SI)
Navodila za montažo in obratovanje. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1593
Slovenčina (SK)
Návod na montáž a prevádzku . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1666
Türkçe (TR)
Montaj ve kullanım kılavuzu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1738
Українська (UA)
Інструкції з монтажу та експлуатації . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1811
中文 (CN)
安装和使用说明书 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1884
日本語 (JP)
取扱説明書 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1946
Қазақша (KZ)
Орнату және пайдалану нұсқаулықтары . . . . . . . . . . . . . . . . . . . . . . . . . . 2017
(AR) ﺍﻟﻌﺭﺑﻳ ﺔ
ﺏ ﻭ ﺍﻟﺗﺷ ﻐﻳﻝ ﺎﺕ ﺍﻟﺗﺭﻛﻳ ﺗﻌﻠﻳﻣ. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2161
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2162
3
English (GB) Installation and operating instructions
English (GB)
4
14. Bus signal 59 1. Symbols used in this document
English (GB)
15. Priority of settings 60
DANGER
16. Grundfos Eye 61
Indicates a hazardous situation which, if
17. Signal relays 62 not avoided, will result in death or serious
18. Installing a communication interface personal injury.
module 63
19. Identification of functional module 65 WARNING
20. Identification of control panel 65 Indicates a hazardous situation which, if
not avoided, could result in death or
21. Changing the position of the control
panel serious personal injury.
66
22. Servicing the product 67 CAUTION
22.1 Motor 67
Indicates a hazardous situation which, if
22.2 Pump 67
not avoided, could result in minor or
23. Cleaning the product 67 moderate personal injury.
24. Factory settings 68
25. Megging 70
Tips and advice that make the work easier.
26. Technical data, single-phase motors 70
26.1 Supply voltage 70
26.2 Leakage current 70 If these instructions are not observed, it
27. Technical data, three-phase motors 70 may result in malfunction or damage to the
27.1 Supply voltage 70 equipment.
27.2 Leakage current (AC) 71
28. Inputs/outputs 71 A blue or grey circle with a white graphical
symbol indicates that an action must be
29. Other technical data 73 taken.
29.1 Sound pressure level 74
30. Disposing of the product 74 A red or grey circle with a diagonal bar,
possibly with a black graphical symbol,
Read this document before installing the indicates that an action must not be taken
product. Installation and operation must or must be stopped.
comply with local regulations and accepted
codes of good practice.
5
2. Abbreviations and definitions 3. General information
English (GB)
Current
The ability to draw current into the 4. General description
terminal and guide it towards GND in
sinking Grundfos E-pumps are fitted with
the internal circuitry.
frequency-controlled permanent-magnet motors for
The ability to push current out of the single-phase or three-phase mains connection.
Current
terminal and into an external load
sourcing
which must return it to GND. 4.1 Pumps without factory-fitted sensor
DI Digital input. The pumps have a built-in PI controller and can be
set for an external sensor enabling the control of the
DO Digital output. following parameters:
ELCB Earth leakage circuit breaker. • constant pressure
FM Functional module. • constant differential pressure
Grundfos Digital Sensor. • constant temperature
GDS Factory-fitted sensor in some • constant differential temperature
Grundfos pumps. • constant flow rate
Proprietary Grundfos fieldbus • constant level
GENIbus
standard. • constant curve
Ground fault circuit interrupter. • constant other value.
GFCI
(USA and Canada). The pumps have been factory-set to constant-curve
GND Ground. control mode. You can change the control mode with
R100 or Grundfos GO Remote.
Grundfos
Status indicator light.
Eye 4.2 Pumps with factory-fitted pressure
Low voltage with the risk of electric sensor
LIVE
shock if the terminals are touched. The pumps have a built-in PI controller and are set
Open collector: for a pressure sensor enabling the control of the
OC outlet pressure.
Configurable open-collector output.
The pumps have been factory-set to
PE Protective earth.
constant-pressure control mode. The pumps are
Protective extra-low voltage. typically used to keep a constant pressure in
A voltage that cannot exceed ELV variable-demand systems.
PELV under normal conditions and under
single-fault conditions, except earth
faults in other circuits.
RCD Residual-current device
Safety extra-low voltage.
A voltage that cannot exceed ELV
SELV under normal conditions and under
single-fault conditions, including
earth faults in other circuits.
6
4.3 Settings 5. Receiving the product
English (GB)
The description of settings applies both to pumps
without factory-fitted sensor and to pumps with a 5.1 Transporting the product
factory-fitted pressure sensor.
WARNING
Setpoint
You can set the desired setpoint in three ways: Falling objects
Death or serious personal injury
• on the pump control panel
- Secure the product during
• via an input for external setpoint signal transportation to prevent it from tilting or
• with the Grundfos wireless R100 remote control falling down.
or Grundfos GO Remote.
Other settings CAUTION
Make all other settings with R100 or Grundfos GO Crushing of feet
Remote. Minor or moderate personal injury
You can read important parameters, such as the - Wear safety shoes when moving the
actual value of the control parameter and power product.
consumption, via R100 or Grundfos GO Remote. • Motors from 2.2 to 5.5 kW: Do not stack more
If special or customised settings are required, use than two motors in their original packaging.
Grundfos PC Tool. Contact your local Grundfos • Motors from 5.5 to 11 kW: Do not stack the
company for more information. motors.
4.4 Radio communication 5.2 Inspecting the product
This product incorporates a radio module for remote Before you install the product, do the following.
control which is a class 1 device and which you can
1. Check that the product is as ordered.
use anywhere in the EU without restrictions.
2. Check that no visible parts have been damaged.
For use in USA and Canada, see page 2162.
3. If parts are damaged or missing, contact your
Some variants of the product and products sold in
local Grundfos sales company.
China and Korea have no radio module.
This product can communicate with the Grundfos
GO Remote and other products of the same type via
6. Mechanical installation
the built-in radio module.
6.1 Handling the product
In some cases, an external antenna may be
required. Only Grundfos-approved external antennas Observe local regulations setting limits for manual
may be connected to this product, and only by a lifting or handling. The motor weight is stated on the
Grundfos-approved installer. nameplate.
7
6.2 Mounting 6.6 Outdoor installation
English (GB)
B3 B14 B5
TM02 9037 1604
8
7. Electrical installation 7.2 Cable requirements
English (GB)
7.2.1 Cable cross-section
DANGER
Electric shock DANGER
- Death or serious personal injury Electric shock
- Switch off the power supply to the motor
- Death or serious personal injury
and to the signal relays. Wait at least 5
- Always comply with local regulations as
minutes before you make any
to cable cross-sections.
connections in the terminal box. Make
sure that the power supply cannot be 1 x 200-230 V
accidentally switched on.
Cross section
DANGER Power Conductor
[kW] type
Electric shock [mm2] [AWG]
- Death or serious personal injury Solid 1.5 - 2.5 16-12
- Check that the supply voltage and 0.25 - 1.5
frequency correspond to the values Stranded 1.5 - 2.5 16-12
stated on the nameplate.
3 x 380-500 V
If the power supply cable is damaged, it must be
replaced by the manufacturer, the manufacturer's
Cross section
service partner or a similarly qualified person. Power Conductor
The user or the installer is responsible for the [kW] type
[mm2] [AWG]
installation of correct earthing and protection
according to local regulations. All operations must be Solid 1.5 - 10 16-8
carried out by a qualified electrician. 0.25 - 2.2
Stranded 1.5 - 10 16-8
7.1 Protection against electric shock, Solid 2.5 - 10 14-8
3.0 - 11
indirect contact Stranded 2.5 - 10 14-8
WARNING 3 x 200-240 V
Electric shock
- Death or serious personal injury Cross section
Power Conductor
- Connect the motor to a protective earth [kW] type
and provide protection against indirect [mm2] [AWG]
contact in accordance with local
Solid 1.5 - 10 16-8
regulations. 1.1 - 1.5
Stranded 1.5 - 10 16-8
Protective-earth conductors must always have a
yellow/green (PE) or yellow/green/blue (PEN) colour Solid 2.5 - 10 14-8
marking. 2.2 - 5.5
Stranded 2.5 - 10 14-8
7.1.1 Protection against mains voltage transients
7.2.2 Conductors
The motor is protected against mains voltage
transients in accordance with EN 61800-3. Type
7.1.2 Motor protection Stranded or solid copper conductors.
The motor requires no external motor protection. The Temperature rating
motor incorporates thermal protection against slow Temperature rating for conductor insulation: 60 °C
overloading and blocking. (140 °F).
Temperature rating for outer cable sheath: 75 °C
(167 °F).
9
7.3 Mains supply The wires in the motor terminal box must be as short
as possible. Excepted from this is the separated
English (GB)
type B
RCD,
type B
10
7.4 Additional protection Overtemperature protection
The electronic unit has a built-in temperature sensor
English (GB)
DANGER as an additional protection. When the temperature
Electric shock rises above a certain level, the motor automatically
compensates for this by reducing the speed and
- Death or serious personal injury
stops if the temperature keeps rising. The motor
- Only use residual-current circuit
remains stopped for a set period. After this period,
breakers (ELCB, GFCI, RCD) of type B.
the motor automatically attempts to restart.
The residual-current circuit breaker must be marked
Protection against phase unbalance
with the following symbol:
Three-phase motors must be connected to a power
supply with a quality corresponding to IEC
60146-1-1, class C, to ensure correct motor
operation at phase unbalance. This also ensures
long life of the components.
The total leakage current of all the electrical
equipment in the installation must be taken into 7.5 Connection terminals
account. You find the leakage current of the motor in The descriptions and terminal overviews in this
sections 26.2 Leakage current and 27.2 Leakage section apply to both single- and three-phase
current (AC). motors.
This product can cause a direct current in the For maximum torques, see section Torques, page
protective earth conductor. 73.
Overvoltage and undervoltage protection
7.5.1 Connection terminals, CRE, CRIE, CRNE,
Overvoltage and undervoltage may occur in case of SPKE and MTRE pumps
unstable power supply or a faulty installation. The
CRE, CRIE, CRNE, SPKE and MTRE pumps have a
motor is stopped if the voltage falls outside the
number of inputs and outputs enabling the pumps to
permissible voltage range. The motor restarts
be used in advanced applications where many inputs
automatically when the voltage is again within the
and outputs are required.
permissible voltage range. Therefore, no additional
protection relay is required. The pumps have these connections:
• three analog inputs
The motor is protected against transients • one analog output
from the power supply according to EN
61800-3. In areas with high lightning • two dedicated digital inputs
intensity, we recommend external lightning • two configurable digital inputs or open-collector
protection. outputs
• Grundfos Digital Sensor input and output
Overload protection
• two Pt100/1000 inputs
If the upper load limit is exceeded, the motor
automatically compensates for this by reducing the • two LiqTec sensor inputs
speed and stops if the overload condition persists. • two signal relay outputs
The motor remains stopped for a set period. After • GENIbus connection.
this period, the motor automatically attempts to See fig. 8.
restart. The overload protection prevents damage to
the motor. Consequently, no additional motor
protection is required.
11
Digital input 1 is factory-set to be start-stop
English (GB)
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by NC
reinforced insulation in their entire C1
lengths. NO
VAC. 20 GND
22 LiqTec
PELV: +24 V*
OC
GND
DI
The output is galvanically separated from 10 DI3/OC1
12
Terminal Type Function Terminal Type Function
English (GB)
Normally closed A GENIbus, A GENIbus, A (+)
NC
contact Y GENIbus, Y GENIbus, GND
Signal relay 1
C1 Common B GENIbus, B GENIbus, B (-)
(LIVE or PELV)
Normally open
NO
contact 3 GND Ground
15 +24 V Supply
Normally closed
NC 8 +24 V Supply
contact
Signal relay 2 Supply to
C2 Common
(PELV only) 26 +5 V potentiometer and
Normally open sensor
NO
contact
23 GND Ground
18 GND Ground Grundfos Digital
25 GDS TX
Sensor output
Digital input/output,
configurable. Grundfos Digital
24 GDS RX
11 DI4/OC2 Open collector: Max. Sensor input
24 V resistive or
Analog input:
inductive.
0-20 mA / 4-20 mA
7 AI2
Pt100/1000 Pt100/1000 sensor 0.5 - 3.5 V / 0-5 V /
19
input 2 input 0-10 V
Pt100/1000 Pt100/1000 sensor
17
input 1 input
Analog output:
12 AO 0-20 mA / 4-20 mA
0-10 V
9 GND Ground
Analog input:
14 AI3 0-20 mA / 4-20 mA
0-10 V
Digital input,
1 DI2
configurable
Digital input/output,
configurable.
10 DI3/OC1 Open collector: Max.
24 V resistive or
inductive.
Analog input:
0-20 mA / 4-20 mA
4 AI1
0.5 - 3.5 V / 0-5 V /
0-10 V
Digital input,
2 DI1
configurable
Supply to
5 +5 V potentiometer and
sensor
6 GND Ground
13
7.5.2 Connection terminals, MTHE, CME pumps
The MTHE, CME pump has these connections:
English (GB)
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by
reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from
the mains-conducting parts by reinforced insulation
and galvanically separated from other circuits. All
control terminals are supplied by protective extra-low
voltage (PELV), thus ensuring protection against
electric shock.
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250
VAC to the output.
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
• Mains supply (terminals N, PE, L or L1, L2, L3,
PE).
14
Terminal Type Function
English (GB)
Normally
NC
closed contact
Signal relay 1
C1 Common
(LIVE or PELV)
Normally open
NO
contact
Normally
NC
closed contact
Signal relay 2
C2 Common
NC
(PELV only)
Normally open
C1 NO
NO contact
NC
C2 Digital input/output,
NO configurable.
10 DI3/OC1 Open collector: Max.
OC DI
+24 V* GND
10 DI3/OC1
4 AI1 24 V resistive or
+24 V* +24 V* +24 V*/5 V*
+ +
2 DI1 inductive.
5 +5 V
6 GND
Analog input:
0-20 mA / 4-20 mA
A GENIbus A 4 AI1
Y GENIbus Y
0.5 - 3.5 V / 0-5 V /
B GENIbus B
0-10 V
3 GND Digital input,
2 DI1
15 +24 V configurable
8 +24 V
TM05 3510 3512
26 +5 V Supply to
23 GND 5 +5 V potentiometer and
+24 V* +24 V* +24 V*/5 V* + + 25 GDS TX sensor
24 GDS RX
+5 V* 7 AI2
6 GND Ground
A GENIbus, A GENIbus, A (+)
* If you use an external supply source, there must Y GENIbus, Y GENIbus, GND
be a connection to GND.
B GENIbus, B GENIbus, B (-)
Fig. 9 Connection terminals, MTHE, CME pump
(optional for CRE, CRIE, CRNE, SPKE
3 GND Ground
and MTRE pumps)
15 +24 V Supply
8 +24 V Supply
Supply to
26 +5 V potentiometer and
sensor
23 GND Ground
Grundfos Digital
25 GDS TX
Sensor output
Grundfos Digital
24 GDS RX
Sensor input
Analog input:
0-20 mA / 4-20 mA
7 AI2
0.5 - 3.5 V / 0-5 V /
0-10 V
15
7.6 Signal cables 7.7 Bus connection cable
English (GB)
Motor
16
8. Operating conditions 8.3 Installation altitude
English (GB)
Installation altitude is the height above sea level of
8.1 Maximum number of starts and stops the installation site.
The number of starts and stops via the power supply Motors installed up to 1000 m above sea level can
must not exceed four times per hour. be loaded 100 %.
When switched on via the power supply, the pump The motors can be installed up to 3500 m above sea
starts after approximately 5 seconds. level.
If a higher number of starts and stops is desired, use
the input for external start-stop when Motors installed more than 1000 m above
starting/stopping the pump. sea level must not be fully loaded due to
the low density and consequent low
When started via an external on/off switch, the pump cooling effect of the air.
starts immediately.
17
In order to maintain the galvanic isolation and ensure 9. User interfaces
correct clearance according to EN 60664-1:2007,
English (GB)
210
200
0 500 1000 1500 2000 2500 3000 3500 4000
Altitude [m]
8.4 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %,
open the drain holes in the drive-end flange. See
section 6.7 Drain holes.
18
10. Standard control panel 10.1 Setpoint setting
English (GB)
The pumps are fitted with this control panel as Set the desired setpoint of the pump by pressing
standard. or . The green light fields on the control panel
indicate the setpoint set.
10.1.1 Pump in constant pressure control mode
1
The following example applies to a pump in an
application where a pressure sensor gives a
2 feedback to the pump. If the sensor is retrofitted to
the pump, you must set it up manually as the pump
does not automatically register a connected sensor.
3 See section 13.7 Analog inputs.
Figure 17 shows that the light fields 5 and 6 are
bar
Fig. 16 Standard control panel 6
19
10.1.2 Pump in constant-curve control mode Example: Pump set to minimum curve.
In constant-curve control mode, the pump Figure 20 shows that the bottom light field is
English (GB)
performance lies between the maximum and flashing, indicating minimum curve.
minimum curve of the pump. See fig. 18.
H
H
Max.
20
11. Advanced control panel Pos. Symbol Description
English (GB)
The pumps can be fitted with the advanced control
panel as an option. Saves changed values, resets
alarms and expands the value field.
Enables radio communication with
Grundfos GO Remote and other
1 products of the same type.
When you try to establish radio
communication between the pump
and Grundfos GO Remote or
2
another pump, the green indicator
4
light in Grundfos Eye flashes. A
6 3
note also appears in the pump
21
11.1 Home display
Pos. Symbol Description
English (GB)
1 2 3 4
Indicates that the possibility to
make settings has been disabled
Home for protective reasons. See
Status Settings Assist 9
section 13.33 "Buttons on
Setpoint Control mode product" (Enable/disable
Const. pressure settings).
5.00 bar
11.2 Startup guide
Operating mode Actual controlled value
The pump incorporates a startup guide which is
Normal started at the first startup. See section 13.41 Run
4.90 bar
9 8 7 6 5
Home
This menu shows up to four
user-defined parameters. You can
select parameters shown as
1
shortcut icon , and when
pressing you go directly to the
"Settings" display for the selected
parameter.
Status
This menu shows the status of the
2 -
pump and system as well as
warnings and alarms.
Settings
This menu gives access to all
setting parameters. You can make
3 - detailed settings of the pump in
this menu.
See section 13. Description of
functions.
Assist
This menu enables assisted pump
setup, provides a short
4 -
description of the control modes
and offers fault advice.
See section 13.44 Assist.
22
11.3 Menu overview for advanced control panel
English (GB)
11.3.1 Home
CRE, CRIE,
Home CRNE, SPKE, MTHE, Multipump
CME system
MTRE
● ● ●
11.3.2 Status
CRE, CRIE,
Status CRNE, SPKE, MTHE, Multipump
CME system
MTRE
Operating status ● ● ●
Operating mode, from ● ● ●
Control mode ● ● ●
Pump performance ● ● ●
Actual controlled value ● ● ●
Resulting setpoint ● ● ●
Speed ● ● ●
Acc. flow and specific energy ● ● ●
Power and energy consumption ● ● ●
Measured values ● ● ●
Analog input 1 ● ● ●
Analog input 2 ● ● ●
Analog input 3 ● ● 1) ● 1)
Pt100/1000 input 1 ● ● 1) ● 1)
Pt100/1000 input 2 ● ● 1) ● 1)
1)
Analog output ● ● ● 1)
Warning and alarm ● ● ●
Actual warning or alarm ● ● ●
Warning log ● ● ●
Alarm log ● ● ●
Operating log ● ● ●
Operating hours ● ● ●
Fitted modules ● ● ●
Date and time ● ● ●
Product identification ● ● ●
Motor bearing monitoring ● ● ●
Multi-pump system ●
System operating status ●
System performance ●
System input power and energy ●
Pump 1, multi-pump system ●
Pump 2, multi-pump system ●
Pump 3, multi-pump system ●
Pump 4, multi-pump system ●
1) Only available if an advanced functional module, type FM 300, is fitted.
23
11.3.3 "Settings"
English (GB)
CRE, CRIE,
Settings CRNE, MTHE, Multipump Section Page
system
SPKE, MTRE CME
Setpoint ● ● ● 13.1 Setpoint 30
Operating mode ● ● ● 13.2 Operating mode 30
Set manual speed ● ● ● 13.3 Set manual speed 30
Set user-defined speed ● ● ● 13.4 "Set user-defined speed" 30
Control mode ● ● ● 13.5 "Control mode" 31
Setting the proportional 13.6 Setting the proportional
● ● ● 36
pressure pressure
Analog inputs ● ● ●
Analog input 1, setup ● ● ●
13.7 Analog inputs 36
Analog input 2, setup ● ● ●
1) 1)
Analog input 3, setup ● ● ●
Pt100/1000 inputs ● ● 1) ● 1)
Pt100/1000 input 1, setup ● ● 1) ● 1) 13.8 Pt100/1000 inputs 37
Pt100/1000 input 2, setup ● ● 1) ● 1)
Digital inputs ● ● ●
Digital input 1, setup ● ● ● 13.9 Digital inputs 38
Digital input 2, setup ● ● 1) ● 1)
Digital inputs/outputs ● ● ●
Digital input/output 3, setup ● ● ● 13.10 Digital inputs/outputs 39
Digital input/output 4, setup ● ● 1) ● 1)
Relay outputs ● ● ●
13.11 "Signal relays" 1 and 2
Relay output 1 ● ● ● 40
(Relay outputs)
Relay output 2 ● ● ●
Analog output ● ● 1) ● 1)
Output signal ● ● 1) ● 1) 13.12 Analog output 41
Function of analog output ● ● 1) ● 1)
13.13 "Controller" (Controller
Controller settings ● ● ● 42
settings)
Operating range ● ● ● 13.14 Operating range 43
13.15 External setpoint
Setpoint influence ● ● ● 44
function
13.15 External setpoint
Ext. setpoint infl. ● ● ● 44
function
1) 1)
Predefined setpoints ● ● ● 13.16 Predefined setpoints 45
Monitoring functions ● ● ●
13.26 Motor bearing
Motor bearing monitoring ● ● ● 50
monitoring
"Bearings replaced" (Motor
Motor bearing maintenance ● ● ● 51
bearing maintenance)
Limit-exceeded function ● ● ● 13.17 Limit-exceeded function 46
13.18 "LiqTec" (LiqTec
LiqTec function ● ● ● 47
function)
Alarm handling ● ● ● 13.25 Alarm handling 50
1) Only available if an advanced functional module, type FM 300, is fitted.
Continued on page 25.
24
Continued from page 24.
English (GB)
CRE, CRIE,
Settings CRNE, MTHE, Multipump Section Page
SPKE, MTRE CME
system
Special functions ● ● ●
13.19 "Stop function"
Low-flow stop function ● ● ● 47
(Low-flow stop function)
Stop at min. speed ● ● ● 13.20 Stop at min. speed 49
Pipe filling function ● ● ● 13.21 Pipe filling function 49
13.22 "Pulse flowmeter"
Pulse flowmeter setup ● ● ● 50
(Pulse flowmeter setup)
Ramps ● ● ● 13.23 Ramps 50
Standstill heating ● ● ● 13.24 Standstill heating 50
Communication ● ● ●
13.28 "Number" (Pump
Pump number ● ● ● 51
number)
13.29 "Radio communication"
Enable/disable radio comm. ● ● ● 51
(Enable/disable radio comm.)
General settings ● ● ●
Language ● ● ● 13.30 Language 51
13.31 "Date and time" (Set
Set date and time ● ● ● 52
date and time)
13.32 "Unit configuration"
Units ● ● ● 52
(Units)
13.33 "Buttons on product"
Enable/disable settings ● ● ● 52
(Enable/disable settings)
Delete history ● ● ● 13.34 Delete history 52
Define Home display ● ● ● 13.35 Define Home display 53
Display settings ● ● ● 13.36 Display settings 53
13.37 "Store settings" (Store
Store actual settings ● ● ● 53
actual settings)
13.38 "Recall settings" (Recall
Recall stored settings ● ● ● 53
stored settings)
Run start-up guide ● ● ● 13.41 Run start-up guide 54
1) Only available if an advanced functional module, type FM 300, is fitted.
11.3.4 Assist
CRE, CRIE,
Assist CRNE, MTHE, Multipump Section Page
system
SPKE, MTRE CME
Assisted pump setup ● ● ● 13.45 Assisted pump setup 55
Setup, analog input ● ● ● 13.46 Setup, analog input 55
Setting of date and time ● ● ● 13.47 Setting of date and time 56
13.48 "Multi-pump setup"
Setup of multi-pump system ● ● ● 56
(Setup of multi-pump system)
13.49 Description of control
Description of control mode ● ● ● 59
mode
Assisted fault advice ● ● ● 13.50 Assisted fault advice 59
25
12. Grundfos GO Remote 12.1 Communication
English (GB)
The pump is designed for wireless radio or infrared When Grundfos GO Remote initiates communication
communication with Grundfos GO Remote. with the pump, the indicator light in the middle of
Grundfos GO Remote enables setting of functions Grundfos Eye flashes green. See section
and gives access to status overviews, technical 16. Grundfos Eye.
product information and actual operating Furthermore, on pumps fitted with an advanced
parameters. control panel a text appears in the display saying
Grundfos GO Remote offers the following mobile that a wireless device is trying to establish
interfaces (MI). connection. Press on the pump in order to
establish connection with Grundfos GO Remote or
press to reject connection.
Establish communication using one of these
communication types:
• radio communication
• infrared communication.
1 12.1.1 Radio communication
Grundfos MI 301:
Separate module enabling radio or infrared
1 communication. You can use the module in
conjunction with an Android or iOS-based
smart device with Bluetooth connection.
26
12.2 Menu overview for Grundfos GO Remote
English (GB)
CRE, CRIE,
Dashboard CRNE, MTHE, Multipump
system
SPKE, MTRE CME
● ● ●
CRE, CRIE,
"Status" CRNE, MTHE, Multipump
SPKE, MTRE CME
system
"System mode" ● 2)
"Resulting setpoint" ● ●
"Resulting system setpoint" ● 2)
"Actual controlled value" ● ● ● 2)
"Motor speed" ● ●
"Power consumption" ● ●
"Power cons., sys." ● 2)
"Energy consumption" ● ●
"Energy cons., sys." ● 2)
"Acc. flow, specific energy" ● ● ● 2)
"Operating hours" ● ●
"Operating hours, system" ● 2)
1)
"Pt100/1000 input 1" ● ●
"Pt100/1000 input 2" ● ● 1)
"Analog output" ● ● 1)
"Analog input 1" ● ●
"Analog input 2" ● ●
"Analog input 3" ● ● 1)
"Digital input 1" ● ●
"Digital input 2" ● ● 1)
"Digital in/output 3" ● ●
"Digital in/output 4" ● ● 1)
"Fitted modules" ● ●
"Pump 1" ● 2)
"Pump 2" ● 2)
"Pump 3" ● 2)
"Pump 4" ● 2)
1)
Only available if an advanced functional module, type FM 300, is fitted.
2)
Only available if Grundfos GO Remote is connected to a multipump system.
27
CRE, CRIE,
English (GB)
Multipump
"Settings" CRNE, MTHE, Section Page
system
SPKE, MTRE CME
"Setpoint" ● ● ● 13.1 Setpoint 30
"Operating mode" ● ● ● 13.2 Operating mode 30
"Set user-defined speed" ● ● ● 13.4 "Set user-defined speed" 30
"Control mode" ● ● ● 13.5 "Control mode" 31
"Setting the proportional 13.6 Setting the proportional
● ● ● 36
pressure" pressure
"Pipe-filling function" ● ● ● 13.21 Pipe filling function 49
13.33 "Buttons on product"
"Buttons on product" ● ● 52
(Enable/disable settings)
13.18 "LiqTec" (LiqTec
"LiqTec" ● ● 1) 47
function)
13.19 "Stop function" (Low-flow
"Stop function" ● ● ● 47
stop function)
"Stop at min. speed" ● ● ● 13.20 Stop at min. speed 49
13.13 "Controller" (Controller
"Controller" ● ● ● 42
settings)
"Operating range" ● ● ● 13.14 Operating range 43
"Ramps" ● ● 13.23 Ramps 50
13.28 "Number" (Pump
"Number" ● ● 51
number)
13.29 "Radio communication"
"Radio communication" ● ● 51
(Enable/disable radio comm.)
"Analog input 1" ● ●
"Analog input 2" ● ● 13.7 Analog inputs 36
"Analog input 3" ● ● 1)
"Pt100/1000 input 1" ● ● 1)
13.8 Pt100/1000 inputs 37
"Pt100/1000 input 2" ● ● 1)
"Digital input 1" ● ●
13.9 Digital inputs 38
"Digital input 2" ● ● 1)
"Digital in/output 3" ● ●
13.10 Digital inputs/outputs 39
"Digital in/output 4" ● ● 1)
13.22 "Pulse flowmeter" (Pulse
"Pulse flowmeter" ● ● 50
flowmeter setup)
"Predefined setpoint" ● ● ● 13.16 Predefined setpoints 45
"Analog output" ● ● 1) 13.12 Analog output 41
13.15 External setpoint
"External setpoint funct." ● ● 44
function
"Signal relay 1" ● ● 13.11 "Signal relays" 1 and 2
40
"Signal relay 2" ● ● (Relay outputs)
1)
Only available if an advanced functional module, type FM 300, is fitted.
Continues on page 29.
28
Continued from page 28.
English (GB)
CRE, CRIE,
Multipump
"Settings" CRNE, MTHE, Section Page
system
SPKE, MTRE CME
"Limit 1 exceeded" ● ● ●
13.17 Limit-exceeded function 46
"Limit 2 exceeded" ● ● ●
"Alternating operation,
● 2)
time"
13.48 "Multi-pump setup"
"Sensor to be used" ● 2) 56
(Setup of multi-pump system)
"Time for pump 1) + 2)
●
changeover"
"Standstill heating" ● ● 13.24 Standstill heating 50
"Alarm handling" ● ● ● 13.25 Alarm handling 50
"Motor bearing monitoring" ● ● 13.26 Motor bearing monitoring 50
"Service" ● ● 13.27 "Service" 51
13.31 "Date and time" (Set date
"Date and time" ● ● 1) 52
and time)
13.37 "Store settings" (Store
"Store settings" ● ● 53
actual settings)
13.38 "Recall settings" (Recall
"Recall settings" ● ● 53
stored settings)
"Undo" ● ● ● 13.38.1 "Undo" 53
"Pump name" ● ● ● 13.39 "Pump name" 53
"Connection code" ● ● ● 13.40 "Connection code" 54
13.32 "Unit configuration"
"Unit configuration" ● ● 52
(Units)
1) Only available if an advanced functional module, type FM 300, is fitted.
2) Only available if Grundfos GO Remote is connected to a multipump system.
CRE, CRIE,
Multipump
"Alarms and warnings" CRNE, MTHE, Section Page
system
SPKE, MTRE CME
"Alarm log" ● ● ● 13.42 Alarm log 54
"Warning log" ● ● ● 13.43 Warning log 55
"Reset alarm" button ● ● ●
CRE, CRIE,
Multipump
"Assist" CRNE, MTHE, Section Page
system
SPKE, MTRE CME
"Assisted pump setup" ● ● 13.45 Assisted pump setup 55
"Assisted fault advice" ● ● ● 13.50 Assisted fault advice 59
13.48 "Multi-pump setup"
"Multi-pump setup" ● ● ● 56
(Setup of multi-pump system)
29
13. Description of functions All operating modes are illustrated in fig. 24.
English (GB)
13.1 Setpoint H
Max.
MTHE, CME ●
CRE, CRIE, CRNE, Normal
● Manual
SPKE, MTRE
30
13.5 "Control mode" 13.5.2 "Constant pressure"
English (GB)
Pump variant Control mode Pump variant "Constant pressure"
31
13.5.3 "Constant temperature" 13.5.4 "Constant differential pressure"
English (GB)
This control mode ensures a constant temperature. The pump maintains a constant differential pressure,
Constant temperature is a comfort control mode that independently of the flow in the system. See fig. 30.
you can use in domestic hot-water systems to control
the flow to maintain a fixed temperature in the H
system. See fig. 28.
p
Controller settings
For recommended controller settings, see section • Two pressure sensors.
13.13 "Controller" (Controller settings). Constant differential-pressure control is
Factory setting achievable with two pressure sensors. The
pump uses the inputs from the two sensors and
See section 24. Factory settings.
calculates the differential pressure.
Both sensors must have the same unit and must
be set as feedback sensors. You can set the
sensors manually, sensor by sensor, or by using
the Assist menu. See section 13.45 Assisted
pump setup.
p
p
p p
p
Controller settings
For recommended controller settings, see section
13.13 "Controller" (Controller settings).
Factory setting
See section 24. Factory settings.
32
13.5.5 "Constant differential temperature"
Examples
English (GB)
"Constant differential
Pump variant • One differential-temperature sensor.
temperature"
The pump uses the input from the sensor to
MTHE, CME ● control the differential temperature.
You can set the sensor manually or by using the
CRE, CRIE, CRNE, Assist menu. See section 13.45 Assisted pump
●
SPKE, MTRE setup.
The pump maintains a constant differential
temperature in the system and the pump
performance is controlled according to this. See fig.
32. t
H
• Two temperature sensors.
Constant differential-temperature control is
33
13.5.6 "Constant flow rate" 13.5.7 "Constant level"
English (GB)
The pump maintains a constant flow in the system, The pump maintains a constant level, independently
independently of the head. See fig. 34. of the flow rate. See fig. 36.
H
H
Controller settings
For recommended controller settings, see section
13.13 "Controller" (Controller settings).
Factory setting
See section 24. Factory settings.
34
The type of level control function depends on the 13.5.8 "Constant other value"
setting of the built-in controller. See section
English (GB)
13.13 "Controller" (Controller settings). Pump variant "Constant other value"
MTHE, CME ●
CRE, CRIE, CRNE,
●
SPKE, MTRE
Fig. 37 "Constant level" You can set the pump to operate according to a
constant curve, like an uncontrolled pump. See fig.
Controller settings 38.
For recommended controller settings, see section The desired speed can be set in % of maximum
13.13 "Controller" (Controller settings). speed in the range from 13 to 100 %.
Factory setting
See section 24. Factory settings. H
Controller settings
For recommended controller settings, see section
13.13 "Controller" (Controller settings).
Factory setting
See section 24. Factory settings.
35
13.6 Setting the proportional pressure Function
The analog inputs can be set to these functions:
English (GB)
FM 200* FM 300*
Function (terminal) Fig. 39 Overview of sensor locations
(standard) (advanced)
36
Unit 13.8 Pt100/1000 inputs
English (GB)
Available inputs depend on the functional module
Parameter Possible units fitted in the pump:
Pressure bar, m, kPa, psi, ft
FM 200* FM 300*
Level m, ft, in Function (terminal)
(standard) (advanced)
Pump flow m³/h, l/s, yd³/h, gpm
Pt100/1000 input 1,
- ●
Liquid temperature °C, °F setup (17 and 18)
Other parameter % Pt100/1000 input 2,
- ●
setup (18 and 19)
Electrical signal
Select signal type: * See section 19. Identification of functional
module.
• 0.5-3.5 V
• 0-5 V If you want to set the Pt100/1000 input for a
feedback sensor, we recommend that you do this via
• 0-10 V
the Assisted pump setup menu. See section
• 0-20 mA 13.45 Assisted pump setup.
• 4-20 mA. If you want to set a Pt100/1000 input for other
Sensor range, minimum value purposes, you can do this manually.
Set the minimum value of the connected sensor. You can set the analog inputs via the Setup, analog
input menu. See section 13.46 Setup, analog input.
Sensor range, maximum value
If you make the manual setting via Grundfos GO
Set the maximum value of the connected sensor. Remote, you need to enter the menu for the
Factory setting Pt100/1000 input under the Settings menu.
See section 24. Factory settings. Function
13.7.1 Setting two sensors for differential The Pt100/1000 inputs can be set to these functions:
measurement • Not active
In order to measure the difference of a parameter • Feedback sensor
between two points, set the corresponding sensors The sensor is used for the selected control mode.
as follows: • Ext. setpoint infl.
See section 13.15 External setpoint function.
Analog input Analog input • Other function.
Parameter
for sensor 1 for sensor 2
37
Measured parameter • Max. (maximum speed).
Select one of the parameters listed below, i.e. the When the input is activated, the pump runs at the
English (GB)
38
Activation delay 13.10 Digital inputs/outputs
Select the activation delay (T1).
English (GB)
It is the time between the digital signal and the Pump variant Digital inputs/outputs
activation of the selected function.
MTHE, CME ●
Range: 0-6000 seconds.
CRE, CRIE, CRNE,
Duration timer mode ●
SPKE, MTRE
Select the mode. See fig. 41.
• Not active Available inputs/outputs depend on the functional
• active with interrupt (mode A) module fitted in the pump:
• active without interrupt (mode B)
FM 200* FM 300*
• active with after-run (mode C). Function (terminal)
(standard) (advanced)
Select the duration time (T2).
It is the time which, together with the mode, Digital input/output 3,
● ●
determines how long the selected function is active. setup (6 and 10)
Range: 0 to 15,000 seconds. Digital input/output 4,
- ●
setup (11 and 18)
T input > T1 + T2 T input < T1 + T2
T input > T1 + T2 T input < T1 + T2 * See section 19. Identification of functional
module.
Digital
input You can select if the interface is to be used as input
TT input
input TTinput
input or output. The output is an open collector and you
can connect it to e.g. an external relay or controller
Mode A such as a PLC.
T1 T2 T1
TM06 4949 3415
Mode B + 24V
T1 T2 T1 T2
Factory setting
See section 24. Factory settings. Fig. 42 Example of configurable digital
inputs/outputs
39
Possible functions, digital input/output 3 Duration timer mode (only for input)
Select the duration timer mode. See fig. 41.
English (GB)
40
• "Operating" (Operation). Function of analog output
"Operating" equals "Running" but the pump is still • Actual speed
English (GB)
in operation when the pump is stopped due to low
flow. See section "Low-flow detection" on page
Actual speed
48. Signal
[%]
• "Running" (Pump running). range
The pump is running. [V, mA]
0 100 200
• Warning.
There is an active warning. 0-10 V 0V 5V 10 V
• Digital input 1, state 0-20 mA 0 mA 10 mA 20 mA
If digital input 1 is activated, the output is also
4-20 mA 4 mA 12 mA 20 mA
activated.
• Digital input 2, state The reading is a percentage of the rated speed.
If digital input 2 is activated, the output is also • Actual value
activated.
• Digital input 3, state Signal "Actual value"
If digital input 3 is activated, the output is also range
activated. [V, mA] Sensormin Sensormax
• Digital input 4, state
If digital input 4 is activated, the output is also 0-10 V 0V 10 V
activated. 0-20 mA 0 mA 20 mA
• Limit 1 exceeded
When this function is activated, the signal relay is 4-20 mA 4 mA 20 mA
activated. See section 13.17 Limit-exceeded
The reading is a percentage of the range between
function.
the minimum and maximum value.
• Limit 2 exceeded.
• Resulting setpoint
When this function is activated, the signal relay is
activated. See section 13.17 Limit-exceeded
function. Resulting setpoint
Signal
[%]
• "External fan control" (Control of external fan). range
When you select "External fan control", the relay [V, mA]
0 100
is activated if the internal temperature of the
motor electronics reach a preset limit value. 0-10 V 0V 10 V
Factory setting 0-20 mA 0 mA 20 mA
See section 24. Factory settings.
4-20 mA 4 mA 20 mA
13.12 Analog output The reading is a percentage of the external setpoint
range.
Pump variant Analog output • Motor load
MTHE, CME ●
Motor load
CRE, CRIE, CRNE, Signal
● [%]
SPKE, MTRE range
[V, mA]
0 100
Whether the analog output is available or not,
depends on the functional module fitted in the pump: 0-10 V 0V 10 V
0-20 mA 0 mA 20 mA
FM 200* FM 300*
Function (terminal) 4-20 mA 4 mA 20 mA
(standard) (advanced)
Analog output - ●
41
The reading is a percentage of the range between 0 13.13 "Controller" (Controller settings)
and 200 % of the maximum permissible load at the
English (GB)
actual speed.
"Controller"
• Motor current Pump variant
(Controller settings)
Flow rate
Signal
[%] p
range 0.5 0.5
[V, mA]
0 100 200 p
0-10 V 0V 5V 10 V p p
0-20 mA 0 mA 10 mA 20 mA
4-20 mA 4 mA 12 mA 20 mA L1
ǻS
The reading is a percentage of the range between 0 L1 < 5 m: 0.5
and 200 % of the nominal flow. 0.5 L1 > 5 m: 3
Factory setting L1 L1 > 10 m: 5
See section 24. Factory settings. ǻS
42
Kp Constant level Kp Ti
English (GB)
Constant
Ti
temperature Heating Cooling L
system 1) system 2)
-10 0
L2
10 0
L2
t
• Set the maximum speed within the range from
L2
user-set minimum speed to fixed maximum
speed.
L2: Distance [m] between heat exchanger and
The range between the user-set minimum and
sensor.
maximum speeds is the operating range. See fig. 44.
Operating range
Constant pressure Kp Ti
TM00 6785 5095
Factory setting
See section 24. Factory settings.
43
13.15 External setpoint function Example with constant curve with linear
influence
English (GB)
Sensor 0 0
Actual External Setpoint influence [%]
min. 0 100 %
0.5
0
input 3.5 V
5V
setpoint
0 signal 10 V signal 100
0 20 mA
4 (60 %) 20 mA
-50 204 C
0
0 100 % External
0.5 3.5 V input
0 5V
0 10 V
0 20 mA
4 20 mA
-50 204 C
44
• Linear with Stop 13.16 Predefined setpoints
In the input signal range from 20 to 100 %, the
English (GB)
setpoint is influenced linearly.
Pump variant Predefined setpoints
If the input signal is below 10 %, the pump
changes to operating mode Stop. MTHE, CME -
If the input signal is increased above 15 %, the
operating mode is changed back to Normal. CRE, CRIE, CRNE,
●
See fig. 48. SPKE, MTRE
0
0 20 100 % External Digital
0.5 3.5 V input inputs
0 5V Setpoint
0 10 V
0 20 mA 2 3 4
4 20 mA
-50 204 C 0 0 0 Normal setpoint or stop
TM06 4167 1615
1 0 0 Predefined setpoint 1
Normal
0 1 0 Predefined setpoint 2
Stop
1 1 0 Predefined setpoint 3
0 0 1 Predefined setpoint 4
Fig. 48 Linear with Stop
1 0 1 Predefined setpoint 5
• Influence table. 0 1 1 Predefined setpoint 6
The setpoint is influenced by a curve made out of
two to eight points. There is a straight line 1 1 1 Predefined setpoint 7
between the points and a horizontal line before 0: Open contact
the first point and after the last point. 1: Closed contact
External
4
Setpoint 4
0 100 % Actual setpoint
input
3
Setpoint 3
TM06 4269 1815
0.5 3.5 V
2
0 5V Setpoint 2
0 10 V 1
0 Setpoint 1
0 20 mA
4 20 mA
-50 204 C Normal
setpoint
Stop
Fig. 49 Influence table (example with five
points) Fig. 50 Principle sketch showing how
Factory setting predefined setpoints function
See section 24. Factory settings. If all digital inputs are open, the pump stops or runs
at the normal setpoint. Set the desired action with
Grundfos GO Remote or with the advanced control
panel.
Factory setting
See section 24. Factory settings.
45
13.17 Limit-exceeded function • Alarm + User-defined speed
An alarm is given, and the pump runs at the
English (GB)
English (GB)
"LiqTec" • no unnecessary heating of the pumped liquid
Pump variant
(LiqTec function) • reduced wear of the shaft seals
• reduced noise from operation.
MTHE, CME -
The disadvantages of enabling the "Low-flow stop
CRE, CRIE, CRNE, function" may be the following:
●
SPKE, MTRE
• The delivered pressure is not completely
You can enable the function of the LiqTec sensors in constant as it fluctuates between the start and
this display. A LiqTec sensor protects the pump stop pressures.
against dry running. • The frequent starts/stops of the pump may in
The function requires that a LiqTec sensor has been some applications cause acoustic noise.
fitted and connected to the pump. The impact of the above disadvantages very much
When you have enabled the LiqTec function, it stops depends on the setting selected for the stop function.
the pump if dry running occurs. Restart the pump The High-comfort mode setting minimises pressure
manually if it has been stopped due to dry running. fluctuations and acoustic noise.
"Dry running detection delay" Select Energy-optimal mode if the main priority is to
reduce the energy consumption as much as
You can set a detection delay in order to make sure possible.
that the pump is given a chance to start up before
the LiqTec function stops the pump due to dry Possible settings of the stop function:
running. • Energy-optimal mode
Range: 0-254 seconds. The pump automatically adjusts the parameters
for the stop function so that the energy
Factory setting consumption during the start-stop operation
See section 24. Factory settings. period is minimised.
In this case, the stop function uses the
13.19 "Stop function" (Low-flow stop factory-set values of the minimum flow (Qmin1)
function) and other internal parameters. See fig. 52.
• High-comfort mode:
The pump automatically adjusts the parameters
"Stop function"
Pump variant for the stop function so that the disturbances
(Low-flow stop function)
during the start-stop operation period are
MTHE, CME ● minimised.
In this case, the stop function uses the
CRE, CRIE, CRNE, factory-set values of the minimum flow (Qmin2)
●
SPKE, MTRE and other internal parameters. See fig. 52.
You can set the "Low-flow stop function" to these • "User-defined mode" (Customised operating
values: mode):
The pump uses the parameters set for ΔH and
• Not active minimum flow (Qmin3) respectively for the stop
• Energy-optimal mode function. See fig. 52.
• High-comfort mode
• "User-defined mode" (Customised operating H
mode).
When the low-flow stop function is active, the flow is
monitored. If the flow becomes lower than the set
minimum flow (Qmin), the pump changes from
Stop pressure
continuous operation at constant pressure to
ƸH
TM06 4267 1815
Qmin2 Qmin1 Q
Qmin3
47
In start-stop operation, the pressure varies between Operating conditions for the low-flow stop
the start and stop pressures. See fig. 52. function
English (GB)
In "User-defined mode" (Customised operating You can only use the stop function if the system
mode), ΔH has been factory-set to 10 % of the actual incorporates a pressure sensor, a non-return valve
setpoint. ΔH can be set within the range from 5 to 30 and a diaphragm tank.
% of actual setpoint.
The pump changes to start-stop operation if the flow Always install the non-return valve before
becomes lower than the minimum flow. the pressure sensor. See figures 53 and
54.
The minimum flow is set in % of the nominal flow of
the pump (see the pump nameplate).
In "User-defined mode" (Customised operating Diaphragm tank
mode), the minimum flow has been factory-set to 10
% of nominal flow. Pressure sensor
Factory setting
48
"Diaphragm tank volume" The pipes are slowly filled with water. When the
The stop function requires a diaphragm tank of a pressure sensor of the system detects that the
English (GB)
certain minimum size. Set the size of the installed pipes have been filled, phase two begins.
tank in this display. 2. Pressure build-up phase.
In order to reduce the number of start-stops per hour The system pressure is increased until the
or to reduce the ΔH, install a larger tank. setpoint is reached. The pressure build-up takes
place over a pressure build-up time. If the
Install the tank immediately after the pump. The
setpoint is not reached within a given time, a
precharge pressure must be 0.7 x actual setpoint.
warning or an alarm can be given, and the pumps
Recommended diaphragm tank size: can be stopped at the same time.
Rated flow rate of Typical diaphragm tank 1. Filling phase 2. Pressure build-up
pump size (constant-curve phase
[m3/h] [litres] operation) (constant-pressure
Pressure
0-6 8 operation)
7-24 18
Setpoint
25-40 50
41-70 120
Setpoint
71-100 180 Filling pressure ramp-up
Factory setting
See section 24. Factory settings. Actual value
13.20 Stop at min. speed Time
This function stops the pump when consumption is Filling time Pressure [sec]
Factory setting
See section 24. Factory settings.
50
13.27 "Service" 13.29 "Radio communication"
(Enable/disable radio comm.)
English (GB)
"Time to next service" (Motor bearing service)
This display shows when to replace the motor
bearings. The controller monitors the operating "Radio communication"
pattern of the motor and calculates the period Pump variant (Enable/disable radio
between bearing replacements. comm.)
Displayable values: MTHE, CME ●
• "in 2 years"
CRE, CRIE, CRNE,
• "in 1 year" ●
SPKE, MTRE
• "in 6 months"
• "in 3 months" You can set the radio communication to either
enabled or disabled. You can use this function in
• "in 1 month" areas where radio communication is not allowed.
• "in 1 week"
• "Now"
IR communication remains active.
"Bearing replacements"
Indicates the number of bearing replacements that
have been done during the lifetime of the motor. Factory setting
See section 24. Factory settings.
"Bearings replaced" (Motor bearing
maintenance)
13.30 Language
When the bearing monitoring function is active, the
controller gives a warning when the motor bearings
are due to be replaced. Pump variant Language
When you have replaced the motor bearings, press MTHE, CME ●
[Bearings replaced].
CRE, CRIE, CRNE,
●
13.28 "Number" (Pump number) SPKE, MTRE
51
13.31 "Date and time" (Set date and time) 13.33 "Buttons on product"
(Enable/disable settings)
English (GB)
52
13.35 Define Home display 13.38 "Recall settings" (Recall stored
settings)
English (GB)
Pump variant Define Home display
"Recall settings"
MTHE, CME ● Pump variant
(Recall stored settings)
CRE, CRIE, CRNE,
● MTHE, CME ●
SPKE, MTRE
CRE, CRIE, CRNE,
This menu is only available in the advanced control ●
SPKE, MTRE
panel.
In this menu, you can set the Home display to show Grundfos GO Remote
up to four user-defined parameters. In this menu, you can recall stored settings from a
Factory setting number of previously stored settings that the pump
then uses.
See section 24. Factory settings.
Advanced control panel
13.36 Display settings In this menu, you can recall the last stored settings
that the pump then uses.
Pump variant Display settings
13.38.1 "Undo"
MTHE, CME ●
Pump variant "Undo"
CRE, CRIE, CRNE,
●
SPKE, MTRE MTHE, CME ●
This menu is only available in the advanced control CRE, CRIE, CRNE,
●
panel. SPKE, MTRE
In this menu, you can adjust the display brightness
This menu is only available in Grundfos GO Remote.
and set whether or not the display is to turn off if no
buttons have been activated for a period of time. In this display, you can undo all settings that have
been made with Grundfos GO Remote in the current
Factory setting communication session. Once you have recalled
See section 24. Factory settings. settings, you cannot undo.
53
13.40 "Connection code" 13.41 Run start-up guide
English (GB)
This menu is only available in Grundfos GO Remote. This menu is only available in the advanced control
You can set a connection code to avoid having to panel.
press the connection button each time and to restrict The startup guide automatically starts when you start
remote access to the product. the pump for the first time.
Setting the code in the product using Grundfos You can always run the startup guide later via this
GO Remote menu.
1. Connect Grundfos GO Remote to the product. The startup guide guides you through the general
settings of the pump.
2. In the product dashboard, select "Settings".
• Language. See section 13.30 Language.
3. Choose "Connection code".
• Select date format.*
4. Enter the wanted code and press [OK].
See section 13.31 "Date and time" (Set date and
The code must be a character string (ASCII).
time).
You can always change the code. The old code is
not needed. • Set date.*
See section 13.31 "Date and time" (Set date and
Setting the code in Grundfos GO Remote time).
You can define a default connection code in • Select time format.*
Grundfos GO Remote so that it automatically See section 13.31 "Date and time" (Set date and
attempts to connect to the selected product via this time).
code.
• Set time.*
When you select a product with the same connection See section 13.31 "Date and time" (Set date and
code in Grundfos GO Remote, Grundfos GO Remote time).
automatically connects to the product and you do not
• Setting of pump "
have to press the connection button on the module.
– Go to Home
Define the default code in Grundfos GO Remote in
this way: – Run with Constant curve/Run with Constant
pressure.
1. In the main menu, under "General", select
See section 13.5 "Control mode".
"Settings".
– Go to "Assisted pump setup".
2. Choose "Remote".
See section 13.45 Assisted pump setup.
3. Enter the connection code in the field "Preset
– Return to factory settings.
connection code". The field now says
"Connection code set". * Applies only for pumps fitted with advanced
functional module, FM 300. For further
You can always change the default connection code
information, see section 19. Identification of
by pressing [Delete] and entering a new one.
functional module.
If Grundfos GO Remote fails to connect and ask you
to press the connection button on the product, it 13.42 Alarm log
means that the product has no connection code or
has a different connection code. In this case, you This menu contains a list of logged alarms from the
can only establish connection via the connection product. The log shows the name of the alarm, when
button. the alarm occurred and when it was reset.
54
13.43 Warning log Advanced control panel
1. Open the Assist menu.
English (GB)
This menu contains a list of logged warnings from
the product. The log shows the name of the warning, 2. Select Assisted pump setup.
when the warning occurred and when it was reset. 3. Select control mode Const. pressure.
4. Select which analog input to be used as sensor
13.44 Assist
input.
This menu consist of a number of different assist 5. Select the measured parameter which is to be
functions which are small guides that take you controlled. See fig. 39 on page 36.
through the steps needed to set the pump.
6. Select measuring unit according to the sensor
13.45 Assisted pump setup specifications.
7. Set the minimum and maximum sensor range
values according to the sensor specifications.
Pump variant Assisted pump setup
8. Select electrical input signal according to the
MTHE, CME ● sensor specifications.
CRE, CRIE, CRNE, 9. Set the desired setpoint.
●
SPKE, MTRE 10. Set the gain and integral time of the controller.
See section 13.13 "Controller" (Controller
This menu guides you through the following: settings).
Setting of pump 11. Check the summary of settings and confirm them
• Selection of control mode. See page 31. by pressing [OK].
• Configuration of feedback sensors. 13.46 Setup, analog input
• Adjusting the setpoint. See page 30.
• Controller settings. See page 42. Pump variant Setup, analog input
• Summary of settings.
MTHE, CME ●
Example of how to use the Assisted pump setup
for setting up the pump to constant pressure: CRE, CRIE, CRNE,
●
SPKE, MTRE
Grundfos GO Remote
1. Open the Assist menu. This menu is only available in the advanced control
2. Select Assisted pump setup. panel.
3. Select control mode "Constant pressure" (Const. This menu guides you through the following:
pressure). Setup, analog input
4. Read the description for this control mode. • "Analog inputs" 1 to 3. See page 36.
5. Select which analog input to use as sensor input. • "Pt100/1000 input" 1 and 2. See page 37.
6. Select sensor function according to where the • "Adjusting the setpoint". See page 30.
sensor is installed in the system. See fig. 39 on • "Summary".
page 36.
7. Select electrical input signal according to the
sensor specifications.
8. Select measuring unit according to the sensor
specifications.
9. Set the minimum and maximum sensor range
values according to the sensor specifications.
10. Set the desired setpoint.
11. Set the gain and integral time of the controller.
See section 13.13 "Controller" (Controller
settings).
12. Type the desired pump name.
13. Check the summary of settings and confirm
them.
55
13.47 Setting of date and time 13.48 "Multi-pump setup" (Setup of
multi-pump system)
English (GB)
56
13.48.3 "Cascade operation" Grundfos GO Remote and wireless pump
Cascade operation is only available in CRE and connection
English (GB)
MTHE, CME pumps on request. Contact Grundfos 1. Power on the pumps.
for further information. 2. Establish contact to one of the pumps with
Cascade operation is possible with up to four pumps Grundfos GO Remote.
of the same size and type connected in parallel. 3. Set the needed analog and digital inputs via
Each pump requires a non-return valve in series with Grundfos GO Remote according to the
the pump. connected equipment and the required
Up to 4 pumps can be operating continuously functionality. See section 13.45 Assisted pump
depending on consumption. Pumps will be cut in and setup.
cut out to ensure a constant controlled value, for 4. Assign a pump name to the pump using Grundfos
example, constant pressure, and to ensure a high GO Remote. See section 13.39 "Pump name".
system efficiency and an even amount of running
5. Disconnect Grundfos GO Remote from the pump.
hours.
6. Establish contact to the next pump.
13.48.4 "Alternating operation, time" 7. Set the needed analog and digital inputs via
The interval of alternation between the two pumps. Grundfos GO Remote according to the
The function is only available in alternating connected equipment and the required
operation. See section 13.48.1 "Alternating functionality. See section 13.45 Assisted pump
operation". setup.
13.48.5 "Time for pump changeover" 8. Assign a pump name to the pump using Grundfos
GO Remote. See section 13.39 "Pump name".
Time of day for a pump changeover to take place.
The function is only available in alternating 9. Repeat steps 5 to 8 if more pumps are installed in
operation. See section 13.48.1 "Alternating the system.
operation". 10. Select the "Assist" menu and choose Setup of
multi-pump system.
13.48.6 "Sensor to be used"
11. Select the desired multipump function. See
Defines the sensor to be used for controlling the sections 13.48.1 "Alternating operation",
pump system. If a sensor is placed in a way that 13.48.2 "Backup operation" and
enables it to measure the output from all pumps in 13.48.3 "Cascade operation".
the system, for example, in the manifold, then select
"Master pump sensor". 12. Press [>] to continue.
If a sensor is placed on or across the individual 13. Set the time for a pump changeover i.e. the time
pumps, for example, installed behind non-return at which the alternation between the two pumps
valves and not able to measure the output from all is to take place.
pumps, then select "Running pump sensor".
This step applies only if you have selected
13.48.7 Setting up a multipump system "Alternating operation, time" and if the
You can set a multipump system in the following motors are fitted with FM 300.
ways: 14. Press [>] to continue.
• Grundfos GO Remote and wireless pump 15. Select "Radio" as the communication method to
connection be used between the pumps.
• Grundfos GO Remote and wired pump 16. Press [>] to continue.
connection
17. Select pump 2.
• Advanced control panel and wireless pump
18. Select the pump from the list.
connection
• If applicable, select pump 3 (only in cascade)
• Advanced control panel and wired pump
connection • If applicable, select pump 4 (only in cascade)
See step-by-step descriptions below.
Use the [OK] or button to identify the
pump.
57
Grundfos GO Remote and wired pump Advanced control panel and wireless pump
connection connection
English (GB)
1. Connect the pumps with each other with a 3-core 1. Power on the pumps.
screened cable between the GENIbus terminals 2. On the pumps, set the analog and digital inputs
A, Y, B. according to the connected equipment and the
2. Power on the pumps. required functionality. See section 13.45 Assisted
3. Establish contact to one of the pumps with pump setup.
Grundfos GO Remote. 3. Select the Assist menu on one of the pumps, and
4. Set the needed analog and digital inputs via choose Setup of multi-pump system.
Grundfos GO Remote according to the 4. Press [>] to continue.
connected equipment and the required 5. Select Wireless as the communication method to
functionality. See section 13.45 Assisted pump be used between the pumps.
setup.
6. Press [>] to continue.
5. Assign a pump name to the pump using Grundfos
7. Select the desired multipump function. See
GO Remote. See section 13.39 "Pump name".
sections 13.48.1 "Alternating
6. Assign pump number 1 to the pump. See section operation",13.48.2 "Backup operation" and
13.28 "Number" (Pump number). 13.48.3 "Cascade operation" above.
7. Disconnect Grundfos GO Remote from the pump. 8. Press [>] three times to continue.
8. Establish contact to the next pump. 9. Press [OK] to search for other pumps.
9. Set the needed analog and digital inputs via The green indicator light in the middle of
Grundfos GO Remote according to the Grundfos Eye flashes on the other pumps.
connected equipment and the required 10. Press the connect button on the pumps which are
functionality. See section 13.45 Assisted pump to be added to the multipump system.
setup.
11. Press [>] to continue.
10. Assign a pump name to the pump using Grundfos
12. Set the time for a pump changeover i.e. the time
GO Remote. See section 13.39 "Pump name".
at which the alternation between the two pumps
11. Repeat steps 7 to 10 if more pumps are installed is to take place.
in the system.
12. Select the "Assist" menu and choose Setup of This step applies only if you have selected
multi-pump system. "Alternating operation, time" and if the
13. Select the desired multipump function. See motors are fitted with FM 300.
sections 13.48.1 "Alternating operation", 13. Press [>] to continue.
13.48.2 "Backup operation" and
14. Press [OK] to confirm the setting.
13.48.3 "Cascade operation".
The multipump-function icons appear in the
14. Press [>] to continue. bottom of the control panels.
15. Set the time for a pump changeover i.e. the time
at which the alternation between the two pumps
is to take place.
58
Advanced control panel and wired pump Disabling a multipump system via the advanced
connection control panel
English (GB)
1. Connect the pumps with each other with a 3-core 1. Select the Assist menu.
screened cable between the GENIbus terminals 2. Select Setup of multi-pump system.
A, Y, B.
3. Press [>] to continue.
2. On the pumps, set the needed analog and digital
4. Confirm No multi-pump function by pressing
inputs according to the connected equipment and
[OK].
the required functionality. See section
13.45 Assisted pump setup. 5. Press [>] to continue.
3. Assign pump number 1 to the first pump. See 6. Press [OK] to confirm.
section 13.28 "Number" (Pump number).
13.49 Description of control mode
4. Assign pump number 2 to the next pump. See
section 13.28 "Number" (Pump number). This menu is only available in the advanced control
5. Assign pump number 3 and 4 if more than two panel.
pumps are installed in the system. See sections This menu describes each of the possible control
13.48.3 "Cascade operation" and modes. See also section 13.5 "Control mode".
13.28 "Number" (Pump number).
6. Select the Assist menu on one of the pumps and 13.50 Assisted fault advice
choose Setup of multi-pump system. This menu gives guidance and corrective actions in
7. Press [>] to continue. case of pump failures.
8. Select Wired GENIbus as the communication
method to be used between the two pumps. 14. Bus signal
9. Press [>] twice to continue. The pump supports serial communication via an
10. Select the desired multipump function. See RS-485 input. The communication is carried out
sections 13.48.1 "Alternating operation", according to the Grundfos GENIbus protocol and
13.48.2 "Backup operation" and enables connection to other pumps as well as a
13.48.3 "Cascade operation" above. building management system or another external
control system.
11. Press [>] to continue.
Via a bus signal, you can remote-set pump operating
12. Press [OK] to search for other pumps.
parameters, such as setpoint and operating mode. At
13. Select the pump from the list. the same time, the pump can, via the bus, provide
14. Press [>] to continue. status information about important parameters, such
15. Set the time for a pump changeover i.e. the time as actual value of control parameter, input power and
at which the alternation between the two pumps fault indications.
is to take place. Contact Grundfos for further information.
This step applies only if you have selected If you use a bus signal, the number of
"Alternating operation, time" and if the settings available via R100 or Grundfos
motors are fitted with FM 300. GO Remote are reduced.
16. Press [>] to continue.
17. Press [OK] to confirm the setting.
The multipump function icons appear in the
bottom of the control panels.
Disabling a multipump system via Grundfos GO
Remote
1. Select the "Assist" menu.
2. Select Setup of multi-pump system.
3. Select "Disable".
4. Press [>] to continue.
5. Confirm the setting by pressing [Send].
6. Press [Finish].
59
15. Priority of settings
English (GB)
1 Stop
2 Stop*
3 Manual
"Max. speed"* /
4
"User-defined speed"
5 Stop
"User-defined
6
speed"
7 Stop
8 "Max. speed"
9 "Min. speed"
10 "Start"
11 "Max. speed"
12 "Min. speed"
13 "Min. speed"
14 "Start"
15 "Start"
60
16. Grundfos Eye
English (GB)
The operating condition of the pump is indicated by
Grundfos Eye on the control panel. See fig. 57, A.
The green indicator light in the middle This is a feedback signal which the
flashes quickly four times. pump gives in order to ensure
identification of itself.
61
17. Signal relays
English (GB)
The power is
-
off.
Off C NO NC C NO NC C NO NC C NO NC C NO NC
The pump
runs in Manual
Manual mode. C NO NC C NO NC C NO NC C NO NC C NO NC
Green, rotating
The pump is
in operating Stop
mode Stop. Green, steady C NO NC C NO NC C NO NC C NO NC C NO NC
Warning, but
the pump runs
Manual
in Manual
NO NC NO NC NO NC
mode.
C C C NO NC C
Yellow, rotating C NO NC
Warning, but
the pump was
stopped via a Stop
Stop Yellow, steady C NO NC C NO NC C NO NC C NO NC C NO NC
command.
The pump is
stopped due
Normal
to Low-flow
stop function. Green, steady C NO NC C NO NC C NO NC C NO NC C NO NC
62
18. Installing a communication 1. Loosen the four screws (fig. 59, A) and remove
the terminal box cover (fig. 59, B).
English (GB)
interface module
DANGER
Electric shock A
- Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Wait at least 5
63
4. Fit the CIM module by aligning it with the three 8. Route the wires for the CIM module. See the
plastic holders (fig. 62, A) and the connecting example in fig. 64.
English (GB)
64
19. Identification of functional module 20. Identification of control panel
English (GB)
You can identify the fitted module in one of the You can identify the fitted module in one of the
following ways: following ways:
Grundfos GO Remote Grundfos GO Remote
You can identify the functional module in the "Fitted You can identify the control panel in the "Fitted
modules" menu under "Status". modules" menu under "Status".
Pump display Pump display
For pumps fitted with the advanced control panel, For pumps fitted with the advanced control panel,
you can identify the functional module in the Fitted you can identify the control panel in the Fitted
modules menu under Status. modules menu under Status.
Motor nameplate Motor nameplate
You can identify the fitted module on the motor You can identify the fitted control panel on the motor
nameplate. See fig. 66. nameplate. See fig. 67.
VARIANT VARIANT
ype :
Typ
Type P.C. : INPUT
Hp PB :
OUTPUT VARIANT ype :
Type
Typ P.C. : INPUT
Hp PB :
OUTPUT VARIANT
: :
Xxxxxxxxxxx
Xxxxxxxxxxx
P.N. : Serial no : U in P
P2 : Hp PB : P.N. : Serial no : U in P
P2 : Hp PB :
rpm FM : rpm FM :
E.P. Motor
E.P. Motor
DE : Env.Ty
Env.Type
ype
p : TEFC ~ V n max: rpm FM : DE : Env.Ty
Env.Type
ype
p : TEFC ~ V n max: rpm FM :
NDE : SF : CL: f in : Hz Eff : HMI : Made in Hungary NDE : SF : CL: f in : Hz Eff : HMI : Made in Hungary
Wgt
Wggt : g Tamb :
kg F PF: I SF Ampp: A I 1/1 : A HMI :
HMI: CIM : DK - 8850 Bjerringbro, Denmark
Wgt
Wggt : g Tamb :
kg F PF: I SF Ampp: A I 1/1 : A HMI :CIM : DK - 8850 Bjerringbro, Denmark
CIM : CIM :
TM06 1889 3314
65
21. Changing the position of the 3. Press and hold in the two locking tabs (A) while
gently lifting the plastic cover (B).
English (GB)
control panel
DANGER
Electric shock
- Death or serious personal injury
- Switch off the power supply to the motor
66
7. Tighten the four screws (TX25) with 5 Nm. 23. Cleaning the product
English (GB)
WARNING
Electric shock
- Death or serious personal injury
- Switch off the power supply to the motor
and to the signal relays. Check that the
terminal box cover is intact before
spraying water on the product.
DANGER
Magnetic field
Death or serious personal injury
- Do not handle the motor or rotor if you
have a pacemaker.
22.1 Motor
If service is needed on the product, please contact
Grundfos Service.
22.2 Pump
Service documentation is available in Grundfos
Product Center
(http://product-selection.grundfos.com/).
If you have any questions, please contact the
nearest Grundfos company or service workshop.
67
24. Factory settings
English (GB)
● Function is enabled.
❍ Function is disabled.
- Function is not available.
68
CRE, CRIE, CRNE, SPKE, MTRE
English (GB)
Function
Settings With Without description
factory-fitted factory-fitted MTHE, on page
sensor sensor CME
"LiqTec"1) Not active Not active -1)
1)
47
"Detection delay time" 10 seconds 10 seconds -1)
Standstill heating Not active Not active Not active 50
Motor bearing monitoring Not active Not active Not active 50
"Pump name" - - - 53
"Connection code" - - - 54
"Unit configuration" SI SI SI 52
1)
Only available if an advanced functional module, type FM 300, is fitted.
69
25. Megging 27. Technical data, three-phase
English (GB)
0.25 - 0.75 6 10 3 10 16
1.1 - 1.5 10 16 4 13 16
5.5 16 32
You can use standard as well as quick-blow or
slow-blow fuses. 7.5 20 32
11 32 32
26.2 Leakage current
Earth leakage current less than 3.5 mA, AC. • 3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Earth leakage current less than 10 mA, DC.
The leakage currents are measured in accordance Motor size Min. Max.
with EN 61800-5-1:2007. [kW] [A] [A]
1.1 10 20
1.5 10 20
2.2 13 35
3 16 35
4 25 35
5.5 32 35
70
27.2 Leakage current (AC) 28. Inputs/outputs
English (GB)
Earth reference
Mains Leakage
Speed Power All voltages refer to earth. All currents return to
voltage current
[min-1] [kW] earth.
[V] [mA]
Absolute maximum voltage and current limits
≤ 400 < 3.5
0.25 - 1.5 Exceeding the following electrical limits may result in
> 400 <5 severely reduced operating reliability and motor life:
1400-2000 ≤ 400 < 3.5 Relay 1:
2.2 - 4 Maximum contact load: 250 VAC, 2 A or 30 VDC, 2
1450-2200 > 400 < 3.5
A.
≤ 400 < 3.5 Relay 2:
5.5 - 7.5
> 400 <5 Maximum contact load: 30 VDC, 2 A.
≤ 400 < 3.5 GENI terminals: -5.5 to 9.0 VDC or less than 25
0.25 - 2.2 mADC.
> 400 <5
Other input/output terminals: -0.5 to 26 VDC or less
≤ 400 < 3.5 than 15 mADC.
2900-4000 3 - 5.5
> 400 < 3.5 Digital inputs, DI
≤ 400 < 3.5 Internal pull-up current greater than 10 mA at Vi
7.5 - 11 equal 0 VDC.
> 400 <5
Internal pull-up to 5 VDC (currentless for Vi greater
≤ 400 < 3.5 than 5 VDC).
0.25 - 2.2
> 400 <5 Certain low logic level: Vi less than 1.5 VDC.
≤ 400 < 3.5 Certain high logic level: Vi greater than 3.0 VDC.
4000-5900 3 - 5.5 Hysteresis: No.
> 400 < 3.5
Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
≤ 400 < 3.5 Maximum cable length: 500 m.
7.5 - 11
> 400 <5 Open-collector digital outputs, OC
The leakage currents are measured without any load Current sinking capability: 75 mADC, no current
on the shaft and in accordance with EN sourcing.
61800-5-1:2007. Load types: Resistive or/and inductive.
Low-state output voltage at 75 mADC: maximum 1.2
VDC.
Low-state output voltage at 10 mADC: maximum 0.6
VDC.
Overcurrent protection: Yes.
Screened cable: 0.5 - 1.5 mm2, 28-16 AWG.
Maximum cable length: 500 m.
71
Analog inputs, AI Pt100/1000 inputs, Pt
Voltage signal ranges: Temperature range:
English (GB)
72
29. Other technical data Cable entries
English (GB)
EMC (electromagnetic compatibility) Number and size of cable entries
Standard used: EN 61800-3. Motor
[kW]
The table below shows the emission category of the 2900-4000 min-1 4000-5900 min-1
motor.
0.25 - 1.5 4xM20 4xM20
C1 fulfils the requirements for residential areas.
Note: When connected to a public network, 11 kW 2.2 4xM20 4xM20
motors do not comply with the partial weighted 3-4 1xM25 + 4xM20 1xM25 + 4xM20
harmonic distortion (PWHD) requirements of EN
61000-3-12. If required by the distribution network 5.5 1xM25 + 4xM20 1xM25 + 4xM20
operator, compliance can be obtained in the 7.5 - 11 1xM32 + 5xM20 1xM32 + 5xM20
following way:
The impedance of the mains cables between the Cable glands delivered with the pump
motor and the point of common coupling (PCC) must
be equivalent to the impedance of a 50 m cable with Cable
a cross-section of 0.5 mm. Motor Thread
Quantity diameter
[kW] size
C3 fulfils the requirements for industrial areas. [mm]
Note: When the motors are installed in residential
areas, supplementary measures may be required as 2 5
0.25 - 2.2 M20 x 1.5
the motors may cause radio interference. 1 7-14
4 M20 x 1.5 5
Emission category 3 - 5.5
Motor 1 M25 x 1.5 9-18
[kW] 2900-4000 min-1
1450-2000 min-1 4 M20 x 1.5 5
4000-5900 min-1 7.5 - 11
1 M32 x 1.5 14-25
0.25 C1 C1
0.37 C1 C1 Torques
73
29.1 Sound pressure level
Sound pressure
English (GB)
Maximum level
Sound pressure speed ISO 3743
Maximum level Motor Speed
stated on [dB(A)]
speed ISO 3743 [kW] [min-1]
Motor Speed nameplate
stated on [dB(A)] [min-1] 1-phase 3-phase
[kW] [min-1]
nameplate motors motors
[min-1] 1-phase 3-phase
motors motors 1500 58
2000
1500 37 37 2000 61
2000
2000 43 43 3000 61
5.5 4000
3000 50 50 4000 69
0.25 -
4000
0.75 4000 60 60 4000 64
5900
4000 58 58 5900 74
5900
5900 68 68 1500 58
2000
1500 37 2000 61
2000
2000 43 3000 66
7.5 4000
3000 50 50 4000 73
1.1 4000
4000 60 60 4000 69
5900
4000 58 58 5900 79
5900
5900 68 68 3000 66
4000
1500 42 4000 73
2000 11
2000 47 4000 69
5900
3000 57 57 5900 79
1.5 4000
4000 64 64 The grey fields indicate that the motor is not
available in this MGE motor range.
4000 58 58
5900
5900 68 68 30. Disposing of the product
1500 48 This product or parts of it must be disposed of in an
2000
2000 55 environmentally sound way:
1. Use the public or private waste collection service.
3000 57
2.2 4000 2. If this is not possible, contact the nearest
4000 64 Grundfos company or service workshop.
4000 58 Dispose of the waste battery through the national
5900 collective schemes. If in doubt, contact your local
5900 68
Grundfos company.
1500 48 The crossed-out wheelie bin symbol on
2000
2000 55 a product means that it must be
disposed of separately from household
3000 60 waste. When a product marked with this
3 4000
4000 69 symbol reaches its end of life, take it to a
collection point designated by the local
4000 64 waste disposal authorities. The separate collection
5900
5900 74 and recycling of such products will help protect the
environment and human health.
1500 48
2000 See also end-of-life information at
2000 55 www.grundfos.com/product-recycling.
3000 61
4 4000
4000 69
4000 64
5900
5900 74
74
Appendix 1
Appendix
To maintain the cURus approval, the additional information in this section must be followed.
The UL approval is according to UL 1004-1.
Outdoor installation
According to UL 778/C22.2 No 108-14, pumps intended for outdoor use must be marked enclosure type 3 and
the product must be tested at a surface temperature down to -35 °C. The MLE enclosure is approved for type 3
or 4 and is rated at a surface temperature down to 0 °C, thus it is only for indoor use in UL 778/C22.2 No 108-14
pump applications.
For more information about ambient temperature during operation, see 8.5.2.2 Ambient temperature during
operation.
Pour le Canada
Codes de l'électricité:
Ce produit est conforme au code canadien de l'électricité et au code national de l'électricité américain.
Ce produit a été testé selon les normes nationales s'appliquant aux moteurs protégés électroniquement:
CSA 22.2 100.04: 2009 (s'applique au Canada uniquement).
UL 1004-1: Juin 2011 (s'applique aux États-Unis uniquement).
Pour le Canada
Ce dispositif est conforme à la partie 15 des règles de la FCC et aux normes RSS210 de l'IC. Son
fonctionnement est soumis aux deux conditions suivantes:
• Ce dispositif ne doit pas provoquer de brouillage préjudiciable.
• Il doit accepter tout brouillage reçu, y compris le brouillage pouvant entraîner un mauvais fonctionnement.
2162
Appendix
A.1.3. Identification numbers
For the USA
Grundfos Holding A/S
Contains FCC ID: OG3-RADIOM01-2G4.
For Canada
Grundfos Holding A/S
Model: RADIOMODULE 2G4
Contains IC: 10447A-RA2G4M01.
Pour le Canada
Numéros d'identification:
Grundfos Holding A/S
Modèle: RADIOMODULE 2G4
Contient IC: 10447A-RA2G4M01.
Stop
TM069745
Identification numbers
TM069746
Identification numbers
Torques
See Torques in section 29.
Line reactors
The maximum line reactor size in front of the drive must not exceed the following values:
2163
Appendix
Exceeding these values creates resonance between the reactor and the drive, which reduces the life of the
product.
Short-circuit current
If a short circuit occurs, the pump can be used on a mains supply delivering not more than 5000 RMS
symmetrical amperes, 600 V maximum.
Fuses
Fuses used for motor protection must be rated for minimum 500 V. Motors up to and including 10 hp require
class K5 UL-listed fuses. Any UL-listed fuse can be used for motors of 15 hp.
Branch-circuit protection
When the pump is protected by a circuit breaker, the circuit breaker must be rated for a maximum voltage of 480
V. The circuit breaker must be of the "inverse time" type.
Overload protection
Degree of overload protection provided internally by the drive, in percent of full-load current: 102 %.
2164
Grundfos companies
Argentina China Greece
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Hellas A.E.B.E.
Ruta Panamericana km. 37.500industin 10F The Hub, No. 33 Suhong Road 20th km. Athinon-Markopoulou Av.
1619 - Garín Pcia. de B.A. Minhang District P.O. Box 71
Tel.: +54-3327 414 444 Shanghai 201106 PRC GR-19002 Peania
Fax: +54-3327 45 3190 Tel.: +86 21 612 252 22 Tel.: +0030-210-66 83 400
Fax: +86 21 612 253 33 Fax: +0030-210-66 46 273
Australia
GRUNDFOS Pumps Pty. Ltd. Columbia Hong Kong
P.O. Box 2040 GRUNDFOS Colombia S.A.S. GRUNDFOS Pumps (Hong Kong) Ltd.
Regency Park Km 1.5 vía Siberia-Cota Conj. Potrero Unit 1, Ground floor, Siu Wai industrial
South Australia 5942 Chico, Centre
Tel.: +61-8-8461-4611 Parque Empresarial Arcos de Cota Bod. 29-33 Wing Hong Street & 68 King Lam
Fax: +61-8-8340-0155 1A. Street, Cheung Sha Wan
Cota, Cundinamarca Kowloon
Austria Tel.: +57(1)-2913444 Tel.: +852-27861706 / 27861741
GRUNDFOS Pumpen Vertrieb Fax: +57(1)-8764586 Fax: +852-27858664
Ges.m.b.H.
Grundfosstraße 2 Croatia Hungary
A-5082 Grödig/Salzburg GRUNDFOS CROATIA d.o.o. GRUNDFOS Hungária Kft.
Tel.: +43-6246-883-0 Buzinski prilaz 38, Buzin Tópark u. 8
Fax: +43-6246-883-30 HR-10010 Zagreb H-2045 Törökbálint
Tel.: +385 1 6595 400 Tel.: +36-23 511 110
Belgium Fax: +385 1 6595 499 Fax: +36-23 511 111
N.V. GRUNDFOS Bellux S.A. www.hr.grundfos.com
Boomsesteenweg 81-83 India
B-2630 Aartselaar Czech Republic GRUNDFOS Pumps india Private Limited
Tel.: +32-3-870 7300 GRUNDFOS Sales Czechia and Slovakia 118 Old Mahabalipuram Road
Fax: +32-3-870 7301 s.r.o. Thoraipakkam
Čajkovského 21 Chennai 600 097
Belarus 779 00 Olomouc Tel.: +91-44 2496 6800
Представительство ГРУНДФОС в Tel.: +420-585-716 111
Минске Indonesia
220125, Минск Denmark PT GRUNDFOS Pompa
ул. Шафарнянская, 11, оф. 56, БЦ GRUNDFOS DK A/S Graha intirub Lt. 2 & 3
«Порт» Martin Bachs Vej 3 Jln. Cililitan Besar No.454. Makasar,
Тел.: +375 17 397 397 3 DK-8850 Bjerringbro Jakarta Timur
+375 17 397 397 4 Tel.: +45-87 50 50 50 ID-Jakarta 13650
Факс: +375 17 397 397 1 Fax: +45-87 50 51 51 Tel.: +62 21-469-51900
E-mail: minsk@grundfos.com E-mail: info_GDK@grundfos.com Fax: +62 21-460 6910 / 460 6901
www.grundfos.com/DK
Bosnia and Herzegovina Ireland
GRUNDFOS Sarajevo Estonia GRUNDFOS (Ireland) Ltd.
Zmaja od Bosne 7-7A GRUNDFOS Pumps Eesti OÜ Unit A, Merrywell Business Park
BiH-71000 Sarajevo Peterburi tee 92G Ballymount Road Lower
Tel.: +387 33 592 480 11415 Tallinn Dublin 12
Fax: +387 33 590 465 Tel.: + 372 606 1690 Tel.: +353-1-4089 800
www.ba.grundfos.com Fax: + 372 606 1691 Fax: +353-1-4089 830
E-mail: grundfos@bih.net.ba
Finland Italy
Brazil OY GRUNDFOS Pumput AB GRUNDFOS Pompe Italia S.r.l.
BOMBAS GRUNDFOS DO BRASIL Trukkikuja 1 Via Gran Sasso 4
Av. Humberto de Alencar Castelo FI-01360 Vantaa I-20060 Truccazzano (Milano)
Branco, 630 Tel.: +358-(0) 207 889 500 Tel.: +39-02-95838112
CEP 09850 - 300 Fax: +39-02-95309290 / 95838461
São Bernardo do Campo - SP
France
Tel.: +55-11 4393 5533 Pompes GRUNDFOS Distribution S.A. Japan
Fax: +55-11 4343 5015 Parc d’Activités de Chesnes GRUNDFOS Pumps K.K.
57, rue de Malacombe 1-2-3, Shin-Miyakoda, Kita-ku
Bulgaria F-38290 St. Quentin Fallavier (Lyon) Hamamatsu
Grundfos Bulgaria EOOD Tel.: +33-4 74 82 15 15 431-2103 Japan
Slatina District Fax: +33-4 74 94 10 51 Tel.: +81 53 428 4760
Iztochna Tangenta street no. 100 Fax: +81 53 428 5005
BG - 1592 Sofia
Germany
Tel.: +359 2 49 22 200 GRUNDFOS GMBH Korea
Fax: +359 2 49 22 201 Schlüterstr. 33 GRUNDFOS Pumps Korea Ltd.
E-mail: bulgaria@grundfos.bg 40699 Erkrath 6th Floor, Aju Building 679-5
Tel.: +49-(0) 211 929 69-0 Yeoksam-dong, Kangnam-ku, 135-916
Canada Fax: +49-(0) 211 929 69-3799 Seoul, Korea
GRUNDFOS Canada inc. E-mail: infoservice@grundfos.de Tel.: +82-2-5317 600
2941 Brighton Road Service in Deutschland: Fax: +82-2-5633 725
Oakville, Ontario kundendienst@grundfos.de
L6H 6C9
Tel.: +1-905 829 9533
Fax: +1-905 829 9512
Grundfos companies
www.grundfos.com
Trademarks displayed in this material, including but not limited to Grundfos, the Grundfos logo and “be
think innovate” are registered trademarks owned by The Grundfos Group. All rights reserved. © 2022 Grundfos Holding A/S, all rights reserved.