Professional Documents
Culture Documents
Book 1
Book 1
Book 1
Jeevan Tara
Sr.no. Location Loop Impedance Value PSC Value
2nd Floor Electrical Room DB'S
Light DB
1 TPN 0.3 712
2 R-Phase 0.2 713
3 Y-Phase 0.4 694
4 B-Phase 0.3 709
5 R-Phase MCB-1 0.3 678
6 R-Phase MCB-2 0.4 710
7 Y-Phase MCB-1 0.3 666
8 Y-Phase MCB-2 0.4 698
9 B-Phase MCB-1 0.3 679
10 B-Phase MCB-2 0.3 689
11 B-Phase MCB-3 0.4 688
UPS Power DB
12 TPN 1.7 150.3
13 R-Phase 1.7 210
14 Y-Phase 1.9 118.3
15 B-Phase 1.7 119.4
16 R-Phase MCB-1 1.8 120.3
17 R-Phase MCB-2 1.9 222.4
18 R-Phase MCB-3 1.7 223.8
19 R-Phase MCB-4 1.8 2103
20 Y-Phase MCB-1 1.8 312.4
21 Y-Phase MCB-2 1.6 313.8
22 Y-Phase MCB-3 1.9 348.3
23 Y-Phase MCB-4 1.8 194.4
24 B-Phase MCB-1 1.9 195.3
25 B-Phase MCB-2 1.7 205.2
26 B-Phase MCB-3 1.8 209.9
27 B-Phase MCB-4 1.9 215.5
AC Power DB
28 TPN 1.1 292
29 R-Phase 1.3 387
30 Y-Phase 1.2 394
31 B-Phase 1.3 392
32 C-ARC MCB-1 1.1 394
33 C-ARC MCB-2 1.1 389
34 C-ARC MCB-3 1.5 390
35 R-Phase MCB-1 1.5 382
36 R-Phase MCB-2 1.1 383
37 R-Phase MCB-3 1.3 389
38 R-Phase MCB-4 1.4 391
39 Y-Phase MCB-1 1.2 385
40 Y-Phase MCB-2 1.4 401
41 Y-Phase MCB-3 1.5 398
42 Y-Phase MCB-4 1.6 378
43 B-Phase MCB-1 1.9 336
44 B-Phase MCB-2 1.7 358
45 B-Phase MCB-3 1.2 345
46 B-Phase MCB-4 1.9 372
Raw Power DB
47 TPN 0.3 1396
48 R-Phase 0.2 1463
49 Y-Phase 0.2 1478
50 B-Phase 0.1 1500
51 R-Phase MCB-1 0.1 1455
52 R-Phase MCB-2 0.2 1243
53 R-Phase MCB-3 0.2 1458
54 R-Phase MCB-4 0.2 1544
55 R-Phase MCB-5 0.2 1428
56 R-Phase MCB-6 0.2 1531
57 Y-Phase MCB-1 0.1 1400
58 Y-Phase MCB-2 0.1 1452
59 Y-Phase MCB-3 0.2 1384
60 Y-Phase MCB-4 0.1 1461
61 B-Phase MCB-1 0.1 1396
62 B-Phase MCB-2 0.2 1457
63 B-Phase MCB-3 0.1 1398
64 B-Phase MCB-4 0.2 1415
65 B-Phase MCB-5 0.1 1390
Emergency DB
66 DP MCB 1.2 178.4
67 MCB-1 1.2 189.2
68 MCB-2 1.4 181.5
69 MCB-3 1.3 168.5
70 MCB-4 1.1 161.9
Cabin No-16
71 Raw Power Earth Wire Not Conectied
72 Raw Power Earth Wire Not Conectied
73 UPS Power 338
74 UPS Power 339
Cabin No-18
75 Raw Power Earth Wire Not Conectied
76 Raw Power Earth Wire Not Conectied
77 UPS Power 343
78 UPS Power 345
Phase-1 Work Station Sokite's
79 UPS Power Work Station Table No-85 340
80 UPS Power Work Station Table No-85 343
81 UPS Power Work Station Table No-82 355
82 UPS Power Work Station Table No-82 341
83 UPS Power Work Station Table No-80 352
84 UPS Power Work Station Table No-80 331
85 Raw Power Work Station Table No-75 Earth Wire Not Conectied
86 UPS Power Work Station Table No-75 376
87 Raw Power Work Station Table No-72 Earth Wire Not Conectied
88 UPS Power Work Station Table No-72 341
89 Raw Power Work Station Table No-69 Earth Wire Not Conectied
90 UPS Power Work Station Table No-69 356
91 Raw Power Work Station Table No-67 Earth Wire Not Conectied
92 UPS Power Work Station Table No-67 359
93 Raw Power Work Station Table No-64 Earth Wire Not Conectied
94 UPS Power Work Station Table No-64 384
95 Raw Power Work Station Table No-61 Earth Wire Not Conectied
96 UPS Power Work Station Table No-61 395
97 Raw Power Work Station Table No-58 Earth Wire Not Conectied
98 UPS Power Work Station Table No-58 402
99 Raw Power Work Station Table No-55 Earth Wire Not Conectied
100 UPS Power Work Station Table No-55 314
101 Raw Power Work Station Table No-52 Earth Wire Not Conectied
102 UPS Power Work Station Table No-52 341
103 Raw Power Work Station Table No-50 Earth Wire Not Conectied
104 UPS Power Work Station Table No-50 345
105 Raw Power Work Station Table No-47 Earth Wire Not Conectied
106 UPS Power Work Station Table No-47 347
107 Raw Power Work Station Table No-45 Earth Wire Not Conectied
108 UPS Power Work Station Table No-45 321
109 Raw Power Work Station Table No-42 Earth Wire Not Conectied
110 UPS Power Work Station Table No-42 335
111 Raw Power Work Station Table No-25 Earth Wire Not Conectied
112 UPS Power Work Station Table No-25 Earth Wire Not Conectied
113 Raw Power Work Station Table No-09 Earth Wire Not Conectied
114 UPS Power Work Station Table No-09 Earth Wire Not Conectied
115 UPS Power Work Station Table No-20 339
116 UPS Power Work Station Table No-20 340
Phase-2 Work Station Sokite's
117 Raw Power TCS Table-1 Earth Wire Not Conectied
118 UPS Power TCS Table-1 Earth Wire Not Conectied
119 UPS Power TCS Table-1 Earth Wire Not Conectied
120 Raw Power TCS Table-3 Earth Wire Not Conectied
121 UPS Power TCS Table-3 343
122 UPS Power TCS Table-3 342
123 Raw Power TCS Table-5 341
124 UPS Power TCS Table-5 353
125 UPS Power TCS Table-5 352
126 Raw Power TCS Table-6 Earth Wire Not Conectied
127 UPS Power TCS Table-6 341
128 UPS Power TCS Table-6 354
129 Raw Power TCS Table-7 356
130 UPS Power TCS Table-7 347
131 UPS Power TCS Table-7 348
132 Raw Power Work Station Table No-141 Earth Wire Not Conectied
133 UPS Power Work Station Table No-141 351
134 Raw Power Work Station Table No-142 Earth Wire Not Conectied
135 UPS Power Work Station Table No-142 353
136 Raw Power Work Station Table No-143 Earth Wire Not Conectied
137 UPS Power Work Station Table No-143 355
138 Raw Power Work Station Table No-144 Earth Wire Not Conectied
139 UPS Power Work Station Table No-144 332
140 Raw Power Work Station Table No-145 Earth Wire Not Conectied
141 UPS Power Work Station Table No-145 345
142 Raw Power Work Station Table No-146 1309
143 UPS Power Work Station Table No-146 1309
144 UPS Power Work Station Table No-146 1102
145 UPS Power Work Station Table No-148 1101
146 Raw Power Work Station Table No-148 Earth Wire Not Conectied
147 UPS Power Work Station Table No-148 958
148 Raw Power Work Station Table No-154 Earth Wire Not Conectied
149 UPS Power Work Station Table No-154 Earth Wire Not Conectied
150 UPS Power Work Station Table No-154 Earth Wire Not Conectied
Remarks
'S
wer)
'S
wer)
Remark's
'S