Professional Documents
Culture Documents
220 KV Subsatation Maintenance
220 KV Subsatation Maintenance
1.1 Introduction 1
1.2 Mission and Vision 2
Chapter 2 220 kv Receving station
2.1 Introduction 3
Chapter 3 220 kv SRS equipments and its functions 7
3.1 Switchgear and Protection 8
3.2 Lightning Arrestor 9
3.3 Instrument Transformer 11
3.4 Circuit Breaker 13
3.5 Isolator 15
3.6 Insulators 16
3.7 Busbar scheme 17
3.8 Bus coupler 20
3.9 Earthing Switches 21
3.10 Classification of voltages 21
3.11 Conductors 21
3.12 Underground Cables 22
3.13 Wave Trap 23
3.14 Power Transformer 24
Chapter 4 220kv SRS protective relays
4.1 Relays used for power transformer 28
4.2 Relay used for protection for transmission line 30
4.3 Nitrogen Injection system 31
4.4 Batteries ans Battery Charger 32
4.5 Capacitor Bank 33
4.6 Feeders 34
4.7 Control room 36
Chapter 5 Maintenance of substation
CHAPTER -1
INTRODUCTION OF KPTCL
1.1 Introduction
The State of Karnataka, with availability of cheap electric power, and other infrastructure
facilities, was conductive for increased tempo of industrial activity. It became necessary
therefore, to augment power generating capacity by harnessing the entire potential of the
Sharavathi Valley. The first unit of 89.1 MW was commissioned in 1964 and completed
in 1977.
KPTCL is divided into 5 companies. These companies came into existence from 1st
June 2002
Emphasizing best electricity utility in the country, the KPTCL pledges to optimize its
human and technical resources for the benefits of all its customers.
CHAPTER 2
220KV RECEVING STATION
2.1 Introduction
The Sharavathi Receiving Station (SRS) is the one of the receiving station which is
located at Vidyuthnagara, Davangere. The station is established on the year 1982 which
is named under the river sharavathi.
The station is 220/66/11kv receiving stations which have incoming lines from different
areas. The receiving station or switching station receives the power from incoming
lines, step downs the voltage and supplies the power through outgoing lines.
There are 5, 220kv lines and 8 outgoing lines at 66kv for SRS. The station receives power
from the high voltage end i.e., from 220kv line and step downs to 66kv, further the step-
down power fed to the consumers through the feeders.
The incoming and outgoing lines for 220kV SRS Davangere are of 5 ways. They are
1) Guttur-2
2) Honnali
3) Shivamogga
4) Guttur-3
5) Guttur-1
Guttur-2, Guttur-3 and Guttur-1 are the incoming lines whereas Honnali and Shivamogga
are the outgoing lines in general. But sometimes Honnali and Shivamogga also act as
incoming lines whenever necessary.
A single line diagram is a simplified diagram that shows the electrical system of a
power distribution or transmission network in a single line format.
It uses standard symbols to represent electrical components and their
interconnections, and is often used in design, analysis and operation of electrical
systems.
The single line diagram provides a quick overview of the system, including the
major components such as bus bars, power transformers, circuit breakers, isolators,
capacitor banks,CTs and PTs, wave trap units, surge arrestors etc.
At the incoming and outgoing line of side circuit breaker are used to protect the
network fromoverloads and fault.
Current transformer is located near the circuit breaker for the purpose of measuring
the currentflowing through the circuit and it also give the signal to the relay of the
circuit breaker to get trip.
Isolators are erected near the current transformer and circuit breaker to ensure the
safe isolationof a section of the system for maintenance, Repair or replacement
work.
CHAPTER 3
220KV SRS EQUIPMENTS AND ITS FUNCTION
Equipment Function
In addition to that from commercial point of view every electrical power system
needs measuring, controlling and regulating arrangement. Collectively the whole
system is called switchgear and protection of power system. The electrical
switchgear has been developing in various forms.
Switchgear protection plays a vital role in modern power system network, right
from generationthrough transmission to distribution end. The current interruption
devices are called circuit breaker. The circuit breakers can be operated manually
as when required and it can also be operated automatically during over current and
short circuit or any other faults in the system bysensing the abnormality of system
parameters. These power system parameters can be current, voltage, frequency,
phase angle etc. The circuit breaker senses the faulty condition of system through
protection relays and these relays are again actuated by faulty signal normally
comes from current transformer or voltage transformer.
Fig 3.3.1.1 Current Transformer
used to provide a low voltagesignal that accurately represents the high voltage in the
power system. This low voltage signal can thenbe used by various instruments such as
meters, relays, and protective devices to control and monitor the power system.
After the breaker operation (i.e., after arc extinction in circuit breaker), the valve
is closed by the actionof a set of springs.
Fig:3.4.3.1 220kv SF6 Circuit Breaker Fig: 3.4.3.2 220kv SF6 CB name plate
While Opening: Open circuit breaker, Open isolator and then close earthing switch.
While closing: Open earthing switch, close isolator and then close circuit breaker.
Double brake type isolator: It consists of three loads of post isolators. The
middle isolator holds a tubular contact which can be turned straightly by a spin
of middle post isolator and other two post isolators are fixed. It can be rotated
by a lever method at the bottom of the postisolator by manual operation. As the
name indicates there are two brakes so that the magnitudeof the arc produced is
divided and the damage to isolator is reduced.
Single break type isolator: In this isolator the arm contact is separated into two
elements. Thefirst arm contact holds one contact, and second arm contact holds
another contact. When the isolator is in open condition the contacts are
separated, when isolator is in close condition contacts are hold together tightly.
Fig:3.5.1 Single break type Isolator Fig:3.5.2 Double break type Isolator
3.6 Insulators:
An electrical insulator is a material whose internal electric charges do not flow freely.
The bare line conductors are connected to the transmission towers through the
insulators. Insulators act as insulating medium for flow of leakage current from
conductor to ground through tower structures.
Some of the insulating materials are Porcelain, Glass and Steatite materials.
The disc type insulators are curved, because the curved shape
ii) water does not enter/ deposit at the bottom of a disc and
Single Bus System is simplest and cheapest one. In this scheme all the feeders and
transformer bay are connected to only one single bus. If any of the sources is out of
the system, still all loadscan be fed by switching on the sectional circuit breaker or
bus coupler breaker. If one section ofthe bus bar system is under maintenance, a
part load of the substation can be fed by energizing the other section of the bus bar.
outgoing or incoming feeder can be taken from any of the bus. Actually every
feeder is connected to both ofthe buses in parallel through individual isolator as
shown in the figure 19. By closing any of the isolators, one can put the feeder to
the associated bus. Both of the busesare energized, and total feeders are divided
into two groups, one group is fed from one bus and other from other buses. But
any feeder at any time can be transferred from one bus to other.
Name Range
Low Voltage 50-1000v
3.11 Conductors:
A conductor is an object or type of material that allows the flow of an electrical current
in one or moredirection. Materials made of metal are common electrical conductor.
The most commonly used conductors for transmission today is ACSR (Aluminium
Conductor SteelReinforced). They are classified into various types based on their
current rating some of them are asfollows:
Wave traps are typically installed at the entry point of the substation, where the
transmission line entersthe substation area. They can also be installed at other points
along the transmission line, depending on the specific needs of the system.
Wave traps are an important component of power transmission systems, as they help to
ensure the reliable and safe operation of the system by preventing interference from
high frequency communication signals.
In case of heavy faults due to surge in oil OSR relay will operate and causes tripping
of bothHT and LT breakers of the transformer.
Pressure Relief Valve: In case of a sudden and uncontrolled increase in pressure
inside thetransformer, the pressure relief device allows the insulating fluid to
be discharged in milliseconds. Pressure relief devices significantly improve
transformer reliability and safety.
Oil Temperature Indicator & Winding Temperature Indicator: The WTI
means winding temperature Indicator and OTI means Oil Temperature
Indicator which indicates the winding temperature & oil temperature of the
Fig3.14.2 Air-cell
Breather: The purpose of these silica gel breathers is to absorb the moisture
in the airsucked in by the transformer during the breathing process.
Magnetic Oil Gauge: It is also known as oil level indicator. The MOG
(Magnetic Oil Gauge) is a device by which we can supervise the level of liquid/oil
inside the tank or conservator of power transformer and also gives us an alert of low oil
level indication with making mercury switch. It is connected at the bottom of the
Conservator tank.
Radiators: When transformer is in the loaded condition, the hot oil comes up
in the main tank, and enters into the radiator tank through upper valve. As the
heat transfer surface of the radiator is quite large, the oil gets cooled and enters
into the transformertank via lower value of radiator units. The convectional
CHAPTER 4
220KV SRS PROTECTIVE RELAYS
4.1 Relays used for the protection of power transformer:
Fig:4.1 Relays
Differential Relay:
Differential protection is the primary protection for the power transformer. Differential
protection is acommon technique used to protect power transformers from internal
faults. The basic idea behind differential protection is to compare the current entering
the transformer with the current leaving the transformer. If the difference between
these two currents exceeds a predetermined threshold, it is an indication of an internal
fault in the transformer.
while the CTs on the secondary side of the transformer measure the current leaving the
transformer. The currents from both sets of CTs are then fed into a differential relay,
which compares the two currents and determines if there is a fault in the transformer.
Overcurrent Relay:
Overcurrent protection is another important technique used to protect power
transformers fromdamage caused by overcurrent or short circuits. Overcurrent can be
caused by a variety of reasons, including faults in the power system, lightning strikes,
or switching operations. Overcurrent protection typically involves the use of
overcurrent relays, which are designed to detect overcurrent and operate protective
devices, such as circuit breakers, to isolate the transformer from the power system.
Overcurrent relays are typically installed on both the primary and secondary sides of
the transformer.
There are different types of overcurrent relays, including instantaneous overcurrent
relays, time-delay overcurrent relays, and directional overcurrent relays. Directional
overcurrent relays aredesigned to detect overcurrent that flow in a particular direction,
which can be useful in detecting faults that occur close to the transformer.
located at the faultlocation, which opens the breaker and isolates the faulty section of
the power system.
the pressureand flow ofthe gas are controlled by a regulator and a flow meter. The system
may also include a nitrogen purge system, which allows for the removal of any moisture
or other contaminants from the transformer prior to filling it with nitrogen.
It's important to note that a nitrogen injection system is not a substitute for regular
maintenance and testing of power transformers. The system should be used in
conjunction with other preventative maintenance measures, such as regular oil
sampling and testing, to ensure the continued safe and reliable operation of the
transformer.
Capacitors are used to control the level of the voltage supplied to the customer by
reducing or eliminating the voltage drop in the system caused by inductive reactive
loads.
A Capacitor Bank is a group of several capacitors of the same rating that are
connectedin series or parallel with each other to store electrical energy.
The resulting bank is then used to counteract or correct a power factor lag or phase
shift in an alternating current (AC) power supply.
Improving power factor means reducing the phase difference between voltage and
current. Since the majority of loads are of inductive nature, they require some
amount of reactive power for them to function. The capacitor or bank of capacitors
installed parallel to the load provides this reactive power.
It reduces the electricity bill, used to reduce signal noise and they also prevent
electromechanical contacts from burning.
30MVR Capacitor Bank-1 and 20MVAR Capacitor Bank-2 are used
4.6 Feeders:
In electric power distribution, Feeder is “voltage power line transferring power from a
distributionsubstation to the distribution transformers”.
Feeders are the conductors which connect the stations (sometimes generating
stations) to the area to be fed by those stations.
Generally, from feeders no tapping is taken to the consumers, therefore,
current loading of a feeder remains the same along its length.
Fig:4.6 Feeders
Chitradurga-2 F2 – Tholahunase
66kvoutgoing
F3- Kukwada(IP)
F4- Yellamma(IP)
F5- Belanger
Guttur 3 220kV incoming Harihara-Hospet
BANK 2
66kvoutgoing
F9 – Shamnur(Vr)
F10-Saraswarthi
badavane
F11 – Water worksF12 –
Attigeri(Vr) F13 –
Honnali 220 KV
Yaragunta 66kv outgoing BANK 3
OUTGOINGLINES
SCADA:
Supervisory control and data acquisition (SCADA) is a control system architecture
comprising computers, networked data communications and graphical user interfaces
(GUI) for high-level process supervisory management, while also comprising other
peripheral devices like programmable logic controllers (PLC) and discrete proportional-
integral-derivative (PID) controllers to interface with process plant or machinery.
• Computer control is one of the most cost-effective solutions for improving reliability,
optimum operation, intelligent control and protection of a power system network. Having
advanced data collection capabilities, SCADA system plays a significant role in power
system operation.
• At distribution side SCADA does more than simply collecting data by automating entire
distribution network and facilitating remote monitoring, coordinate, control and
operating distribution components just like in Smart Grid System.
1. Substation Control
2. Feeder Control
• Improves the continuity of service by restoring service after the occurrence of faults
(temporary).
• Automatically improves the voltage profile by power factor correction and VAR control.
• Facilitates the view of historian data in various ways.
• Reduces the labour cost by reducing the staff required for meter reading
PLCC:
PLCC (Power line carrier communication) in modern electrical power system substation
is mainly used for following purpose:
• Carrier protection relaying of transmission line so that: Inter trip command can be issued
by relay due to tripping of circuit breaker at any one end.
• Wave Trap--The carrier energy on the transmission line must be directed towards the
remote line terminal and not towards the station bus and it must be isolated from bus
impedance variations. This task is performed by the line trap. A parallel resonant circuit
has high impedance at its tuned frequency, and it then causes most of the carrier energy
to flow toward the remote line terminal. The coil of the line trap provides a low
impedance path for the flow of the power frequency energy. Since the power flow is
rather large at times, the coil used in a line trap must be large in terms of physical size.
Hence a line trap unit/Wave trap is inserted between busbar and connection of coupling
capacitor to the line.
• Wave trap protects the electrical substation from high frequency communication
signals by acting as Low Pass Filter.
DCDB:
(ii) Boost type – It is a type of charging which boosts up the low voltage to the specified
value.
ACDB:
It gives extra protection to the system in case of failures on load side. ACDB is made for
breaker, isolators, voltage and current monitoring etc. Substation AC auxiliary systems
are typically used to supply loads such as transformer cooling, oil pumps, and load tap
changers, circuit breaker air compressors and charging motors, outdoor device heaters,
outdoor lighting and receptacles, motor-operated disconnecting switches, emergency
feeders, yard lighting, and control house. Control house usually includes lighting and
receptacles, heating, ventilating and air conditioning, battery charger input and water well
pump.
CHAPTER 9 CONCLUSION
Finally, from this report we can conclude that, electricity plays a very important role in our life. So,
we came to know that how the electricity is transmitted and distributed through the substation.
Substation is one of the crucial, important and integral part of the power system which forms the
important link between the transmission and distribution.
The current at high voltage is received at the SRS receiving station and is stepped down to the
required level and distributed to many industries and housing purpose.
1. The main function of the station is to transform voltage from high to low or the reverse.
3. The electricity is transmitted at high voltages and low currents to reduce the heat of the eddy
currents, and other transmission losses. In the station the voltages are increased to high voltages
by using step up transformers, and after the transmission, they are again stepped down for
distribution.
2) It's voltage on discharge is the higher of all the reversible combinations used.
3) Uses comparatively cheap and plentiful materials.
4) The completely reversible chemical reactions produce little physical change in
the plates.
5) It can operate satisfactorily over wide range of temperature from approximately
-18 degrees Celsius to 43 degrees Celsius.
2) Visual inspection of HF point bushing for any damage and earthing if not used
for PLCC.
► Earthing rods.
6.1 Electrical Safety:
1) Do check for continuity of DC supply for efficient operation.