Internal Findings:
External Findings:
Page 1 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Recommendations:
Ser. Recommendations:
Insert plate is required for hole area of the bottom HCL feed tank at north West direction with
1
dimension (350mm *460mm) and this insert plate contain a 6mm projection width.
2 Replace the corrosion area of tank projection.
3 Perform WVT after re-weld the insert plates of HCL feed tank.
4 Perform DPT after re-weld the insert plates of HCL feed tank.
Surface preparation by sandblasting and repainting is required for corroded and rusted area to close
5
visual inspection of the HCL Feed Tank.
6 Housekeeping around the HCL feed tank.
Action taken:
Drawing
Page 2 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
General photo
Page 3 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos
Page 4 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos#01&02: Hole have been found in the bottom at north West direction of the HCL Feed Tank, The length of
this hole is approximately 10 cm and the UT thickness around the hole was measured until the sound area ,
ranging from 8.5mm to 9mm.
Photos#03&04: The rubber lining on bottom and course # 01 has been removed.
Page 5 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 05&06: The rubber lining of course #02-05 and the roof has been found in satisfactory condition by visual
inspection from the tank bottom.
Photos# 07&08: Rust has been found at a lot of locations of tank bottom.
Page 6 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 09&10: Corrosion has been observed at the projection with dimension (60mm * 400mm) on either side of
the hole and a lot of locations.
Photos# 11&12: Damage has been observed at earthling line of the HCL feed tank
Page 7 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 13&14: Heavy rust has been observed at the external fist course and projection
Photos# 15&16: Rust has been found at man ladder of HCL feed tank.
Page 8 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 17&18: Water mixed HCL has been observed around HCL feed tank.
Photos# 19&20: Heavy corrosion has been observed at a lot of locations of tank projection
Page 9 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 21&22: Heavy corrosion has been observed at a lot of locations of tank projection
Photos# 23&24: The insert plate for the hole area was installed by welded with dimension (350mm *460mm) and
this insert plate contain a 6mm projection width
Page 10 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 25&26: The 3 insert plates for the corrosion area of tank projection was installed by welded with
dimension and thickness 8 mm
Photo# 27: The 3 insert plates for the corrosion area of tank projection was installed by welded with dimension
and thickness 8 mm
Page 11 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 28&29: The 3 insert plates for the corrosion area of tank projection was installed by welded with
dimension and thickness 8 mm
Photos# 30&31: Perform DPT after re-weld the insert plates of HCL feed tank, DPT was accepted.
Page 12 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 32&33: Perform DPT after re-weld the insert plates of HCL feed tank, DPT was accepted.
Photos# 34&35: Perform DPT after re-weld the insert plates of HCL feed tank, DPT was accepted.
Page 13 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 36&37: Perform DPT after re-weld the insert plates of HCL feed tank, DPT was accepted.
Photos# 38&39: The internal weld caps of the new insert plates inside the tank have been removed.
Page 14 of 15
GENERAL INSPECTION REPORT
Engineering Department
Mechanical Integrity Division
Photos# 40&41: The internal weld caps of the new insert plates inside the tank have been removed.
Site Inspection
Inspected By: Khaled Ghoniem
Engineer
23-04-2024
Senior Inspection
Approved By: Mahmoud Gamal
Engineer