Project: HMEL_PVsyst Report_Punjab
Variant: RCC_phase 3_Beas Guest House_waaree 545Wp_solis_PVsyst
Report_R02N_07.03.24
PVsyst V7.4.2
VDJ, Simulation date:
07/03/24 17:39 GENSOL ENGINEERING LIMITED (India)
with v7.4.2
Project summary
Geographical Site Situation Project settings
Rāmsara Latitude 29.93 °N Albedo 0.20
India Longitude 74.95 °E
Altitude 196 m
Time zone UTC+5.5
Meteo data
Rāmsara
NASA-SSE satellite data 1983-2005 - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 45 units Nb. of units 1 unit
Pnom total 24.53 kWp Pnom total 25.00 kWac
Pnom ratio 0.981
Results summary
Produced Energy 33779 kWh/year Specific production 1377 kWh/kWp/year Perf. Ratio PR 77.55 %
Apparent energy 33779 kVAh/year
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 5
Loss diagram 6
P50 - P90 evaluation 7
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 15 / 87 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Waaree Energies Limited Manufacturer Ginlong Technologies
Model WSMD-545 Model Solis-25K-5G
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 545 Wp Unit Nom. Power 25.0 kWac
Number of PV modules 45 units Number of inverters 1 unit
Nominal (STC) 24.53 kWp Total power 25.0 kWac
Modules 3 Strings x 15 In series Operating voltage 180-1000 V
At operating cond. (45°C) Max. power (=>40°C) 27.5 kWac
Pmpp 22.87 kWp Pnom ratio (DC:AC) 0.98
U mpp 574 V Power sharing within this inverter
I mpp 40 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 313 mΩ
Uc (const) 15.0 W/m²K Loss Fraction 2.0 % at STC
Uv (wind) 0.0 W/m²K/m/s
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 2.5 % Loss Fraction 0.0 % Loss Fraction 1.0 % at MPP
System losses
Unavailability of the system Auxiliaries loss
Time fraction 2.0 % Proportionnal to Power 5.0 W/kW
7.3 days, 0.0 kW from Power thresh.
3 periods
AC wiring losses
Inv. output line up to injection point
Inverter voltage 400 Vac tri
Loss Fraction 2.50 % at STC
Inverter: Solis-25K-5G
Wire section (1 Inv.) Alu 1 x 3 x 240 mm²
Wires length 1262 m
Main results
System Production
Produced Energy 33779 kWh/year Specific production 1377 kWh/kWp/year
Apparent energy 33779 kVAh/year Perf. Ratio PR 77.55 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
Loss diagram
1787 kWh/m² Global horizontal irradiation
Probability distribution