1.2.0 Inputs
1.2.1 System Voltage V : 0.415 kV
1.2.2 Frequency f : 50.00 Hz
1.2.3 Rating of load P : 622.00 kVA Max Power from system
1.2.4 Load power factor CosQ : 1.00
Q : 0.00
SinQ : 0.00
Length From LT Panel to
1.2.5 Maximum Length of cable L : 400.00 m
Termination As per layout
2.0.0 ENVIRONMENTAL DETAILS
2.1.1 Design Ambient Temperature T : 35.00 deg. C
3.0.0 CABLE DATA
3.1.0 Voltage grade Vc : 1.1 kV
3.1.1 No. of Cores : 4.0 cores
3.1.2 Cross Section Area A : 400.00 Sq.mm
Conductor Material (Copper /
3.1.3 : Aluminium
Aluminium)
3.1.4 PROJECT : 13.7MW HMEL : XLPE
Type of cable Armoured
3.1.5 Referance : As per IS 3961 part-6
CHECKING OF THERMAL
5.0.0
AMPACITY
Calculation of De-rating factor for
5.1.0
Direct buried/ laying in Trench
De-rating factor for Temp. variation in
G1 : 0.87 IS 3961-Part-6 Table 8
Ground Temperature
De-rating factor for variation in
G2 : 1.00 IS 3961-Part-6 Table 16
Thermal Resistivity of Soil
1 of 2
: 184.8 A Ground
: 184.8 A
De-rated Current Carrying capacity of
: 1478.4 A
cables selected
: 865.4
: 865.4 A TRUE
5.0.0 RESULT
Minimum Cable size Selected to lay in Ground from 451.54kVA 415V LT Panel to SS-12 will be 1.1kV 4 Run x 4Cx 400sqmm Al XLPE Armored.
√3 x IL x (RcosQ + XsinQ) x L
Steady State Volatge Drop Vd : n x 1000
0.0077 kV
Percentage Voltage drop for this length %Vd : (Vd/V)*100
1.85%