JLL Rajyash Plumbing (Int. Water - Piping)
JLL Rajyash Plumbing (Int. Water - Piping)
JLL Rajyash Plumbing (Int. Water - Piping)
WATER PIPING)
Project Rajyash Regius
PMC JLL
Ref.Drg.No.
Location:
PRE-EXECUTION CHECKS
1 Has the line on walls done by chalk in proper alignment, plumb and as
per the heights mentioned in plumbing drawings?
4 Has it been ensured that the groove chasing does not exceed 30 mm
after rough plaster for cold water supply line and cold feed line and 50
mm for hot water supply lines?
1 Has the pipe-skeleton been prepared and the joints checked for
proper tightness?
4 Are proper sized wooden plugs inserted in the pipe end and then has
the threading carried out?
POST-EXECUTION CHECKS
1 Are the internal pipe works in toilets and kitchen concealed and
carried out as per working drawings?
2 Are the sharp edges of gripping vice and other handling tools
muffed with a suitable packing to prevent damage of pipe surface?
3 Are the joints made with hand tightening of the fitting over pipe and
covered with proper layer of Teflon tape?
4 Has special care been taken while connecting UPVC pipe with G.I.
Fittings?
5 Has water tightness of line been checked using pressure testing
equipment?
6 Has bitumen paint been applied over the G.I pipe work?
7 Has it been ensured that the bore pieces projecting out should be of
minimum 200 mm from plastered surface?
8 Has a gap of 10 mm been kept between all pipes and fittings to
accommodate thermal expansion and contraction of pipes for longer
life of the system?
9 Are all the horizontal lines within bathrooms cement encased and
tested before compacting of sunken floor to avoid any accidental
damages?
10 Has curing been done over the plaster for at least 7 days?
Approved With
Approved Not Approved
Comments
Approved With
Approved Not Approved
Comments
Contractor JLL Client
Name: Name: Name:
Sign: Sign: Sign:
Date: Date: Date: