Automatic Voltage Regulator Selection Chart

2/16/2021
Field Field Sensing Circuit Ratings Power Input Ratings
Minimum Field Field
Rated Field Rated Forcing Regulation Parallel Frequency Over Special
Model Resistance Forcing Model
Volts Amps (Adc) Volts Burden-VA Nominal Frequency Nominal Frequency Accuracy(±) Compensation Compensation Excitation Characteristics
(Ω) Amps (Adc) 1 PH 3 PH Burden (VA)
(Vdc) (Vdc) (Per Phase) Voltages (Hz) Voltages (Hz)
Multi-micro based,
optional redundant
Based Excitation Based Excitation
DECS-2100 Provides excitation currents up to 10,000 Adc Standard Standard <1 120/240Vac 50/60 50-400 0.10% Standard Standard Standard controllers w/ DECS-2100
Levels Levels
independent
supervisory channel
Micro-based
Based Excitation Based Excitation programmable,
DECS-450 Provides excitation currents up to 2500 Adc Standard Standard <1 120/240 50/60 50-400 0.10% Standard Standard Standard DECS-450
Levels Levels optional redundant
controllers
Micro-based includes
VAR Sharing over
Enet, Autotuning, VAR
63 1.26 90 80 5.7k
DECS-250E limiter, Programmable DECS-250E
125 50 2.50 72 180 Standard Standard <1 NOTE 1 50/60 160 50/60 11.4k 0.25% Standard Standard Standard
(50A Version) Logic, Stator Current (50A Version)
250 5.00 360 320 22.7k
Limiting and Real-Time
Monitor, compact
design

Micro-based includes
VAR Sharing over
Enet, Autotuning, VAR
63 0.63 90 80 11.4k
DECS-250E limiter, Programmable DECS-250E
125 100 1.25 144 180 Standard Standard <1 NOTE 1 50/60 160 50/60 22.7k 0.25% Standard Standard Standard
(100A Version) Logic, Stator Current (100A Version)
250 2.50 360 320 45.4k
Limiting and Real-Time
Monitor, Compact
Design

Micro-based includes
VAR Sharing over
Enet, Autotuning, VAR
63 0.315 90 80 22.7k
DECS-250E limiter, Programmable DECS-250E
125 200 0.625 288 180 Standard Standard <1 NOTE 1 50/60 160 50/60 45.4k 0.25% Standard Standard Standard
(200A Version) Logic, Stator Current (200A Version)
250 1.250 360 320 90.9k
Limiting and Real-Time
Monitor, Compact
Design

Micro-based includes
VAR Sharing over
32 2.13 50 60Vac 780 Enet, Autotuning, VAR
50-500
DECS-250 63 15 4.20 30 100 Standard Standard <1 NOTE 1 50/60 120Vac/125Vdc 1570 0.25% Standard Standard Standard limiter, Programmable DECS-250
and dc
125 8.33 200 240Vac/250Vdc 3070 Logic, Stator Current
Limiting and Real-Time
Monitor

Micro-based includes
VAR Sharing over
63 3.15 120/-120 120Vac 3400 Enet, Autotuning, VAR
DECS-250N 125 20 6.25 40 240/-240 Standard Standard <1 NOTE 1 50/60 240Vac 50-420* 6800 0.25% Standard Standard Standard limiter, Programmable DECS-250N
250 12.5 480/-480 480Vac 13600 Logic, Stator Current
Limiting and Real-Time
Monitor

Low cost, micro-based


includes Auto Tuning,
63 7 9 10 90 120Vac
DECS-150 Standard Standard <1 90-660 50/60 50-500 650 0.25% Standard Standard Standard SCL Limiter, DECS-150
125 10** 17.85 14 135 240Vac
Programmable Logic,
and Real Time Monitor
Designed to control
BE2000E 75 3 18 7.5 150 Standard Standard <1 120-600 50/60 180-240Vac 120-300 330 0.25% Standard Standard Standard BE2000E
single phase PMGs
AVC63-2 63 2 32 3.17 100 Standard No N/A 208/240 50/60 240Vac 50/60 350 1.0% None None None Encapsulated AVC63-2
AVC63-2.5 63 2.5 25.2 3.97 100 Standard No N/A 208/240 50/60 240Vac 50/60 350 1.0% None Standard None Encapsulated AVC63-2.5
AVC63-4 63 4 15 7 100 Standard No N/A 208/240 50/60 240Vac 50/60 500 1.0% None Standard Shutdown Encapsulated AVC63-4
AVC63-4A 63 4 15 9 134 Standard No 0.25 120/240 50/60 120Vac 50/60 450 1.0% None Standard Standard Encapsulated AVC63-4A
Encapsulated with
AVC63-4D 63 4 15 7 100 Standard No N/A 208/240 50/60 240Vac 50/60 500 1.0% None Standard Shutdown AVC63-4D
pots. down
AVC63-7 63 7 9 12 100 Standard No <5 208/240 50/60 240Vac 50/60 900 0.25% Standard Standard Shutdown Encapsulated AVC63-7
50/60 or
AVC63-12 63 12 5.25 24 125 Standard Standard <1 120/240 120Vac 50-400 1092 0.50% Standard Standard Standard High power, low cost AVC63-12
400
50/60 or
AVC125-10 125 10 12.5 20 250 Standard Standard <1 120/240 240Vac 50-400 1750 0.50% Standard Standard Standard Rugged design AVC125-10
400
BE350 73 3.5 21 5 105 Standard No N/A 190/240 50/60 240Vac 50/60 500 1.0% None Standard None Includes EMI BE350
BE300PM 63 3 15 5 100 Standard No 0.25 240 50/60 240Vac 250-300 500 1.00% None Standard Standard Includes EMI BE300PM

Note 1: 120/208/240/416/480/600 Volts


Note 2: This regulator is designed for systems that do not require paralleling. For paralleling applications, contact factory.

*High Power option (250 Vdc Out) is 50/60Hz only.


**10 Adc continuous is possible by limiting the max operating temperature to 55°C.

For more information, please visit our web site - http://www.basler.com