ADDITIONAL

BLOCKS WHERE
DIRECTED

BEND TEE PLAN

STREETiGROUND
/ SURFACE

CROSS

TEE ELEVATION

l,----
----1lPIIII .·:..,:""!-n--------.u 0 ~
o '. ;,11 I Z 0

~
~------~~.~.~------~ ~ ~

~~~.~~=:
~~

18" MINIMUM
INTO NATIVE MATERIAL
T±2 . A" '. . '. '.-

REDUCER VERT BENDS PLAN


SEE NOTE
1 BELOW
ANCHOR BLOCK

END CAP VERT BENDS ELEVATION

NOTES:
1) THE ANCHOR BLOCKS ON VERTICAL BENDS REQUIRE ENGINEER APPROVAL.

2) A MINIMUM OF 6" OF CONCRETE SHALL BE POURED ON WETTED UNDISTURBED OR


COMPACTED SOIL BENEATH EACH INSTALLATION.

3) TEE SHALL BE CONCRETE BLOCKED A MINIMUM OF 6" ON ALL THREE SIDES.

4) USE 12" - 18" LENGTH OF PIPE BETWEEN THE END CAP AND THE LAST
JOINT AS A BOND BREAKER ON DEAD END BLOCKING.
SHEET 1 OF 3

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

ORIGINAL' KA . NAGELVOOR OV12


CITY OF SAN DIEGO - STANDARD DRAWING r/J. . ~/:D:/~ .COMMITIEE
~ ~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
CONCRETE THRUST AND
ANCHOR BLOCK INSTALLATIONS DRAWING
SDW-151
NUMBER
VALVE SUPPORT BLOCK THRUST AND ANCHOR BLOCKS
VALVE DIMENSION DIMENSION MINIMUM BEARING AREA IN SQUARE FOOT
SIZE "A" "8" (SQUARE METERS) SEE NOTE 2
4" 12" 12" MAIN 90' 45'
2
2~'
TEES
6" 12" 12" SIZE BEND BEND BEND
8" 13" 14" 4" 4 5 3 1.5
10" 14" 16" 6" 8 10 5 2.5
12" 15" 18" 8" 12 16 9 4.5
DIMENSION "e" = TRENCH WIDTH 10" 17 24 13 6.5
PLUS TWO TIMES THE PIPE DIAMETER 12" 24 33 19 9.5

z
o
00,
zu
w'
::2:
Ci

VALVE SUPPORT
PLAN

lJ. BOTTOM OF g CONCRETE BLOCK

~~:~~~:E:k;":.: ., .~n.~II~~=:L~:1_ TRENCH TYP \ I?~(J TYPICAL , I.


~ ~ ...........• ~ t::2:

~ .' "
DIMENSION "A" ~ "'---- DIMENSION "C"
0

CLEAR BELL OR
FLG, SEE NOTE 4

VALVE SUPPORT
ELEVATION

NOTES:
1) BEARING AREA BASED ON SOIL BEARING VALUE OF 1500 PSF AND 225 PSI LINE PRESSURE AND A MINIMUM OF 36" COVER:
FOR BEARING= 1000 PSF,1.5 x AREA SHOWN
FOR BEARING = 500 PSF, 3.0 x AREA SHOWN

2) ENGINEER SHALL DETERMINE SIZES, REFER TO SPECIFICATIONS FOR THRUST


AND ANCHOR BLOCK SIZING.

3) THRUST BLOCKS SHALL BE CENTERED ON THE FITTING SO THAT THE BEARING AREA IS
EXACTLY OPPOSITE THE RESULTANT DIRECTION OF THRUST.

4) CONCRETE SHALL BE PLACED SO THAT FITTINGS AND VALVES WILL BE ACCESSABLE FOR
REPAIR OR REPLACEMENT.

SHEET 2 OF 3

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

ORIGINAL' KA~. NAGELVOOR 0V12


CITY OF SAN DIEGO - STANDARD DRAWING r/J. . ~/:D:/~ .COMMITIEE
~ ~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
CONCRETE THRUST AND
ANCHOR BLOCK INSTALLATIONS DRAWING
SDW-151
NUMBER
24"
MINIMUM (1YP)

.. ~.: ':. '~ ", ~:. ~~~\ ..: '1,:. :~,~".~';: __


.::~': .

PLAN
TEE WITH GATE VALVES GATE WELL TYPICAL

EDGE OF TRENCH
TYPICAL

BUTIERFLY
VALVE (1YP)

ACTUATOR ..... '~'.

TYPICAL
BEARING : .. ~" ,_ .. " .'~ '" ,,~.
SAND BAGS
AREA "B" MASONRY SUPPORT
TYPICAL
TYPICAL
BEARING BLOCKS, TYPICAL
AREA "A" (1YP) WITH REDWOOD
PLAN SECTION WEDGES AS REQ'D

TEE WITH BUTTERFLY VALVES ON MAIN


GATE WELL TYPICAL

SAND BAGS
TYPICAL

SECTION

TEE WITH BUTTERFLY VALVES

NOTES:
1) BEARING AREA "B" MUST BE EQUAL TO OR GREATER THAN THE AREA REQUIRED FOR A 90*
ELBOW INSTALLATION.

2) INSTALL SAND BAGS AROUND BUTIERFLY VALVE ACTUATOR TO ISOLATE IT FROM CONCRETE.

3) BFV'S INSTALLED AT CROSSES OR TEES REQUIRE A FLANGED DUCTILE IRON SPOOL TO BE


INSTALLED BETWEEN THE FITIING AND VALVE IN ACCORDANCE WITH THE SPECIFICATIONS.

SHEET 3 OF 3

REVISION BY APPROVED DATE RECOMMENDED BY THE CITY OF SAN DIEGO

ORIGINAL' KA . NAGELVOOR OV12


CITY OF SAN DIEGO - STANDARD DRAWING r/J. . ~/:D:/~ .COMMITIEE
~ ~ 1/31/2012
COORDINATOR R.C.E. 65271 DATE
CONCRETE THRUST AND
ANCHOR BLOCK INSTALLATIONS DRAWING
SDW-151