Professional Documents
Culture Documents
Hasa 8
Hasa 8
Abstract—Direct Online (DOL) starting inrush current of II. VOLTAGE DIP DUE TO INDUCTION MOTOR AND
induction motor creates voltage dip throughout the distribution RESTORATION BY VSDG
network. This is one of the main causes of disruption of nearby
sensitive equipment. This paper analyses the characteristics of A. Severity of Voltage Dip during Motor Starting
voltage dip due to the DOL starting induction motor and The typical characteristics of an induction motor starting
explores an approach for mitigating the voltage dip using voltage voltage dip is shown in Fig. 1. It can be seen that this type of
support distributed generation (VSDG). A control strategy to dip has a voltage sensitive zone 1 for a period of 0.1s when the
mitigate the motor start transient and to restore the network
voltage magnitude falls below 0.9 pu and a voltage sensitive
voltage quickly is proposed. Simulation studies are carried out in
Zone 2 when voltage magnitude pulls up from 0.9 pu to 0.95
order to validate the theoretical framework. It is shown that
VSDG can restore the motor starting transient voltage dip
pu before reaching the steady state condition. Within Zone-2
quicker than a voltage regulator or an on-load tap changer the voltage magnitude increases slowly. The recovery time
(OLTC). depends on a number of factors related to several system
conditions: strong or weak network, motor size, motor type,
Keywords-Motor start transient; voltage sag/dip; voltage type of load connected with the motor, location of motor etc.
support distributed generation Hence before designing any mitigation scheme we need to
perform system study in order to quantify the voltage change in
I. INTRODUCTION the network, and to keep the change within acceptable supply
limits. Also this study can determine if the proposed supply
Voltage dip is defined as the reduction of rms voltage arrangements are adequate to start the motor.
between 0.1 pu and 0.9 pu for a duration of 0.5 cycle to 1
minute [1]. Voltage dip is the predominant cause of disruption
to the sensitive equipment used by both commercial and
industrial customers. Due to widespread impact, it is
considered as the most frequently experienced power quality
problem by the customers. Dips are usually caused by faults in
power system or the connection of a heavy load and starting an
induction motor at any place within the network. Most of the Figure 1. Induction motor starting transient voltage dip.
previous research study on voltage dip considered power B. Voltage Dip Restoration with DG
system faults. Only few studies focused on investigating
voltage dip, due to induction motor starting [2]-[3].
Usually, large motors are directly connected to the supply
line and start as DOL (Direct Online) in order to acquire
constant speed, operational simplicity and reduced cost.
However, the starting current requires to produce starting
torque may be 8 to 10 times the full load current which creates
voltage dip at motor terminal. Motor starting voltage dip is
typically longer in duration (greater than 30 cycles) and lower Figure 2. Single line diagram of the test distribution network (LV side).
in magnitude compared to fault-induced voltage dip (0.5 to 30 To calculate the voltage at neighboring bus during motor
cycles). 60%-80% of world's electricity is used for running starting, the distribution network presented in Fig. 2 is
induction motors in domestic and industrial appliances, such as analyzed. A total N number of buses is shown in the model,
driving pumps, fans, compressors, elevators and industrial
where the induction motor (M) is connected at the bus x with
machinery of various types. So the frequency of occurrence of
motor starting dip is higher compare to fault-induced dip. This motor impedance Zm. At bus k, there is a sensitive load (SE)
means that the cost of the mitigation for motor starting dip is which may trip if voltage magnitude is below the threshold
higher. The objective of this paper is: a) to analyze the voltage value. The DG is connected at the bus (N+1). Along with
dip which may occur during connection of the induction motor generating real (P) power, DG units are capable of providing
to the network, and b) to investigate the effectiveness of DG as ancillary services such as reactive (Q) power injection, voltage
low cost voltage support source during motor start. dip compensation and harmonic filtering [4]. This paper aims
(a) (b)
Figure 4. Voltage dip with (a) different distances, (b) restoration using DG.