Professional Documents
Culture Documents
Temptron 607AC - O300 (English)
Temptron 607AC - O300 (English)
Temptron 607AC - O300 (English)
TempTron 607A-C
Program version: O300
Updated: 22.10.2019
By:
Contents
Document Information -------------------------------------------------------------------------------------- 4
Front Panel ------------------------------------------------------------------------------------------------------ 5
Reading Function Set Points ------------------------------------------------------------------------------- 6
Shortcut keys ---------------------------------------------------------------------------------------------------- 6
Recall Function Settings ------------------------------------------------------------------------------------ 6
Programming Function Setting -------------------------------------------------------------------------- 7
Function List ---------------------------------------------------------------------------------------------------- 7
1. Current Time ---------------------------------------------------------------------------- 7
2. Required Room Temperature -------------------------------------------------------- 7
3. Heat -------------------------------------------------------------------------------------- 7
4. Heat Hysteresis ------------------------------------------------------------------------- 7
5. Speed Hysteresis ----------------------------------------------------------------------- 8
Variable Speed Fan Control --------------------------------------------------------------------------------- 8
6. SP Fan Temperature -------------------------------------------------------------------- 8
7. SP Fan Speed Temp Ratio------------------------------------------------------------- 8
8. SP Fan Min Speed ---------------------------------------------------------------------- 8
9. SP Fan Max Speed---------------------------------------------------------------------- 8
10. SP Fan Speed ---------------------------------------------------------------------------- 9
11. Fan On Time----------------------------------------------------------------------------- 9
12. Fan Off Time ---------------------------------------------------------------------------- 9
13. Humidity Set Point --------------------------------------------------------------------- 9
14. Humidity Step -------------------------------------------------------------------------- 9
15. Increase Speed Step (Humidity) ----------------------------------------------------- 9
16. Temperature Humidity Condition ---------------------------------------------------- 9
17. Flap Min Pos/ Min---------------------------------------------------------------------- 9
18. Flap Max Pos/ Min --------------------------------------------------------------------- 9
19. Speed-Limiter Speed ---------------------------------------------------------------- 10
20. Speed-Limiter Time ------------------------------------------------------------------10
21. Fan 1------------------------------------------------------------------------------------10
22. Fan 2------------------------------------------------------------------------------------10
23. Fan 3------------------------------------------------------------------------------------10
24. Flap 1 position %----------------------------------------------------------------------10
25. Flap 2 position %----------------------------------------------------------------------10
26. Flap 3 position %----------------------------------------------------------------------10
27. Cool --------------------------------------------------------------------------------------10
28. Cool Hysteresis ------------------------------------------------------------------------10
29. Cool On Time --------------------------------------------------------------------------11
30. Cool Off Time--------------------------------------------------------------------------11
31. Cool Grow Day ------------------------------------------------------------------------11
32. Alarm Low------------------------------------------------------------------------------11
33. Alarm High -----------------------------------------------------------------------------11
34. Alarm Type -----------------------------------------------------------------------------11
35. Alarm Disable --------------------------------------------------------------------------12
36. Minimum Temperature ---------------------------------------------------------------12
37. Minimum Temperature Time --------------------------------------------------------12
38. Maximum Temperature ---------------------------------------------------------------12
39. Maximum Temperature Time--------------------------------------------------------12
40. Minimum Humidity -------------------------------------------------------------------12
TROUBLE-SHOOTING --------------------------------------------------------------------------------- 17
Revision History
Document version Program version Date Description
Ver. 1.0 O300 First edition
Attention!!
1. This manual may contain mistakes and or printing errors. We accept no liability for
technical mistakes or printing errors, or their consequences.
2. This control unit is supplied with default settings. These setting are only general
settings and should not be seen as final settings. We accept no liability for any
consequences that may occur because of these settings.
Function list
Keyboard
Relay functions
Enter key
Program key Data key
Display screen: The entered values for each function are displayed here.
Function list: Shown here is the list of functions for the 607 program.
Relay functions: Each relay operates a particular output. When an output is in use the
corresponding led goes on.
Enter key: Press on the enter button to store entered values into the 608 memory.
Program key: Press on the PROG button to enter the programming mode for a
chosen function.
Keyboard: A numeric keyboard for entering the set point values for each function.
Shortcut keys
To display temperature sensor 1 readout, press on keyboard number 1. To display
temperature sensor 2 readout, press on keyboard number 2. To display temperature
sensor 3 readout, press on keyboard number 3. To display temperature sensor 4
readout, press on keyboard number 4. To display temperature sensor 5 readout, press
on keyboard number 5. To display the current humidity readout, press on keyboard
number 6.
To display the minimum ventilation cycle time, press on keyboard number 7. To
display current flap position, press on keyboard number 8.
Each set point has a Function number (see Function list on the front panel). It is
possible to call up and program the functions in two ways:
1. Press once on the DATA key, the function number display on the right side of
the panel will increase by one. The programmed information for each function
will appear on the data display screen on the left side of the panel.
2. Press once on the 0 key, two lines will appear on the function display and
FUNC on the data display. Next enter the required function number using the
keyboard and then press Enter.
Example:
If you would like to recall function 8 follow these steps:
Press once on the 0 key. Two lines will appear on the right display (function display).
Press on the 0 key, then on the 8 key.
The function display will display 08. The data display will show the current
programed setting for this function.
If a function number is larger than 10, press on key 0, then the function number.
Example:
If you would like to recall function 12; Press on the 0 key.
Press on the 1 and 2 keys.
The function display will display 12. The data display will show the current
programed setting for this function.
Function List
1. Current Time
Display the current time.
3. Heat
Enter here the average house temperature that when reached will turn on the heating
system.
4. Heat Hysteresis
Example:
Function 02: 25.0
Function 03: 23.0
Function 04: 0.3
Means:
The heater turns on when the room temp is equal or lower than 22.7 C. There is 0.3 C
delay from 23.0 (function 03).
Same case as when the heater should turn off, the heater turns off when the room
temp is equal or above 23.3 C.
The function 04: 0.3 C is not a FIXED value but an input variable, you can input how
many delay they want
Example:
Function 02: 25.0
Function 05: 0.2
Function 06: 1.0
Means:
Intermittent will start at (25.0 – 0.2 = 24.8) and stop at (25.0+0.2 = 25.2)
The function 05: 0.2 is not a FIXED value but an input variable, you can input how
many delay you want.
6. SP Fan On Temperature
Temperature differential above the required room temperature. At (Required Room
Temperature + SP Fan Temperature) the SP fans start to increase in speed according
to the SP Fan Speed Temp Ratio Function 07 below. Up to (Required Room
Temperature + SP Fan Temperature), the SP fans run at the set minimum speed
percentage (function 08 below) or Intermittent Mode).
Example:
Function 02: 25.0
Function 07: 10
Means:
When Actual Temperature is 26.0 then the speed has increased by 10%
This setting is also used for the cooling system. If the cooling system is
running and the humidity reading in the house rises to this level, the cooling
system will not be allowed to operate.
Means:
When Actual Humidity reach 83%, we want the speed to increase by 10% from the
actual speed.
Means:
When Actual Humidity reach 83%, we want the speed to increase by 10% from the
actual speed.
Means:
When there is power switch (power plant – generator) and/or one or more speed fans
having trouble and about to restart automatically, the TempTron will instruct the
other fans to run at speed 30% for 1 minute, then go back to its normal speed.
21. Fan 1
Fan 1 set point is the temperature differential above the required temperature at which
Fan 1 will start running.
22. Fan 2
Fan 2 set point is the temperature differential above the required temperature at which
Fan 2 will start running.
23. Fan 3
Fan 3 set point is the temperature differential above the required temperature at which
Fan 3 will start running.
27. Cool
Enter here the average house temperature that when reached will turn on the cooling
system. Once on, the system will run in its cycle mode according to the Cool On and
Cool Off times (functions 23 and 24).
Means:
The cooling system turns on when the actual room temp is equal or higher than 28.3
C. There is 0.3 C delay from 28.0 (function 21).
Same case as when the cooler should turn off, the cooler turns off when the room
temp is equal or above 27.7 C.
The function 22: 0.3 C is not a FIXED value but an input variable, you can input how
many delay you want.
Example:
Function: Value:
21. Cool 28.0°
22. Cool Hysteresis 0.3
23. Cool On Time 02:00
24. Cool Off Time 05:00
If the average house temperature reaches 28.3°, the cooling system will start to
operate. The cooling system will run for 2 minutes, and be off for 5 minutes when
average house temperature reaches 27.7°.
Humidity Set Point (function 13) is also used for the cooling system. If the
cooling system is running and the humidity reading in the house reaches the
humidity set point, the cooling system will turn off.
31. Cool Grow Day
Enter here the grow day that the cooling system will be activated. From this day, if
the average house temperature is equal to or above the setting set in function 16, the
cooling system will operate. Up to this day the cooling system will be disabled.
Example: If 5.0° is entered in the alarm low function, if the average house
temperature falls 5.0° below the required room temperature (function 02), the alarm
relay will be activated.
Example: If 5.0° is entered in the alarm high function, if the average house
temperature raises 5.0° above the required room temperature (function 02), the alarm
relay will be activated.
Example:
If your cool on time = 1 minute and cool off time = 2 minutes, you will see timer that
counts down from 180 to 0.
When it reaches from 180 to 120 cool will off, when it reaches from 120 to 0 it will
restart again to 180 and cool will work.
Example:
If your fan on time = 1 minute and fan off time = 2 minutes, you will see timer that
counts down from 180 to 0.
When it reaches from 180 to 120 cool will off, when it reaches from 120 to 0 it will
restart again to 180 and cool will work.
Example: Enter 25. The unit will assume that 25 kilos of feed pass through the auger
each minute. After 10 minutes the feed consumption will be 250 kilos.
Example:
Index Table No. Timer 1 On Timer 1 Off Timer 2 On Timer 2 Off
1 a b
2 c d
…
9
1. Enter 1 (function 39)
2. Go function 40 to enter a
3. Go function 41 to enter b
4. If you want to enter c and d, first go to function 39 (enter 2) to go row 2
5. Go function 40 to enter c
6. Go function 41 to enter d
7. And so on until row 9. Do the same thing to enter function 42 and 43
51. Timer 1 On
Enter the time HH:MM (hours : minutes) to turn on RELAY Timer 1
Example:
To Enter temperature reduction of 2 C over 7 days, enter function 45, press on the
program button, and press on 7, then 2, then 0, then on Enter. On the display will
appear: 7 2.0 G1
Push on data key, next group will appear.
To enter temperature reduction of 1.5 C in 3 days, push on 3,
then on 1, then on 5, then on Enter.
On the display will appear: 3 1.5 G2.
65. Flap %
Current Flap position in percent.
67. Navr
It is necessary to define the number of temperature sensors that will be used for the
average temperature reading.
Enter the number of sensors. If two sensors are used enter the value 2. It is possible to
enter up to 4 sensors for the average temperature
Example: 10
The flap will move in steps of 10%.
Example 2:
Reading of temp sensor 5 is 24.5
Example 3:
Reading of Humidity sensor is 75%
Costumer wants reading of 64%
You need to go to function 80 and put value 1_11
This will reduce 11% from actual reading so after that correction costumer will get
reading from Humidity sensor: 75-11=64
We allow in code maximum of 3.0 correction for temp sensors and maximum of 30%
in humidity sensor for safety reasons.
83. Version
The number shown is the program version number for your unit
Relays:
0: Alarm 1: Heat 2: Speed Fan 3: Fan 1 4: Fan 2
5: Fan 3 6: Timer 1 7: Cool
Digital Input:
1: NONE 2: Water 3: Feed 4: Speed Alarm
Analog Input:
1, 2, 3, 4, and 5: Temperature 6: Humidity
Analog Output:
1: SP fan out 2: Flap out
TROUBLE-SHOOTING
1. If a temperature sensor or its cable is disconnected, the sensor reading will show
OPEN.
2. If a temperature sensor or its cable is shorted, the sensor reading will show
SHORT
3. If both sensors are disconnected, the unit will show open as average and activate
the alarm.
If one sensor is disconnected, the system will automatically work on the remaining
sensor.