ZYKT-32R控制器用户随机手册(S911002 1.0)-2020.9.28.zh-CN.en
ZYKT-32R控制器用户随机手册(S911002 1.0)-2020.9.28.zh-CN.en
com
① Product series ZYKT: Central air conditioning controller - The RS485 port (COM2/COM3, A is RS485+, B is RS485-) can be used to connect the touch screen, communicate with some instruments, etc.,
ZYKT-32R controller ② Number of input and output points 32:18 input/14 output Electrical Design Reference and can also be used to connect computer host computer programming software and PLC. Supports MODBUS, X-NET fieldbus
to use the ZYKT-32R host computer programming software, please refer to the "XD/XL/XG Series Programmable Controller User
Insulation voltage DC 500V 2MΩ or more 8) (3) - Analog input and output definition number allocation
Anti-noise Noise voltage 1000Vp-p 1us pulse 1 minute
Manual [Software]" separately issued bythe
》; For ourprogramming
company. methods and instructions of ZYKT-32R, please refer to our company’s other The PLC register definition number corresponding to the analog channel is as follows:
Air No corrosive or flammable gas
"XD/XL Series Programmable Controller User Manual [Basic Instructions]" published by aisle AD signal aisle AD signal
》; Electronic version download URL:
0℃~60℃ 9)
0CH ID0 3CH ID3
ambient temperature
11)
The main features of ZYKT-32R plate heat exchange controller: Communication port 1 (COM1)
2CH ID2
RS232, connect to host computer, human-machine interface programming or debugging
Communication port 2 (COM2) RS485, connect smart instruments, frequency converters, etc.
- Higher instruction processing speed, 0.05us; 12) aisle DA signal aisle DA signal
RJ45, supports Ethernet communication, realizing remote control of industrial field equipment
0CH QD0 2CH QD2
Communication port 3
- Up to 16 XD series expansion modules can be connected. ※2: Individual grounding or shared grounding should be used for grounding. Public grounding cannot be used. The names of each part are as follows:
- Analog mode configuration
①: Power terminal, input terminal ⑧: System indicator light
AD and DA channels are configured according to the following table:
Safety Precautions
Table 2: Performance Specifications
interlock switches to prevent machine damage in the external circuit of the controller; number※2 Output points 14 points Y0~Y15 - Terminal definition Byte4
000:0-10V 000:0-10V
- In order to enable the equipment to operate safely, please design external protection circuits and safety mechanisms for output signals related to major Number of analog input channels 5 channels of 4~20mA current or 0~10V voltage are optional (selected through DIP switch) reserve reserve
- Power input, switch input terminal 011:4-20mA 011:4-20mA
accidents; Number of analog output channels 3 channels (4~20mA current or 0~10V voltage optional) SFD722
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
- The controller CPU may cause all outputs to turn off after detecting an abnormality in its own system; when part of the controller circuit Analog accuracy AD: 12bit (0~4095) ;DA: 12bit (0~4095)
AD4 AD3
fails, its output may be uncontrolled. To ensure the normal operation of the equipment, a suitable external control circuit must be designed; 1280 points - 24V and 0V are power input terminals, and FG is the ground terminal;
Byte5
Internal coil (X)
X0~X77, X10000~X11777, X20000~X20177, X30000~X30077 - L+ and M are switch input power supply terminals. If they are the same power supply as 24V and 0V, they do not need to be connected.
000:0-10V 000:0-10V
reserve reserve
-
1280 points 011:4-20mA 011:4-20mA
When the relay output unit of the controller is damaged, its output cannot be controlled to the ON or OFF state; the controller is designed to Internal coil (Y) - 24V, switching output terminal
Y0~Y77, Y10000~Y11777, Y20000~Y20177, Y30000~Y30077
- be used in indoor electrical environments, and its power supply system level should have a lightning protection device to ensure that
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
internal coil M0~M69999【HM0~HM11999】※3
(M, HM)
87000 points reserve AD5
lightning overvoltage is not applied to the controller power input end, signal input end, control output end and other ports to avoid Special use※4SM0~SM4999 Byte6
- 24V, 0V can power the sensor, but cannot be connected to an external power supply;
damaging the equipment. Process(S) 9000 points S0~S7999【HS0~HS999】※3 reserve 000:0-10V
- Different Y points correspond to different COM points, such as Y6~Y11 corresponding to COM2. reserve reserve
1 2 4: RxD weight it to obtain an effective filter value; the filter coefficient is set by the user to 0~254. The smaller the value, the more stable the data is, but May
Danger! 34 5 5:TxD cause data lag; therefore, when set to 1, the filtering effect is the strongest and the data is the most stable. When set to 254, the filtering effect is the
6 8 .
- Please turn off the power before connecting or removing the communication cable, connecting or removing the cable of the expansion card
Table 3: Analog-to-digital conversion diagram
7 8:GND
weakest. The default is 0 (no filtering)
or control unit, otherwise it may cause damage to the equipment and misoperation;
0~20mA analog input 0~10V analog input (2) In the AD part, in addition to setting the mode in the register, the DIP switch must also be set to the corresponding mode.
Notice! Character
Character
project content
quantity quantity
- When loading and unloading expansion cards, be sure to cut off the power supply;
0 4mA 20mA 0 10v 2 1 Voltage allowable range DC21.6V~26.4V
Analog quantity
Analog quantity
5 43 120mA DC24V
- The button battery needs to be replaced in a charged state (to ensure that the memory data is not lost when the power is turned off) ;Equipment running with power updated
8 6
Rated frequency
0~10V analog output 4~20mA analog output 7 Allow momentary power outage time 10msDC24V
20mA
When replacing batteries, professional electrical technicians must wear insulating gloves before performing the operation.
4mA -
- name
rule
quantity
(1) The above picture is the DVP line wiring diagram. The colors of the 2, 3, and 5-pin inner wires on the DB9 plug (hole) side are brown, red, and The controller body provides DC24V power output (24V, 0V terminals), which can be used as a power supply for sensors. This terminal cannot
① ②③ Notice:When the input data exceeds K4095, the output analog data of D/A conversion remains unchanged at 10V or 20mA. connected to the No. 7 terminal on the back (DB9).
- Switch input specifications and wiring Relay output wiring diagram:
The input is NPN mode. The internal structure and wiring method of this mode are introduced below:
Prevent load short circuit and other faults from burning out the PLC
5A〜10A fuse
project content 5A〜10A
Input signal voltage DC24V±10% +24V ~AC power
load <AC250V
Input signal current 7mA/DC24V
Y*0
follow
Input ON current 4.5mA or more
electricity
For inductive loads connected to AC circuits, an RC instantaneous voltage absorption circuit should be considered in the external circuit; for
- Installation Notes
inductive loads connected to DC circuits, a freewheeling diode should be considered, as shown in the figure below:
The controller is installed using DIN46277 guide rail. When dismantling it, just pull down the assembly hook of the DIN guide rail and remove
+ -
Inductive load
﹢- ●
COM COM Note: Freewheeling diode 1N4007.
● ●
- AC load
●
~ ~
●
Inductive load
●
X0 X0
PLC output contact
Three-wire (NPN type) proximity switch wiring diagram example Two-wire (NPN type) proximity switch wiring diagram example
surge absorber
- Switching output specifications and wiring
Note: Surge absorber R=200Ω 2W,C=0.022uF 250V ac.
The output is relay mode. The internal structure and wiring method of this mode are introduced below:
- Output specifications
- Analog input and output wiring
+24V
CH1 current/voltage input
CH0 current/voltage input
- The relay output type has 2~4 common terminals. Therefore, each common terminal block unit can drive loads of
different power supply voltage systems (for example: AC200V, AC100V, DC24V, etc.);
- Between the relay output coil and the contact, the internal circuit of the programmable controller and the external circuit load circuit are
electrically insulated; in addition, the common terminal blocks are also separated from each other;
- When the coil of the output relay is energized, the LED light turns on and the output contact is ON; the response time from when the coil
- of the output relay is energized or cut off to when the output contact is ON or OFF is about 10ms;
Notice:Current output does not need to be connected in series with DC24 power supply!
- For currents and voltages below AC250V, the output current that can drive purely resistive loads is 5A/1 point, and
inductive loads are below 120VA (AC100V or AC200V). and lamp load below 120W (AC100V or AC200V);
Product dimensions and installation
- When the output contact is OFF, no leakage current is generated, and it can directly drive neon lamps, etc.;
-
-
Standard service life of inductive AC loads such as contactors and solenoid valves: According to the rough standard of relays obtained
80VA About 100,000 times. However, if the load is connected in parallel with a surge absorber, the life will be significantly extended.