RAPHAEL FP Deluge Valve, Ductile Iron, ANSI150 Flange Drilling, 240psi, Electric Actuated, UL Listed, FDV-DEO

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Fire Protection

Deluge Systems
Electric Actuated with Local Reset Deluge Valve FDV - DE0
The FDV is a Fire Protection control valve for Deluge fire
sprinkler systems, designed for installations in hazardous
environments.
The FDV-DE0 Deluge system is actuated electrically and
resets locally.
An electric detection system activates a solenoid valve
through a control panel to open the FDV deluge valve.
The Deluge system incorporates an emergency valve,
bypassing the fire detection systems for manual operation.
Designed for vertical or horizontal installation, a globe
pattern, line pressure operated FDV-DE0 valve features
a direct elastomeric diaphragm Seal. It has no balancing
spring or internal metallic wet components in the valve
body. The hydrodynamic pattern design, ensures high
flow rates with minimum head loss.

AVAILABLE CONNECTIONS ENDS:


Flange X Flange / Groove X Groove / Thread X Thread

MARKETS ADVANTAGES

• Only three parts: body, diaphragm & cover plate. No wet metal spring inside
the control chamber
Commercial Marine Residential • Full bore unobstructed
• Simple manual reset of the valve to standby position without draining or
opening the valve itself, neither closing OS&Y or other valves in the system
• Open fail safe valve, maintained in stand-by closed position
Industry • Low maintenance cost: the valve is serviced in-line with only one replaceable
part which is long life elastomeric diaphragm
T E C H N I C A L D ATA
• Conforms with inspection, testing and maintenance standard of water-based
FLUID: fire protection systems, NFPA 25
Water, Brackish water, Sea water, Foam
SIZE RANGE:
40mm to 250mm (1½’’ to 10”)
CHARACTERISTICS
AVAILABLE CONNECTIONS ENDS: • Hydro-dynamic pattern design ensures high flowrates with minimum head
Flange*Flange, Groove*Groove, loss
Flange*Groove, Groove*Flange, • The valve trips open automatically upon a gradual release of water pressure
Thread*Thread from its control chamber. The trip is actuated by an electric signal transmitted
PRESSURE NOMINAL: to the valve’s solenoid from the main control panel, due to a flame heat
250 psi (17.2 bar) exposure of a sensors detection system

A P P R O VA L S • Soft closing upon pressurization of the valve’s control chamber, by line


pressure or other independent water source, prevents surges
The FDV-DE0 resets to stand-by close position by pressurizing the Dry Pilot
Line and manually operating the PSA device.

13
Fire Protection
Schematic drawing
Set position Fire position

BF - Butterfly valve SR - “Y” strainer TV - Alarm test valve


DL - FDV Deluge valve CV - Check valve EU - Emergency Manual Unit
AL - Acoustic & Electric alarms PS - PSA – Pressure Supply Arrestor S2 - Solenoid 2 way
TS - Trim supply valve MD - MADV – Man/Auto Drain Valve ES - Electric Sensors

OPERATION
SET position
Pressurized water in the valve’s control chamber (DL) is trapped by the closed PSA (PA), the closed 2 way solenoid
valve (S2) and by the closed emergency valve (EU), maintaining the FDV deluge valve (DL) closed.

FIRE situation
When an electric detection system senses flame heat, it triggers the main control panel that in turn,transmits an
electric signal, commanding the 2 way solenoid valve (S2) to open and drain the deluge valve’s control chamber.
The FDV Deluge valve opens and admits water to the spray sprinklers line.

RESET position
System reset requires the reset of the electrical alarm system to de-energize and close the solenoid valve, not allowing
the FDV control chamber to drain. The PSA (PS) push button should be pressed to enable upstream pressure passage to
TALIS FP RANGE

close the FDV main valve.

14
Fire Protection

FDV - DE0
Typical installation

ES

MD

DL

S2
PS
AL
CV

TV SR

EU
TS

BF

BF - Butterfly valve SR - “Y” strainer TV - Alarm test valve


DL - FDV Deluge valve CV - Check valve EU - Emergency Manual Unit
AL - Acoustic & Electric alarms PS - PSA – Pressure Supply Arrestor S2 - Solenoid 2 way
TS - Trim supply valve MD - MADV – Man/Auto Drain Valve ES - Electric Sensors

15
Fire Protection
Dimensions Table
Vertical

C
1 1/2” 2” 3” 4” 6” 8”
Size
mm Inch mm Inch mm Inch mm Inch mm Inch
A 172 6.8 265 10.4 280 11 304 11.9 335 13.2
B 244 9.6 230 9.0 245 9.7 267 10.5 294 11.6

D
C 26.4 1 84 3.3 73 2.9 69 2.7 63 2.5
D 224 8.82 325 12.8 400 15.8 462 18.2 580 11
E 128 5 76 2.9 41 1.6 12 0.5 - -
F 168 6.6 178 7 209 8.2 237 9.3 265 10.4
G 170 6.7 200 7.8 240 9.5 302 11.9 342 13.4

E
Kg/lb 16.9 37.3 29.2 64.4 46 101.5 64.6 142.6 104 229.5
A B

Horizontal
1 1/2” 2” 3” 4” 6” 8”
Size
mm Inch mm Inch mm Inch mm Inch mm Inch
A 290 11.4 265 10.4 280 11 304 12 330 13
B 188 7.4 201 7.9 215 8.4 240 9.5 266 10.5
C - - - - - - - -
D 244 8.8 325 12.8 400 15.8 465 18.2 580 11
E 98 3.9 47 1.8 12 0.5 -
F 157 6.2 171 6.7 208 8.2 231 9 266 10.5
G 209 8.2 238 9.3 277 10.9 341 13.4 373 14.7
Kg/lb 16.7 36.8 29.2 64.4 45.8 101 64.6 142.6 104.2 229.7
F G

Factory Standard

MAIN VALVE: TRIM PLEASE SPECIFY


BODY & COVER PIPING & TUBING: • Working Media
• Ductile iron • Stainless Steel 316 • Ambiental conditions
• Cast Steel WCB • Copper/Brass • Min/Max operating flow
• Stainless Steel CF8 • Cupro-Nickel • Min/Max operating pressure
• Stainless Steel CF8M • Monel ® • Energize to Open/Close valve
• Nickel Aluminum Bronze • Solenoid Voltage
FITTINGS:
• Solenoid Enclosure
ELASTOMERS: • Stainless Steel 316
• Solenoid Protection
• NR, fabric reinforced Natural Rubber • Brass
• Pneumatic working pressure
• EPDM, fabric reinforced • Super Duplex
• System installation orientation
• NBR, fabric reinforced Nitrile Rubber • Cupro-Nickel
• Additional accessories needed
• Monel®
COATING:
• Rilsan Polyamide based (Nylon 11) ACCESSORIES:
• Polyester based EPC • Brass Nickel plated
TALIS FP RANGE

• High built Epoxy FBE • Nickel Aluminium bronze


• Vitreous Enamel (internal only) • Stainless steel CF8M
• Monel®
• Cupro-Nickel

For more detailed technical information, please refer to chapter Engineering Data.

16
CERTIFICATE OF COMPLIANCE
Certificate Number 20160617-EX26941
Report Reference EX26941-20160616
Issue Date 2016-JUNE-17

Issued to: RAPHAEL VALVES INDUSTRIES (1975) LTD


N INDUSTRIAL ZONE
PO BOX 555
30600 OR-AQIVA ISRAEL

This is to certify that SPECIAL SYSTEM WATER CONTROL VALVES, DELUGE


representative samples of TYPE
See Addendum

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: UL 260, Standard for Dry Pipe and Deluge Valves for Fire
Protection Service
ULC-ORD-C260-1975, Guide for the Investigation of Dry
Pipe, Deluge, and Pre-Action Valves for Fire Protection
Service
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 3
CERTIFICATE OF COMPLIANCE
Certificate Number 20160617-EX26941
Report Reference EX26941-20160616
Issue Date 2016-JUNE-17

This is to certify that representative samples of the product as specified on this certificate were tested
according to the current UL requirements.

FDV-DE0 –Electrical Actuated with Local Reset Deluge Valve and FDV-DH0 – Hydraulic Actuated with
Local Reset Deluge Valve in 1.5, 2, 2.5, 3, 4, 6 and 8 in. sizes, for vertical installation for pressures not
exceeding 250 psig (1730 kPa) as shown in the manufacturer’s installation instructions.

MFDV-AH1 –Hydraulic Actuated with Remote Reset Deluge Valve, FDV-DE1 –Electrical Actuated with
Remote Reset Deluge Valve and FDV-DH1 – Hydraulic Actuated with Remote Reset Deluge Valve in
1.5, 2, 2.5, 3, 4, 6 and 8 in. sizes, for vertical installation for pressures not exceeding 250 psig (1730
kPa) as shown in the manufacturer’s installation instructions.

FDV-DP1 – Pneumatic Actuated with Remote Reset Deluge Valve and FDV-AP1 –Pneumatic Actuated
with Remote Reset Deluge Valve in 1.5, 2, 2.5, 3, 4, 6 and 8 in. sizes, for vertical installation for
pressures not exceeding 250 psig (1730 kPa) as shown in the manufacturer’s installation instructions.

FDV-DC0 – Pneu-Electric Actuated with Local Reset Deluge Valve, FDV-AC1 –Pneu-Electric Actuated
with Remote Reset Deluge Valve and FDV-DC1 – Pneu-Electric Actuated with Remote Reset Deluge
Valve in 1.5, 2, 2.5, 3, 4, 6 and 8 in. sizes, for vertical installation for pressures not exceeding 250 psig
(1730 kPa) as shown in the manufacturer’s installation instructions.

FDV-DA1 – Hydraulic actuated & Anti-Columning Remote Reset Deluge Valve in 1.5, 2, 2.5, 3, 4, 6 and
8 in. sizes, for vertical installation for pressures not exceeding 250 psig (1730 kPa) as shown in the
manufacturer’s installation instructions.
FDV-PE0–Electrical Actuated with Local Reset, Pressure reducing Deluge Valve and FDV-PH0 –
Hydraulic Actuated with Local Reset, Pressure reducing Deluge Valve in 1.5, 2, 2.5, 3, 4, 6 and 8 in.
sizes, for horizontal installation for pressures not exceeding 250 psig (1730 kPa) as shown in the
manufacturer’s installation instructions.

FDV-PH1 –Hydraulic Actuated with Remote Reset, Pressure reducing Deluge Valve in 1.5, 2, 2.5, 3, 4,
6 and 8 in. sizes, for horizontal installation for pressures not exceeding 250 psig (1730 kPa) as shown
in the manufacturer’s installation instructions.

FDV-PP0 –Pneumatic Actuated with Local Reset, Pressure reducing Deluge Valve and FDV-PP1 –
Pneumatic Actuated with Remote Reset, Pressure reducing Deluge Valve in 1.5, 2, 2.5, 3, 4, 6 and 8 in.
sizes, for horizontal installation for pressures not exceeding 250 psig (1730 kPa) as shown in the
manufacturer’s installation instructions.

FDV-PC0 – Pneu-Electric Actuated with Local reset, Pressure reducing Deluge Valve and FDV-PC1 –
Pneu-Electric Actuated with Remote Reset, Pressure reducing Deluge Valve in 1.5, 2, 2.5, 3, 4, 6 and 8
in. sizes, for horizontal installation for pressures not exceeding 250 psig (1730 kPa) as shown in the
manufacturer’s installation instructions.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 2 of 3
CERTIFICATE OF COMPLIANCE
Certificate Number 20160617-EX26941
Report Reference EX26941-20160616
Issue Date 2016-JUNE-17

FDV-PA0 – Hydraulic actuated with Pressure reducing Local Reset Deluge Valve & Anti-Columning
and FDV-PA1 – Hydraulic actuated with Pressure reducing Remote Reset Deluge Valve with Anti-
Columning in 1.5, 2, 2.5, 3, 4, 6 and 8 in. sizes, for horizontal installation for pressures not exceeding
250 psig (1730 kPa) as shown in the manufacturer’s installation instructions.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 3 of 3

You might also like