Ground Floor Hvac Power and Cable Tray Layout (Part 4 of 4)
Ground Floor Hvac Power and Cable Tray Layout (Part 4 of 4)
Ground Floor Hvac Power and Cable Tray Layout (Part 4 of 4)
MAKKAH
4 OF 4
DN
DN
KEYPLAN
NOTES
1. CABLE TRAYS SHALL BE MANUFACTURED AND INSTALLED IN ACCORDANCE WITH
NEMA VE 1 AND NEMA VE 2 RESPECTIVELY.
2. UNLESS OTHERWISE SPECIFIED, ALL CABLE TRAYS SHALL BE PERFORATED
TYPE WITHOUT COVER, MADE OF HOT - DIP GALVANIZED STEEL.
3. CABLE TRAY SHALL BE SUPPLIED IN STANDARD 3000mm AND 6000mm LENGHTS.
4. CABLE TRAY SHALL BE SUPPORTED ON STRAIGHT RUNS AT MAXIMUM SPAN OF
3000mm AND WITHIN 300mm FITTINGS.
5. VERTICAL CABLE TRAYS RUNS SHALL BE SUPPORTED 1500mm MAXIMUM.
11 12 13 14 15 16 17 18 19 20 6. ALL PANELBOARDS SHALL BE MOUNTED AT 1800mm ABOVE FINISHED FLOOR TO
THE TOP OF PANEL.
7. USE EMT CONDUITS FOR CONCEALED INDOOR INSTALLATION IN CEILING, RGS
CONDUITS FOR EXPOSED INSTALLATIONS AND PVC CONDUITS FOR EMBEDDED
INSTALLATIONS.
FOR MATCHLINE CONTINUATION SEE DRAWINGS NO. EE-242
8. MECHANICAL EQUIPMENT FEEDERS FROM PANELS TO DISCONNECTED
E E SWITCH SHALL INSIDE CONDUIT/CABLE TRAY.
9. ALL MECHANICAL EQUIPMENT CONTROLLERS SUCH AS AHU, SF, ACCU, VAVS,
PUMPS SEF,CHILLERS, EF, WILL BE PART OF VENDOR SUPPLY AND SHALL BE
INTEGRATED PART OF MECHANICAL EQUIPMENT.
CHEMICAL WAREHOUSE CABLE TRAY STRAIGHT RUN, WIDTH AND DEPTH AS SHOWN
0 5 10M
GROUND FLOOR HVAC POWER AND CABLE TRAY LAYOUT (PART 4 OF 4) GROUND FLOOR HVAC POWER AND CABLE TRAY
SCALE: 1 : 100 LAYOUT (PART 4 OF 4)
DESIGNED BY: AI
HEAD OFFICE:
DRAWN BY: AH PO Box 4549
7545 King Khalid Road, Al
CHECKED BY: SS Tahliyah,
Al Khobar 34716, Saudi Arabia
PROJ ENGR. : GAUTAM . T Tel.:+966 13 887 8838
Fahd Abdullah Alireza & Partenrs Engineering Consultants Co. Fax:+966 13 887 0574
DU SUPV : ﺷﺭﻛﺔ ﻓﻬﺩ ﻋﺑﺩﷲ ﻋﻠﻲ ﺭﺿﺎ ﻭﺷﺭﻛﺎﺅﻩ ﻟﻼﺳﺗﺷﺎﺭﺍﺕ ﺍﻟﻬﻧﺩﺳﻳﺔ www.FAEC.com
This Drawing and the design it covers are the property of the Royal DRAWING NO.
Commission for Jubail and Yanbu / Royal Commission at Jazan. These A/E APPROVAL : O. KHUSHAIM WBS NO :
drawings are loaned on the borrower's express agreement that they will R. C. APPROVAL: CONT. NO : JCPDI I-2031 2031-EE-A0-244
not be reproduced, copied, loaned, exhibited or used except in the limited
way, if any, permitted by written consent of the Royal Commission. DATE: DECEMBER 2022 SCALE: 1:100 REV. NO. 0
"A0" SIZE