Professional Documents
Culture Documents
BHEL - MAHAGENCO - Updated - R3 - 20-03-2024-5pm
BHEL - MAHAGENCO - Updated - R3 - 20-03-2024-5pm
CUSTOMER: MAHAGENCO
9 The UPS shall be 2X100% parallel As per the NIT, 6KVA with Page No : 41 & 42
redundant with 2 sets of battery 1 Hr for Local station and 3
shall be included. KVA with 6 hrs backup UPS
will be provided and
2X100% parallel redundant
with 2 sets of battery is not
required for the CAAQMS
application and we are
giving the assurance of the
UPS and batteries and we
accepted additional 2 years
warranty for the UPS.
10 Please ensure and confirm that Confirm & complied Page No : 33
analyser shelter shall be consider
as per spec clause ref no 3.0 (as per
the NIT)
11 3KVA UPS with 6 Hrs Backup : Incorporated as per the Page No : 42
As per the comments minimum 10 requirement
batteries of 12V/200 AH shall be
considered
12 Minimum 10 No’s of Batteries of Incorporated as per the Page No : 42
12V each shall be considered requirement.
13 Factor of 0.8 shall be conceded Incorporated as per the Page No : 134
instead of 0.7 requirement
14 As per IEEE Std.temperature Incorporated as per the Page No : 134
correction factor also considered in requirement
calculation
15 Earlier 100AH battery considered Incorporated as per the Page No : 134
for 85.68AH, Hence in the present requirement
case sae margin is to be considered
(minimum of 10% margin from
actual)
DATASHEETS FOR
1) CAAQMS ANALYZERS AND ASSOCIATED SYSTEMS (SO2, NOx, CO, CO2, O3, NH3, PM2.5,
PM10, BENZENE(BTEX) with all accessories
NOTE:
1. Two years’ warranty from the date of installation and commissioning, meeting the contract specification is in
the scopeof M/s Swan Technical Services Pvt Ltd.
2. All consumables and replaceable as required during warranty period will be provided by M/s Swan Technical
Services Pvt Ltd.
3. We M/s swan Technical Services Pvt Ltd confirms that offered CAAQMS system fully meets the
requirement of technical specification of contract and fully comply the CPCB present requirements and
guidelines. In case of any deviation w.r.t. technical specification or non-suitability to process requirement.
We will take full responsibility andcorrective action without any cost implication to customer.
INDEX
SNO DESCRIPTION
1 SULPHUR DIOXIDE (SO2) ANALYSER FOR CAAQMS
2 NITROGEN (NO-NO2-NOx) ANALYSER FOR CAAQMS
3 CO ANALYSER FOR CAAQMS
4 CO2 ANALYSER FOR CAAQMS
5 OZONE ANALYSER FOR CAAQMS
6 PM 2.5 ANALYSER FOR CAAQMS WITH INLET HEAD OF PM 2.5
7 PM 10 ANALYSER FOR CAAQMS WITH INLET HEAD OF PM 10
8 NH3 ANALYSER FOR CAAQMS
9 BENZENE ANALYSER FOR CAAQMS
10 DILUTION CALIBRATOR (MULTI GAS CALIBRATOR)
11 ZERO AIR GENERATOR
12 SAMPLE HANDLING SYSTEM & ACCESSORIES
13 CENTRAL DATA ACQUITISION SOFTWARE WITH PC & PRINTER
a SOFTWARE FOR CENTRAL SERVER
b CENTRAL SERVER COMPUTER
c CENTRAL SERVER PRINTER
14 LOCAL DATA ACQUITISION SOFTWARE WITH PC & PRINTER
a SOFTWARE FOR LOCAL STATION
b LOCAL STATION COMPUTER
c LOCAL STATION PRINTER
15 ANALYSER SHELTER FOR CAAQMS
16 METEOROLOGICAL MONITORING SYSTEM FOR CAAQMS
a WIND SPEED SENSOR
b WIND DIRECTION SENSOR
c AMBIENT TEMPERATURE SENSOR
d RELATIVE HUMIDITY SENSOR
e SOLAR RADIATION SENSOR
f RAIN GUAGE SENSOR
g METEOROLOGICAL MAST
17 UNINTERRUPTED POWER SUPPLY FOR CAAQMS & DAS
a 6KVA UPS FOR LOCAL STATIONS
b 3KVA UPS FOR CENTRAL SERVER
18 CALIBRATION GAS CYLINDERS
DESCRIPTION SPECIFICATION
Make Acoem Ecotech,
Model Serinus 50
Measurement Continuous Measurement of SO2 in Ambient Air
Technology Pulsed UV Fluorescent Radiation Technology
Range 0 - 20 ppm (auto ranging)
Concentration units mg/m3, μg/m3, ng/m3, ppm, ppb or ppt
Lower detectable limit < 0.3 ppb or 0.2 % of concentration whichever is greater
Response time 60 seconds to 95 %
Linearity < 1 % of full scale
Accuracy 0.5 ppb or 0.5 % of reading whichever is greater
Zero drift (24 Hours) 24 Hours: < 0.5 ppb
(At Lowest Range) Automatic Zero Compensation Available
Span drift (24 hours) 24 hours: < 0.5 % of reading or
(At Lowest Range) < 0.5 ppb whichever is greater
Sample flow rate 725 cc/min
Operating Temperature range 0 - 50 °C
Operating power 230 VAC, 50 - 60 Hz
Power consumption 255 VA (max at start-up) 180 VA (nominal)
Dimension (W) 429 x (H) 175 x (D) 638 mm
Mounting Rack Mounting
Weight: 18.1 kg
Approvals • US EPA approval (EQSA–0809–188)
• EN approval TÜV (936/21221977/B)
• EN approval MCERTS (MC100168/07)
Communication And Output Ports • #1 RS232 port (supports all protocols*)
Available • #2 RS232 port (supports all protocols* and multidrop)
• USB port (Advanced protocol only)
• Bluetooth (Advanced protocol only)
• TCP/IP network port (optional, supports all protocols*)
• *Avaliable protocols: Modbus (RTU/TCP), Bayern Hessen, EC9800 or
Advanced
Communication analog and digital • 3 x analog outputs (current or voltage), 12 bit resolution user definable
I/O port range (between two user specified points)
Current range: 0 - 20 mA, 2 - 20 mA or 4 - 20 mA Voltage range: 0 - 5 V, 0
- 10 V (voltage offset of 0 V, 0.25 V or 0.5 V)
• 3 x analog inputs (scalable), 0 - 5 V, 16 bit resolution
• 8 x logic level digital control inputs
Data logging 8 GB removable USB flash memory drive that scores the internal data
logger, event log, automatic/manual configuration backup,
automatic/manual parameter list save.
• Internal data logger (can log up to 12 of 200+ parameters)
• Logger interval (1 second to 24 hours)
• Storage capacity ~ 10 years (set to 1 minute interval)
Display LCD Type
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make Aceom Ecotech
Model Serinus 40
Measurement Continuous Measurement of NO, NO2, NOx in Ambient Air
Technology Chemiluminescence Technology
Range (NO, NO2, NOx) 0 to 20 ppm (auto ranging)
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make Aceom Ecotech
Model Serinus 30
Measurement Continuous Measurement of CO in Ambient Air
Technology NDIR gas filter correlation technology
Range 0 to 200 ppm (auto ranging)
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make Aceom Ecotech
Model Serinus 31
Measurement Continuous Measurement of CO2 in Ambient Air
Technology NDIR gas filter correlation technology
Range 0 to 3000 ppm (auto ranging)
Concentration units mg/m3, μg/m3, ng/m3, ppm, ppb or ppt
Lower detectable limit 0.5 PPM
Response time 60 seconds to 95 %
Linearity < 1 % of full scale
Accuracy 0.1 ppm or 0.1 % of reading whichever is greater
Zero drift (24 Hours) 24 hours: < 0.1 ppm for lowest range
(At Lowest Range)
Span drift (24 hours) 7 days: < 0.5 % of reading or 1 ppm whichever is greater
(At Lowest Range)
Sample flow rate 1000 cc/min
Operating Temperature range 0 - 50 °C
Operating power 100 - 240 VAC, 50 - 60 Hz (autoranging)
Power consumption 260 VA (max at start-up) 150 VA (nominal)
Dimension 429 x 175 x 638 mm
Mounting Rack Mounting
Weight: 21.3 kg
Communication And Output Ports • #1 RS232 port (supports all protocols*)
Available • #2 RS232 port (supports all protocols* and multidrop)
• USB port (Advanced protocol only)
• Bluetooth (Advanced protocol only)
• TCP/IP network port (optional, supports all protocols*).
*Avaliable protocols: Modbus (RTU/TCP), Bayern Hessen, EC9800 or
Advanced
Communication analog and digital I/O • 3 x analog outputs (current or voltage), 12 bit resolution user
port definable range (between two user specified points)
Current range: 0 - 20 mA, 2 - 20 mA or 4 - 20 mA
Voltage range: 0 - 5 V, 0 - 10 V (voltage offset of 0 V, 0.25 V or 0.5 V)
• 3 x analog inputs (scalable), 0 - 5 V, 16 bit resolution
Data logging 8 GB removable USB flash memory drive that stores the internal
data logger, event log, automatic/manual configuration backup and
automatic/manual parameter
list save.
• Internal data logger (can log up to 12 of 200+ parameters)
• Logger interval (1 second to 24 hours)
• Storage capacity ~ 10 years (set to 1 minute interval).
OPTIONS
Display LCD Type
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make Aceom Ecotech
Model Serinus 10
Measurement Continuous Measurement of O3 in Ambient Air
Technology Non-dispersive ultraviolet (UV) absorption technology(UV-Photometric)
Range 0 - 20 ppm (auto ranging)
Note:
M/s SWAN ensures that offered items are fully as per contract specification requirements.
* Ozone Gas can’t be stored in cylinders, must be generated at site. Therefore, no calibration
cylinder of ozone available in the market. Ozone Analyzers are calibrated through Ozone Gas
Generator, so gas cylinders not required.
Note:
1. M/s SWAN ensures that offered items are fully as per contract specification requirements.
Note:
1. M/s Swan ensures that offered items are fully as per contract specification requirements.
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make Airmotech (Chromatotec)
Model A73022
Measurement Continuous Measurement of Benzene in Ambient Air
Technology GC/PID
Range 0 to 325 μg/m3
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATIONS
Model AM-5800
Make STSPL
Source Gas Inputs 4 standard 100 - 200 kPa (g) (6 optional)
Dilution Mass Flow Controller 10 SLPM, 0 Deg, 1 ATM (std),
1 SLPM, 2 SLPM, 5 SLPM or 20 SLPM (optional), 2nd MFC (optional)
Flow Accuracy (Constant Temp) Within 1 % of full scale
Flow Repeatability Within 0.2 % of full scale
Linearity Within 0.5 % of full scale
Response Time < 15 seconds
Output Manifold 4 output ports standard
Mounting Rack Mounting
Operating Voltage 230 V VAC 50 / 60 Hz
Power Consumption • 165 VA maximum (typical at start-up) 95 VA after warm-up
Operating Conditions Ambient • 0 - 50°C
Temperature Range
User Interface • Via front panel keypad or computer
Flow Rate • Variable dependent on Dilution Mass Flow Controller installed
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make STSPL
Model No SZAG-09
Zero air flow 0 - 500 ml/min
Zero air pressure 6 kg/cm2
Moisture < 0.5 ppm
Purity O2 ~ 20-21% , N2 ~ 79.0 %
Air Scrubbers Air Clean-Up Canister removes:
NOx, NO, NO2, O3, SO2, H2S,
Less < 0.2 ppb
Hydrogen Nil
Power 220 VAC 50 Hz (115 VAC 60 Hz optional)
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
Dynamic Displays
⯃ Tabular: Displays current data for one or more stations.
⯃ Multi-Sites Textual & Chart dynamic displays
⯃ Last Received: Date/Time of last data and calibration received from each station.
⯃ Dashboards dynamic displays.
⯃ Dynamic GIS Map Viewer: Data display on GIS layer map or Google map.
Reports and Analysis
By using this feature, the user can produce, print and export textual and graphical reports.
⯃ Station Data Report –Standard tabular and graphical reports for Station values. Day, week,
month and user defined (periodic) report intervals are supported. Stored data values may be
averaged before being reported. Values reported may be filtered.
⯃ Multi-Station – Similar in function to the "Station Data Report,” only designed for more than one
station. Also supports multiple parameters.
⯃ Group - Report that reflects a user defined group of monitors related to one or more stations.
⯃ Histogram - The frequency of occurrence of various ranges of a monitor’s value.
⯃ XY Time Plot – Correlation between two parameters.
⯃ 2Y Time Plot - Two parameters plotted against time.
Note:
1) M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
PROCESSOR INTEL i7
RAM 8 GB
OS Window 13 (latest version)
OS License type & Duration LT Version (Duration: perpetual)
HARD DISK 1 TB SSD OR BETTER
NETWORKING ETHERNET LAN ENABLE
INPUT PORTS USB PORTS
MONITOR 17 INCH
OS WINDOWS 10 OR LATEST
KEYBOARD STANDARD KEYBOARD
MOUSE MOUSE + Mouse pad
Note:
1) M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
MAKE HP
MODEL Laser jet P1108 or equivalent
TYPE LASER PRINT
PRINT SIZE A4
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
Note:
1) M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
PROCESSOR INTEL i7
RAM 8 GB
OS Window 13 (latest version)
OS License type & Duration LT Version (Duration: perpetual)
HARD DISK 1 TB SSD OR BETTER
NETWORKING ETHERNET LAN ENABLE
INPUT PORTS USB PORTS
MONITOR 17 INCH
OS WINDOWS 10 OR LATEST
KEYBOARD STANDARD KEYBOARD
MOUSE MOUSE + Mouse pad
Note:
1) M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
MAKE HP
MODEL Laserjet P1108 or equivalent
TYPE LASER PRINT
PRINT SIZE A4
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATION
Make STSPL
Accessories As per tender technical specification
External Dimension 3000mm (L) X 3000mm (W) X 2500mm (H)
Inner Sheet Material GI
Outer Sheet Material SS
Thickness of Inner Sheet 1.2 mm
Floor Type Aluminium Chequered Plate
Insulation Thickness 100 mm
Door Entry Dimension 900 mm X 2000 mm
Partition Available for Cylinder storage and UPS Batteries installation
Internal Surface Finish Painted
Electrical wiring As per the CAAQMS requirement.
19” Rack with accessories Included
Note:
1. M/s SWAN ensures that offered items are fully as per contract specification requirements
2. Door dimensions are adequate considering dimension of analyser rack
a.WIND SPEED:
DESCRIPTION SPECIFICATIONS
Model Anemometer DWA 8600
Make Dynalab
Wind speed Sensor 3 Cup Anemometer.
Operating Temperature 0-50 deg C
Sensing 3 cup assembly mounted on friction free shaft and coupled to a
chopper.
Starting Threshold 0.3 meters/sec.
Range 0 to 65 meters/sec.
Distance constant 2.5 Meters
Output TTL pulses output proportional to wind speed Built in line driver to drive
long cable > 50 ohms loop resistance.
Accuracy Better than 0.5 m/s up to 10 m/s + 2% FSD
Diameter of cup 50 mm.
Diameter of cup assembly 165 mm.
Construction of sensor body Brass housing and stainless steel shaft
Principle Of Operation: Frequency is proportional to wind speed.
DYNALAB anemometer is a fast response, low threshold opto electronic
anemometer. When rotated by wind, a chopper on the anemometer
shaft interrupts an infra-red light source, generating pulses from a
photo transistor. The signal is amplified and fed through a line driver.
The frequency is proportional to wind speed. The anemometer is
provided with a 3 pin connector for easy replacement and comes with
10 meters of shielded cable.
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
b.WIND DIRECTION:
DESCRIPTION SPECIFICATIONS
Model Wind Vane DWD 8601
Make Dynalab
Wind Direction Sensor Wind Vane.
Sensing Vane coupled to linear endless potentiometer.
Starting threshold Better than 0.3 meters/sec.
Range 0 to 357 degrees (3 degrees electrical gap in the Potentiometer
Output 0 to 5 kilo ohm resistance ( 0 to 357 degrees).
Resolution 1 degree.
Accuracy +/ 3 degrees or better than 2% of the full scale.
Operating Temperature -40 to + 60 degree Celsius
Construction of sensor body Brass housing, stainless steel shaft and aluminium vane
Principle Of Operation: Potentiometric type sensor (Resistance proportional to wind
direction)
DWD 8601 wind vane is a counter balanced, low threshold wind vane.
A Linear, wire wound endless potentiometer is coupled to the vane by
an SS shaft. As the vane turns, it rotates a stainless steel shaft which is
coupled to the potentiometer. This potentiometer has excellent
linearity, very low starting torque.
The north of the wind vane is marked on its body. This line is to be
aligned with actual North with the help of prismatic compass, at the
time of installation. Sensor gives minimum resistance at North (i.e., 0
degree approximately 20 ohms ). The resistance output linearly
proportional to the position of the wind vane
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATIONS
Model Air Temperature DWT 8102
Make Dynalab
Sensing Standard Platinum RTD element(PT1000,or PT100 mounted inside a weather
shield
Range - 40 degrees to + 60 degrees Celsius.
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
DESCRIPTION SPECIFICATIONS
Model Net Radiometer DWR 8101
Introduction The DYNALAB Net Radiometer measures the difference between the
incoming and outgoing Solar radiation on a horizontal surface.
Spectral response 0.3 to 60 microns.
Range 0-1500 watt/m2
Sensitivity 40 uV/watt/sq.m.
Accuracy + 3.5%
Operating Temperature 0-50 deg C
Sensing element Two blackened surfaces with a thermopile in between
Wind shield Polyethylene domes.
Carrying arm Approx. 1 m long aluminium tube.
Sensor Two thin metallic films blackened with a special paint ( which has about 98 %
absorption in the entire range ) stuck on the top and bottom of a former about
1 cm thick constitute the sensor. A multi element copper constantan
thermocouple precisely measures the difference of temperature between the
top and bottom surfaces. This difference of temperature is a measure of the
net solar radiation.
The blackened surfaces are protected from rain and dust by very thin molded
polyethylene domes which transmit all
Solar radiation in the 0.3 to 60 micron spectral range . A container with a
desiccant is provided to keep the insides of the domes dry.
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements
g.METEOROLOGICAL MAST
DESCRIPTION SPECIFICATIONS
MAKE STSPL
TYPE TELESCOPIC
EXTENDED HEIGHT 10M
MATERIAL ALUMINIUM
ACCESSORIES Necessary Hanger and Holders along with electrical grounding set
shall be provided for installation of all the sensors.
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
a. 6KVA UPS:
DESCRIPTION SPECIFICATIONS
Model GXT MTX+ 6KVA or equivalent
Make VERTIV (Emerson)
CAPACITY 6000 VA
Phase 3 phase in / 1 phase out
INPUT CHARACTERISTIC
Nominal Voltage 230 VAC
Voltage Range 160 VAC-300 VAC ± 3% at 100% Load
Frequency Range 46~54 Hz or 56~64Hz
OUTPUT CHARACTERISTICS
Output Voltage 220/230/240VAC
AC Voltage Regulation ± 1%
(Batt. Mode)
Frequency Range 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
(Synchronized Range)
Harmonic Distortion ≤3 % @ 100% Linear Load : ≤7% @100% Non-Linear Load
BATTERY CHARACTERISTICS
Battery Type SMF
Battery Capacity 12V/42AH
Numbers 16
Charging Current (max.) Max.: 6A ± 10% (settable)
Charging Current Voltage 13.65 V ±1%
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input / Output voltage,
Discharge timer, and Fault conditions
PHYSICAL
Dimension, D X W X H (mm) 369x190x630
Net Weight (kgs) 75
ENVIRONMENT
Operation Humidity <95% and non-condensing
Noise Level Less than 65dBA @ 1 Meter
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
COPYRIGHT AND CONFIDENTIAL
THE INFORMATION ON THIS DOCUMENT IS THE PROPERTY OF MAHAGENCO, BHARAT HEAVY ELECTRICALS MITED AND SWAN
TECHNICAL SERVICES PVT LTD IN ALLIANCE. IT MUST NOT BE USED DIRECTLY OR NDIRECTLY IN ANY WAY DETRIMENTAL TO
THE INTEREST OF THE COMPANY
SWAN TECHNICAL SERVICES PVT LTD BHARAT HEAVY ELECTRICALS LIMITED MAHAGENCO
b.3 KVA UPS FOR CENTRAL SERVER: AC room controlled temperature is recommended as 25 Deg.C for UPS batteries.
DESCRIPTION SPECIFICATIONS
DESCRIPTION SPECIFICATIONS
Model GXT MTX+ 3KVA or equivalent
Make VERTIV (Emerson)
Phase 1 phase in / 1 phase out
CAPACITY 3000 VA
INPUT CHARACTERISTIC
Nominal Voltage 230 VAC
Voltage Range 160 VAC-300 VAC ± 3% at 100% Load
Frequency Range 46~54 Hz or 56~64Hz
OUTPUT CHARACTERISTICS
Output Voltage 220/230/240VAC
AC Voltage Regulation ± 1%
(Batt. Mode)
Frequency Range 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
(Synchronized Range)
Harmonic Distortion ≤3 % @ 100% Linear Load : ≤7% @100% Non-Linear Load
BATTERY CHARACTERISTICS
Battery Type SMF
Battery Capacity 12V/200AH
Numbers 10
Charging Current (max.) Max.: 6A ± 10% (settable)
Charging Current Voltage 13.65 V ±1%
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input / Output voltage,
Discharge timer, and Fault conditions
PHYSICAL
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
COPYRIGHT AND CONFIDENTIAL
THE INFORMATION ON THIS DOCUMENT IS THE PROPERTY OF MAHAGENCO, BHARAT HEAVY ELECTRICALS MITED AND SWAN
TECHNICAL SERVICES PVT LTD IN ALLIANCE. IT MUST NOT BE USED DIRECTLY OR NDIRECTLY IN ANY WAY DETRIMENTAL TO
THE INTEREST OF THE COMPANY
SWAN TECHNICAL SERVICES PVT LTD BHARAT HEAVY ELECTRICALS LIMITED MAHAGENCO
DESCRIPTION SPECIFICATIONS
Make CHEMTRON SCIENCE
Calibration Gas SO2 ,NO,CO,CO2,NH3,BTEX
Filling Pressure 10L /130Kg/ cm2
Preparation Tolerance PT/ 20, CA/ 3
Cylinder Material Aluminium
Capacity 10Ltr.Water Capacity
Regulator (LH/RH) Size LH For CO Gas & RH For NO, SO2
Stability Period 12 MONTHS
Method of Preparation Gravimetric
Analytical Method IR ANALYSER/ NIST TRACABILITY
Accuracy 3%
Cylinder Basis Outright
Concentration(Range) *SO2 45 ppm Balance N2
*NO 45 PPM Balance N2
*CO 500 ppm Balance N2
*CO2 3050 ppm Balance N2
*NH3 45 PPM Balance N2
*BENZENE-5PPM, M+P XYLENE-5PPM, ETHYL BENZENE-
Note:
1. M/s SWAN ensures that offered items are fully as per contract specification requirements.
2. Selected concentrations are suitable for the span calibration of the corresponding analyzer through Multi
Gas Dilution Calibrator.
DESCRIPTION SPECIFICATIONS
Make CHEMTRON SCIENCE
Gas N2
Filling Pressure 47L /140Kg/cm2
Preparation Tolerance PT/ 20, CA/ 3
Cylinder Material CS
Capacity 47 Ltr.Water Capacity
Regulator (LH/RH) Size RH
Stability Period 12 MONTHS
Method of Preparation Gravimetric
Analytical Method IR ANALYSER/ NIST TRACABILITY
Accuracy 3%
Cylinder Basis Outright
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
DESCRIPTION SPECIFICATIONS
Capacity 1.5 Ton
Energy Star Rating 3 Star
Compressor Inverter Compressor
Cooling Capacity 5100 W or Better
Power Features AC 230 V/50 Hz
Indoor noise level (dB) 29 - 60 db or Better
Power Consumption 1400 W or More Efficient
Gas R 32
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
DESCRIPTION SPECIFICATIONS
TYPE LED DISPLAY
NO. OF LINES MULTI LINES
SIZE 4 FEET(H) x 8 FEET (L)
VISIBILITY 80- 100M DURING DAY TIME
COLOUR MULTI
LANGUAGE ENGLISH
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
NOTES:
1. One-year warranty, meeting the contract specification is in the scope of M/s Swan.
2. All consumables and replaceable as required during warranty period will be provided by M/s Swan.
3. M/s. Swan will be responsible for installation, commissioning of the wireless communication system
and M/s Swan will also cover RF survey, system design, frequency liasoning, frequency license &
royalty charges for 1 year from the date of commissioning. M/s BHEL/MAHAGENCO has to provide
necessary documents from respective department for the issuance of license.
INDEX:
. No. Description
Technical Details / Datasheets for AAQMS Wireless System
BOM for AAQMS Wireless System
Note: M/s SWAN ensures that offered items are fully as per contract specification requirements.
1) Note:
2) All mounting arrangements for Antenna will be in M/s Swan scope.
3) At AAQMS stations Radio modem & SMPS shall be mounted on AAQMS PC desk. No separate cabinet is envisaged. At central station Radio & SMPS shall be mounted
inside IP 65 JB & JB shall be installed as per actual site condition.
4) Required Pole mast at all the stations with civil foundation, earthing shall be in M/s Swan Scope.
5) *Cable quantities & Self-supported Pole mast length mentioned are indicative only and M/s swan will supply all the accessories to complete the RF communication
system.
6) M/s SWAN ensures that offered items are fully as per contract specification requirement.
BILL OF MATERIALS –
MAIN SUPPLY
Central
SL No. Item Description Make Model Total Quantity Station 1 Station 2 Station 3
Server
1 Sulphur Dioxide (SO2) Analyser for CAAQMS ACEOM ECOTECH SERINUS 50 3 1 1 1 0
CHAIR
CUPBOARD
TABLE
Other Accessories as per NIT
15 ELECTRONIC DISPLAY BOARD FOR CAAQMS AT MAIN GATE STSPL 1 0 0 0 1
18 UNINTERRUPTED POWER SUPPLY FOR CAAQMS & LOCAL DAS VERTIV (Emerson) 3 1 1 1 0
Note:
M/s Swan will bear all the initial cost and bill for one year for telephone connections, M/s Swan will obtain necessary approval for licenses
authorizing the use of wireless communication equipment with specified frequencies.
M/s Swan will supply the wireless RF communication system as per the site requirement for successful as per contract specification requirements.
M/s Swan ensures that offered items are fully as per contract specification requirements.
All the Instruments will be fully calibrated and tested before supply.
M/s swan ensure that offered O & M contract for one year after commissioning of stations as per tender specifications.
Note
Replacement frequency of consumables also depends upon the local conditions and may change as per atmospheric conditions like dust, humidity etc.
Any other item not covered above but require for operation of AAQMS would be supplied as part of contract.
LIST OF DRAWINGS
S.NO TITLE DRAWING NUMBER
a Flow Schematic Diagram DWG-VA-20231212-SFD
b GA of Inside Shelter && Rack Arrangements DWG-VA-20231212-SHTLINSD
of Analyzers
c GA of Shelter DWG-VA-20231212-SHTLD
d Earth Pit of CAAQMS DWG-VA-20231212-EP
e CAAQMS Inter-Communication System DWG-VA-20231212-ICS
f Electrical Diagram of CAAQMS DWG-VA-20231212-ED
g Electrical Diagram of 6KVA UPS DWG-VA-20231212-UPS
c) GA of Shelter
415 V AC
450 mm height from Floor
2650
UPS Power
Y
Al. Windows - 2 nos.
3000
B
Tube Light 300 X 300 mm
N
G
PC Table
B
Battery Bank
4Nos 6A & 2 Nos. 16A Sockets
450 mm height from Floor
35 mm
PLAN
50 mm
3000 3000
100
100
80 mm
Suatable Stiffners
600
35 mm
1200
AIR QUALITY MONITORING STATION
533
600 40 x 80 Box
600 600 600 600
40
Steel Door
2700
900 x 2100mm
2100
3000
3000
500
534
50 x 100 Box 100
100 ISMB
533
100 75 mm
1200
600 510 600 510 600 6 mm thick Grouting Plate
welded to I-Beam
600
150 mm
3000
2X18 mm dia holes
50 mm
for M 16 J-Bolts
ELEVATION VIEW - A TOP FRAME PLAN BASE FRAME PLAN
Front side
TITLE:
Shelter 10' X 10' X 9'
SWAN TECHNICAL SERVICES PVT. LTD., BHARAT HEAVY ELECTRICALS LIMITED., DATE NAME
MADHAPUR, HYDERABAD HARIDWAR DRAWN 14.12.2023 D. J. N. CHARY
CHECKED 16.12.2023 D. J. N. CHARY
MATERIAL: VARIOUS APPROVED
PROJECT NAME:
SCALE: NTS SHEET: 1 OF 4 AMBIENT AIR QUALITY MONITORING STATIONS
ALL DIMENSIONS ARE IN MM
PROJECTION:
CUSTOMER: BHEL, HARIDWAR
SWAN TECHNICAL SERVICES PVT LTD BHARAT HEAVY ELECTRICALS LIMITED MAHAGENCO
Office of
Research and Development
These methods for measuring ambient concentrations of specified air pollutants have been designated as
"reference methods" or "equivalent methods" in accordance with Title 40, Part 53 of the Code of Federal
Regulations (40 CFR Part 53). Subject to any limitations (e.g., operating range or temperature range) specified in
the applicable designation, each method is acceptable for use in state or local air quality surveillance systems under
40 CFR Part 58 unless the applicable designation is subsequently canceled. Automated methods for pollutants other
than PM10 are acceptable for use only at shelter temperatures between 20°C and 30°C and line voltages between
105 and 125 volts unless wider limits are specified in the method description.
Prospective users of the methods listed should note (1) that each method must be used in strict accordance
with its associated operation or instruction manual and with applicable quality assurance procedures, and (2) that
modification of a method by its vendor or user may cause the pertinent designation to be inapplicable to the method
as modified. (See Section 2.8 of Appendix C, 40 CFR Part 58 for approval of modifications to any of these methods
by users.)
Further information concerning particular designations may be found in the Federal Register notice cited
for each method or by writing to the Center for Environmental Measurements and Modeling, Air Methods and
Characterization Division (MD-D205-03), U.S. Environmental Protection Agency, Research Triangle Park, North
Carolina 27711. Technical information concerning the methods should be obtained by contacting the source listed
for each method. Source addresses are listed at the end of the listing of methods, except for the addresses for lead
method sources, which are given with the method. New analyzers or PM10 samplers sold as reference or equivalent
methods must carry a label or sticker identifying them as designated methods. For analyzers or PM10 samplers sold
prior to the designation of a method with the same or similar model number, the model number does not necessarily
identify an analyzer or sampler as a designated method. Consult the manufacturer or seller to determine if a
previously sold analyzer or sampler can be considered a designated method or if it can be upgraded to designation
status. Analyzer users who experience operational or other difficulties with a designated analyzer or sampler and
are unable to resolve the problem directly with the instrument manufacturer may contact EPA (preferably in writing)
at the above address for assistance.
This list will be revised as necessary to reflect any new designations, modifications of existing designations,
or any cancellation of a designation currently in effect. The most current revision of the list will be available for
inspection at EPA's Regional Offices, and copies may be obtained at the Internet site identified above or by writing
to the Center for Environmental Measurements and Modeling at the address specified above.
SO2 List of Designated Reference and Equivalent Methods, December 15, 2023 Page 25
Ecotech or Acoem Australasia Serinus 50 Sulfur Dioxide Analyzer or Opsis AB OPS50 Sulfur Dioxide Analyzer or Teledyne
Analytical Instruments 6400E Sulfur Dioxide Analyzer or Tisch Environmental TE 2.0 Sulfur Dioxide Analyzer or Met
One Instruments GAS-1050 Sulfur Dioxide Analyzer or Met One Instruments GAS-1050-TL Sulfur Dioxide Analyzer
Automated Equivalent Method: EQSA-0809-188
“Ecotech or Acoem Australasia Serinus 50 Sulfur Dioxide Analyzer” or “Opsis AB OPS50 Sulfur Dioxide Analyzer” or
“Teledyne Analytical Instruments 6400E Sulfur Dioxide Analyzer” or “Tisch Environmental TE 2.0 Sulfur Dioxide
Analyzer,” operated in the range of 0–0.5 ppm, with a five-micron Teflon® filter element installed, with or without trace option
and with the following selected: Background-Enabled, Control Loop-Enabled, Diagnostic Mode-Operate, Pres/Temp/Flow
Compensation-Enabled, Span Compensation-Disabled, with concentration automatically corrected for temperature and
pressure changes, and operated according to the Serinus 50 Sulfur Dioxide Analyzer User Manual or the Opsis OPS50 Sulfur
Dioxide Analyzer User Manual or the Teledyne Analytical Instruments 6400E Sulfur Dioxide Analyzer Instruction Manual or
the Tisch Environmental TE 2.0 Sulfur Dioxide Analyzer Instruction Manual or Met One Instruments GAS-1050 Sulfur
Dioxide Analyzer Instruction Manual or Met One Instruments GAS-1050-TL Sulfur Dioxide Analyzer Instruction Manual, as
appropriate.
Federal Register: Vol. 74, page 38184, 07/31/2009
Latest Modifications: 05/2010, 05/2011, 05/2012, 8/2014, 12/2019, 11/2021; 07/2022
Ecotech or Acoem Australasia Serinus 40 Oxides of Nitrogen Analyzer or Ecotech or Acoem Australasia Serinus 44
NO/NO2/NOx/NH3 Analyzer or Opsis AB OPS40 Oxides of Nitrogen Analyzer or Teledyne Analytical Instruments 9110E
Oxides of Nitrogen Analyzer or Tisch Environmental TE 4.0 Oxides of Nitrogen Analyzer or Met One Instruments GAS-
1040 Oxides of Nitrogen Analyzer or Met One Instruments GAS-1044 Oxides of Nitrogen Analyzer or Met One Instruments
GAS-1040-TL Oxides of Nitrogen Analyzer
Automated Reference Method: RFNA-0809-186
“Ecotech or Acoem Australasia Serinus 40 Oxides of Nitrogen Analyzer” or “Ecotech or Acoem Australasia Serinus 44
NO/NO2/NOx/NH3 Analyzer” “Opsis AB OPS40 Oxides of Nitrogen Analyzer” or “Teledyne Analytical Instruments 9110E
Oxides of Nitrogen Analyzer” or “Tisch Environmental TE 4.0 Oxides of Nitrogen Analyzer,” operated in the range of 0–0.5
ppm, with a five-micron Teflon® filter element installed, with or without trace option, with either a molybdenum or a vitreous
carbon NO2 to NO catalyst, and with the following selected: Control Loop-Enabled, Diagnostic Mode-Operate, Pres/Temp/Flow
Compensation-Enabled, Span Compensation-Disabled, with concentration automatically corrected for temperature and pressure
changes, and operated according to the Serinus 40 Oxides of Nitrogen Analyzer User Manual or the Serinus 44 NO/NO2/NOX/NH3
Analyzer User Manual or the OPS40 Oxides of Nitrogen Analyzer User Manual or the Teledyne Analytical Instruments 9110E
Oxides of Nitrogen Analyzer Instruction Manual or Tisch Environmental TE 4.0 Oxides of Nitrogen Analyzer Instruction Manual
or Met One Instruments GAS-1040 Oxides of Nitrogen Analyzer Instruction Manual or Met One Instruments GAS-1044 Oxides
of Nitrogen Analyzer Instruction Manual or Met One Instruments GAS-1040-TL Oxides of Nitrogen Analyzer Instruction Manual
as appropriate.
Federal Register: Vol. 74, page 38184, 07/31/2009
Latest Modifications: 05/2010; 05/2011; 05/2012; 03/2013; 08/2014; 7/2017; 12/2019; 11/2021; 07/2022
Ecotech or Acoem Australasia Serinus 60 or Met One Instruments GAS-1060 NO2 CAPS (Cavity Attenuated Phase Shift)
Analyzer
Automated Reference Method: EQNA-0217-242
“Ecotech or Acoem Australasia Serinus 60 NO2 CAPS (Cavity Attenuated Phase Shift) Analyzer” operated at temperatures
between 20°C and 45°C, a line voltage between 80V and 260V, and with or without any of the following options: rack mounts,
internal pump, internal permeation device, high pressure calibration ports, Ethernet output. The following menu choices must
be selected: Control Loop - Enabled; Diagnostic Mode - Operate; Pres/Temp/Flow Compensation - Enabled; Span
Compensation – Disabled; and operated according to the Serinus 60 or Met One Instruments GAS-1060 User Manual.
Federal Register: Vol. 82, page 27816, 6/19/2017
Latest Modifications: 11/2021; 07/2022
Ecotech or Acoem Australasia Serinus 30 Carbon Monoxide Analyzer or Opsis AB OPS 30 Carbon Monoxide Analyzer or
Teledyne Analytical Instruments GFC7001E Carbon Monoxide Analyzer or Tisch Environmental TE 3.0 or Met One
Instruments GAS-1030 or Met One Instruments GAS-1030-TL Carbon Monoxide Analyzer
Automated Reference Method: RFCA-0509-174
“Ecotech or Acoem Australasia Serinus 30 Carbon Monoxide Analyzer” or “Opsis AB OPS30 Carbon Monoxide Analyzer”
or “Teledyne Analytical Instruments GFC7001E Carbon Monoxide Analyzer” or ”Tisch Environmental TE 3.0 Carbon
Monoxide Analyzer,” operated in the range of 0-50 ppm without the trace option, or 0-40 ppm range with the trace option
(Firmware 4.20 or later required for trace), with a five-micron Teflon® filter element installed, and with the following selected:
Background–Enabled, Control Loop–Enabled, Diagnostic Mode–Operate, Pres/Temp/Flow Compensation–Enabled, Span
Compensation–Disabled, with concentration automatically corrected for temperature and pressure changes, and operated
according to the Serinus 30 Carbon Monoxide Analyzer User Manual or the OPS 30 Carbon Monoxide Analyzer User Manual
or the Teledyne Analytical Instruments GFC7001E Carbon Monoxide Analyzer Instruction Manual, or the Tisch
Environmental TE 3.0, or the Met One Instruments GAS-1030 or Met One Instruments GAS-1030-TL Carbon Monoxide
Analyzer Instruction Manual as appropriate.
Federal Register: Vol. 74, page 26395, 06/02/2009
Latest Modifications: 05/2010; 05/2011; 05/2012; 08/2014; 11/2021, 07/2022, 08/2022
Ecotech or Acoem Australasia Serinus 10 Ozone Analyzer or Opsis AB OPS10 Ozone Analyzer or Tisch Environmental TE
1.0 or Met One Instruments Gas 1010 Ozone Analyzer
Automated Equivalent Method: EQOA-0809-187
“Ecotech or Acoem Australasia Serinus 10 Ozone Analyzer” or “Opsis AB OPS10 Ozone Analyzer” or “Tisch Environmental
TE 1.0 Ozone Analyzer,” operated in the range of 0–0.5 ppm, with a five-micron Teflon® filter element installed, and with the
following selected: Control Loop-Enabled, Diagnostic Mode-Operate, Pres/Temp/Flow Compensation-Enabled, Span
Compensation-Disabled, with concentration automatically corrected for temperature and pressure changes, and operated
according to the Serinus 10 Ozone Analyzer User Manual, or the Opsis AB OPS10 Ozone Analyzer User Manual, or the Tisch
Environmental TE 1.0 Ozone Analyzer Instruction Manual or the Met One Instruments GAS-1010 User Manual, as appropriate.
Federal Register: Vol. 74, page 38184, 07/31/2009
Latest Modifications: 05/2010; 05/2012; 8/2014; 11/2021, 07/2022
Met One Instruments, Inc. BAM-1020 Monitor – PM2.5 FEM Configuration, Horiba APDA-371– PM2.5 Configuration, or
Ecotech or Acoem Australasia Spirant BAM1100
Automated Equivalent Method: EQPM-0308-170
“Met One Instruments, Inc. BAM-1020 Beta Attenuation Mass Monitor – PM2.5 FEM Configuration, Horiba Instruments
APDA-371 Beta Attenuation Mass Monitor – PM2.5 FEM Configuration, or Ecotech or Acoem Australasia Spirant BAM1100”,
configured with the standard BX-802 EPA PM10 inlet (or alternative louvered PM10 inlet meeting 40 CFR 50 Appendix L
specifications) and with a BGI VSCC™ Very Sharp Cut Cyclone or Tisch TE-PM2.5C particle size separator, operated for 24
1-hour average measurements with firmware revision 3.2.4 or later, with or without an inlet tube extension (BX-823), with or
without external enclosures BX-902 or BX-903 and equipped with BX-596 ambient temperature and barometric pressure
combination sensor, or BX-597 ambient temperature, barometric pressure, relative humidity combination sensor, internal BX-
961 automatic flow controller operated in Actual (volumetric) flow control mode, the standard BX-802 EPA PM10 inlet head
and a BGI Very Sharp Cut Cyclone (VSCC™ -A) or Tisch TE-PM2.5C cyclone, BX-827 (110V) or BX-830 (230V) Smart Inlet
Heater, with the heater RH set to 35% and the temperature control set to "off", the 8470-1 revision D or later tape control
transport assembly with close geometry beta source configuration, used with standard glass fiber filter tape (460130 or 460180),
COUNT TIME parameter set for 8 minutes, the SAMPLE TIME parameter set for 42 minutes, BX-302 zero filter calibration
kit required and with or without BX-965 report processor board, or with or without BX-970 touch-screen display with USB
interface. Instrument must be operated in accordance with the BAM 1020 Particulate Monitor operation manual, revision F or
later, the Horiba APDA-371 Monitor operation manual or the Ecotech or Acoem Australasia Spirant BAM Manual (rev. A or
later), as appropriate, and the VSCC™ or Tisch TE-PM2.5C supplemental manual and may employ either the standard or
advanced leak test procedure. For instruments running firmware V9.0.0 or later, P/N BX-597A (digital temperature, pressure,
humidity) must be used.
Federal Register: Vol. 73, page 13224, 03/12/2008
Latest modifications: 7/2010; 8/2010; 8/2012; 3/2015; 9/2015; 4/2017; 12/2018; 08/2020; 11/2021
Met One Instruments, Inc. BAM-1020 Beta Attenuation Mass Monitor- PM2.5 FEM Configuration, or Ecotech or Acoem
Australasia Spirant BAM1100
Automated Equivalent Method: EQPM-0715-266
“Met One Instruments, Inc. BAM-1020 Beta Attenuation Mass Monitor – PM2.5 FEM Configuration or Ecotech or Acoem
Australasia Spirant BAM1100,” configured for 24 1-hour average measurements of PM2.5 by beta attenuation, using a glass
fiber filter tape roll (460130 or 460180) and a sample flow rate of 16.67 liters/min and with the standard EPA PM10 inlet
(meeting 40 CFR 50 Appendix L specifications) and with a URG-2000-30EGN PM2.5 (BX-809) cyclonic separator, BX-596
combo T/BP sensor or BX-597 combo T/BP/RH sensor, BX-827 (110V) or BX-830 (230 V) and with or without BX-965 report
processor board and with or without BX-970 touch screen display. Instrument must be operated in accordance with the BAM
1020 Particulate Monitor operation manual, revision L or later or with Ecotech or Acoem Australasia Spirant BAM1100
Operators Manual and may employ either the standard or advanced leak test procedure. Instrument must be operated with
firmware revision 3.2.4 or later. This PM2.5 equivalent method designation only applies to the BAM-1020 or BAM1100
configured with the URG-2000-30EGN cyclone. For instruments running firmware V9.0.0 or later, P/N BX-597A (digital
temperature, pressure, humidity) must be used.
Federal Register: Vol. 80, page 51802, 8/26/2015
Latest modification: 04/2017; 10/2018; 12/2018; 08/2020; 11/2021
Met One Instruments, Inc. BAM-1022 Real Time Beta Attenuation Mass Monitor-Outdoor PM2.5 FEM Configuration
Automated Equivalent Method: EQPM-1013-209
“Met One Instruments, Inc. BAM-1022 Beta Attenuation Mass Monitor – Outdoor PM2.5 FEM Configuration,” configured for
24 1-hour average measurements of PM2.5 by beta attenuation, using a glass fiber filter tape roll (460130 or 460180) and a
sample flow rate of 16.67 liters/min and with the standard (BX-802) EPA PM10 inlet (meeting 40 CFR 50 Appendix L
specifications) and with a BGI VSCC™ Very Sharp Cut Cyclone (BX-808) or Tisch TE-PM2.5C particle size separator, and
equipped with external enclosure BX-922 and BX-592 ambient temperature sensor or BX-596 ambient temperature/barometric
combination sensor or BX-597 ambient temperature/barometric pressure/relative humidity combination sensor. Instrument
must be operated in accordance with the BAM 1022 Particulate Monitor operation manual, revision B or later and may employ
either the standard or advanced leak test procedure. This designation applies to PM2.5 measurements only.
Federal Register: Vol. 78, page 67360, 11/12/2013
Latest modifications: 7/2014; 10/2015; 3/2016; 12/2018; 10/2019
PM10 List of Designated Reference and Equivalent Methods, December 15, 2023 Page 7
Met One or Sibata Models BAM/GBAM 1020, BAM/GBAM 1020-1, Horiba APDA-371, or Ecotech or Acoem Australasia
Spirant BAM1000
Automated Equivalent Method: EQPM-0798-122
“Met One Instruments or Sibata Scientific Technology Models BAM 1020, GBAM 1020, BAM 1020-1, GBAM 1020-1, Horiba
APDA-371 PM10 Beta Attenuation Monitor, or Ecotech or Acoem Australasia Spirant BAM1000 Spirant BAM1000” including
the BX-802 EPA PM10 inlet (or alternative louvered PM10 inlet meeting 40 CFR 50 Appendix L specifications), operated for
24-hour average measurements, with a filter change frequency of one hour, with glass fiber filter tape (460130 or 460180), and
with or without any of the following options: BX-823, tube extension; BX-825, heater kit; BX-826, 230 VAC heater kit; BX-
-828, roof tripod; BX-902,
exterior enclosure; BX-903, exterior enclosure with temperature control; BX-961, mass flow controller; BX-967, internal
calibration device, BX-965 Report Processor Board, BX-970 touch-screen display with USB interface. For software (firmware)
versions V3.0 or higher, a user-selectable measurement time (COUNT TIME) of 4, 6, 8 or 10 minutes selected, along with
appropriate sample time (BAM SAMPLE) setting of 50, 46, 42 or 38 minutes, respectively, to maintain a 60-minute
measurement cycle. For software (firmware) versions V3.5 or higher, user-selectable option to sample under actual conditions
(Flow Type: ACTUAL) and report under standard conditions (Reporting: STD), which requires the use of P/N BX-592 external
temperature sensor or P/N BX-596 external temperature/barometric pressure sensor, or BX-597 external
temperature/barometric pressure/relative humidity sensor. The user may also sample under standard conditions (Flow Type:
STD) and report under standard conditions (Reporting: STD) with any software/firmware 2.0 or higher. For instruments running
firmware V9.0.0 or later, P/N BX-598 (digital temperature) or P/N BX-597A (digital temperature, pressure, humidity) must be
used. Instrument must be operated in accordance with the appropriate instrument manual and may employ either the standard
or advanced leak test procedure.
Federal Register: Vol. 63, page 41253, 08/03/1998
Latest modifications: 06/2009; 07/2010; 8/2010; 8/2012; 4/2017; 12/2018; 08/2020; 11/2021
Met One Instruments, Inc. E-BAM PLUS Beta Attenuation Mass Monitor- PM10 FEM Configuration
Automated Equivalent Method: EQPM-1215-226
“Met One Instruments, Inc. E-BAM PLUS Beta Attenuation Mass Monitor – PM10 FEM Configuration,” configured for 24 1-
hour average measurements of PM10 by beta attenuation, using a glass fiber filter tape roll (460130 or 460180), a sample flow
rate of 16.67 liters/min, with the standard (BX-802) EPA PM10 inlet (meeting 40 CFR 50 Appendix L specifications) and
equipped with 9250 ambient temperature sensor or BX-597 T/BP/RH combination sensor. Instrument must be operated in
accordance with the E-BAM PLUS Particulate Monitor operation manual, revision 1 or later and may employ either the
standard or advanced leak test procedure. This designation applies to PM10 measurements only.
Federal Register: Vol. 81, page 4294, 01/26/2016
Latest modification: 04/2017; 12/2018
Manufactured by:
airmotec AG
(Chromatotec Group)
-Antoine
33240 Val de Virvée
France
Certification ranges:
Page 1 of 6
Form 1335
Issue 11
Certificate Contents
Approved Site Application........................................................................................................ 2
Basis of Certification ............................................................................................................... 2
Product Certified..................................................................................................................... 3
Certified Performance ............................................................................................................. 4
General Notes ........................................................................................................................ 6
Any potential user should ensure, in consultation with the manufacturer, that the monitoring system
is suitable for the intended application. For general guidance on monitoring techniques refer to the
Environment Agency Monitoring Technical Guidance Notes available at www.mcerts.net
The field trial was conducted on an urban background site for 3 months Marylebone Road in
Central London.
Test data for other VOCs can be found in the NPL test report listed below, contact Chromatotec
directly for details.
MCERTS Manufacturing Audit based on EN 15267-2 and ISO 9001 was conducted on 5th May
2018, Report number 70172875
Basis of Certification
This certification is based on the following test report(s) and on CSA Group
ongoing surveillance of the product and the manufacturing process (annual audit):
The tests has been performed by National Physical Laboratory (UKAS 002 accredited for Benzene
(EN 14662-3) and VOC in compliance with ISO 17025)
Page 2 of 6
Form 1335
Product Certified
The Chromatotec® GC 866 PID airToxic (Model A73022) benzene measuring system consists of
the following parts:
This certificate applies to all instruments fitted with software version Vistachrom 1.49 (serial number
20190309) onwards.
This certificate may only be reproduced in its entirety and without change
To authenticate the validity of this certificate please visit www.csagroupuk.org/mcerts
Page 3 of 6
Form 1335
Certified Performance
The instrument was evaluated for use under the following conditions:
Note: If the instrument is supplied with an enclosure then the ambient temperature shall be monitored inside
the enclosure to ensure that it stays within the above ambient temperature range.
Two identical instruments tested in parallel, the worst result is reported below:
Test Test result MCERTS
specification
Laboratory tests
Note 1: In the shelter during the three month field tests, another instrument emitted punctual N Butanol at
consistent concentrations that may have disturbed the zero air generator. The N Butanol emitted
was analysed in ambient air and did not interfere with the benzene measurement of the GC 866
PID airToxic.
This certificate may only be reproduced in its entirety and without change
To authenticate the validity of this certificate please visit www.csagroupuk.org/mcerts
Page 4 of 6
Form 1335
Description
Rack dimensions : 5 U monitor built as a 19" unit Width 483mm x Height 220mm 5U x Depth 660mm
(730mm with rear face connections)
Pneumatic Valve : 6 ports. High speed injection system (up to 350°C) with 'zero dead volume'
sample transfer to the column
Detector : Photo Ionisation Detector (PID), lamp 10.6 eV, electrometer and 0-1 V analogue output,
Self-cleaning lamp for high stability
Sampling system : Gas flow control unit (sample volume calculated) with one critical orifice, linked
to a sampling pump
Trapping system : Enrichment unit with a drum equipped with 1 adsorbent tube packed with
CARBOTRAP, trapping at ambient temperature, thermo desorption up to 350°C
Carrier gas : N2 cylinder or generator. One electronic pressure control and one valve for N2 as carrier
gas that gives consistent retention time.
Calibration : Internal or external calibration with permeation tubes or cylinder, in order to perform
auto-calibration of the instrument.The permeation tube is regulated in temperature and in flow.
Method: Calib, Measure and Blank available in a sequence. It is possible to start a Calibration by
clicking on a button or starting automatic method in the sequence
Power consumption : 150 VA and peak to 360 (24 VDC power supply is available in option XXX005)
Communication protocol : Modbus RTU, Gesytec 1 (Bayer Essen), Gesytec 2, others possible on
request
This certificate may only be reproduced in its entirety and without change
To authenticate the validity of this certificate please visit www.csagroupuk.org/mcerts
Page 5 of 6
Form 1335
General Notes
1. This certificate is based upon the equipment tested. The Manufacturer is responsible for
ensuring that on-going production complies with the standard(s) and performance criteria
defined in this certificate. The manufacturer is required to maintain an approved quality
management system controlling the manufacture of the certified product. Both the product
and the quality management system shall be subject to regular surveillance according to
CSA Group Testing UK Ltd
2. The design of the product certified is defined in the CSA Group design schedule V07 for
certificate No. CSA MC130230/07.
3. If a certified product is found not to comply, CSA Group should be notified immediately at the
address shown on this certificate.
4. The certification marks that can be applied to the product or used in publicity material are
CSA Group Testing UK Ltd Certificat
5. This document remains the property of CSA Group and shall be returned when requested by
CSA Group.
This certificate may only be reproduced in its entirety and without change
To authenticate the validity of this certificate please visit www.csagroupuk.org/mcerts
Page 6 of 6
Form 1335
e
Declaration
This is to certify that we M/s. Acoem (formerly known as Ecotech Pty Ltd & Metone Instruments),
a manufacturer of ambient air quality monitoring gas analysers/Instruments, have supplied
numerous CO2 (Carbon Dioxide) Analyzers and CO (Carbon Monoxide) analysers. Currently the
same upgraded analyser for measuring CO2 is known as Serinus 31 and CO is known as Serinus
30. The Serinus 31 carbon dioxide (CO2) is manufactured based on the Serinus 30 CO (Carbon
Monoxide) analyser and both use Non-Dispersive Infrared Spectrophotometry (NDIR) technology
to provide accurate, stable, and repeatable measurements of gaseous CO2 and CO of ambient air.
As per the USEPSA List of Designated Reference and Equivalent Methods, TUV and MCERTS, the
carbon dioxide (CO2) is not and we hereby inform you that CO2 is not listed for any other
manufacturer.
For M/s. Acoem (formerly known as Ecotech Pty Ltd & Metone Instruments)
Arun Nair
Manager Contracts & Commercial
Mobile +91 990 992 0384
E-mail: arun.nair@acoem.com
Manufacturer Authorization letter And
Confirmations from OEM towards PQR Points of Tender
Date: 06-06-2023
To, To,
Mr. Shashi Pal, Dy. Engineer(Project) Mr. Deshraj Yadav, Dy. Manager (PCRI-BOI)
Department of Heavy Industry Department of Heavy Industry
1x660MW Bhusawal Thermal Power Station 1x660MW Bhusawal Thermal Power Station
Unit 6, Unit 6
Bharat Heavy Electricals Limited(BHEL), Bharat Heavy Electricals Limited(BHEL),
MSPGCL, Bhusawal, HEEP, Haridwar, MSPGCL, Bhusawal, HEEP, Haridwar,
Dist Jalgaon, Dist Jalgaon,
Maharashtra-27, Pin-425307 Maharashtra-27, Pin-425307
Email ID: palsh@bhel.in
Tel : +91 1334 28 1941
Dear Sir s,
This is to certify that, we M/s. ACOEM Ecotech Industries Pvt. Ltd (owned subsidiary of Ecotech, Australia & Met One
Instruments, USA) part of ACOEM Group, France; official manufacturers of SO2, NO-NO2-NOx, NH3, O3, CO, CO2
Gas Analysers and PM10 and PM2.5 Particulate Monitor / Analyzers for Continuous Ambient Air Quality Monitoring
application, having its corporate head office located 200 chem. Des Ormeaux, 69760 Limonest, FRANCE, and in India
M/s. ACOEM operates through its Indian operations / 100% subsidiary company M/s. ACOEM Ecotech Industries Pvt
Ltd., having its registered office / factory at Plot no.57, Sector 2, Dist.: Dhar, Pithmapur 454775, Madhya Pradesh and
is responsible for conduct of its operations in India on behalf of ACOEM Group of Companies and its global subsidiaries.
Please note that globally ACOEM Group is represented through its brands namely Ecotech, MetOne, Dynoptic, 01dB,
Oneprod, Fixturlaser, Meax and Metravib.
This is further to confirm that we M/s. ACOEM Ecotech Industries Pvt Ltd.,hereby authorize our distributor M/s. Swan
Technical Services Pvt. Ltd, a subsidiary company of Swan Environmental Private Limited (SWAN) existing under the
laws of India with its principle place of business at Plot No: 922 &935, Swamy Ayyappa Co-Operative Society,
Madhapur, Hyderabad-500081 to submit the bid with our make of Analyzers Proposal Supply, Installation, Testing
and Commissioning of AAQMS Analyzers and Accessories of AAQMS Analyzers at Chief/Deputy Engineer(Project)
office, 1x660MW Bhusawal Thermal Power Station Unit 6, Bharat Heavy Electricals Limited(BHEL), MSPGCL,
Bhusawal, HEEP, Haridwar, Jalgaon Dist, Maharashtra- for 3 along with Guaranty / Warranty Three
as per tender requirement and to subsequently negotiate and sign the contract.
Acoem Ecotech Industries Pvt. Ltd. *Registered Office & Factory: Plot No.57, Pithampur, Sector 2, Dist. Dhar 454775
Madhya Pradesh * +91 72 9242 6400 * CIN : U29190M2013PTC031610 * info.in@acoem.com * acoem.com
No Company or firm or individual other than M/s. Swan Technical Services Pvt. Ltd. Hyderabad are authorized to bid,
and conclude the contract for the above goods manufactured by us against this specific tender enquiry, without a
written authorization letter from us.
M/s. Swan Technical Services Pvt. Ltd. Hyderabad has experienced engineers trained at our premises and is capable
to install and maintain our equipment. We hereby extend our full guarantee and warranty (03) three years for the
Goods and Services offered by the above firm on our behalf. We hereby Declare and confirm the availability of
spare parts and consumables for at least ten (10) years following the initial supply of the instruments from the date
of placement of order.
We shall be providing our techno-commercial support, warranty support, maintenance support and spares support
through M/s. Swan Technical Services Pvt. Ltd for our make of instruments in India for 1x660MW Bhusawal Thermal
Power Station Unit 6, Bharat Heavy Electricals Limited(BHEL), MSPGCL, Bhusawal, HEEP, Haridwar, Jalgaon-Dist
towards the above referred tender enquiry.
Yours Faithfully
For ACOEM Ecotech Industries Pvt. Ltd.,
Arun Nair,
Manager Contracts & Commercial
Mobile +91 990 992 0384
E-mail: arun.nair@acoem.com
Acoem Ecotech Industries Pvt. Ltd. *Registered Office & Factory: Plot No.57, Pithampur, Sector 2, Dist. Dhar 454775
Madhya Pradesh * +91 72 9242 6400 * CIN : U29190M2013PTC031610 * info.in@acoem.com * acoem.com
Manufacturer Authorization letter And
Confirmations from OEM towards PQR Points of Tender
Date: 06-06-2023
To, To,
Mr. Shashi Pal, Dy. Engineer(Project) Mr. Deshraj Yadav, Dy. Manager (PCRI-BOI)
Department of Heavy Industry Department of Heavy Industry
1x660MW Bhusawal Thermal Power Station 1x660MW Bhusawal Thermal Power Station
Unit 6, Unit 6
Bharat Heavy Electricals Limited(BHEL), Bharat Heavy Electricals Limited(BHEL),
MSPGCL, Bhusawal, HEEP, Haridwar, MSPGCL, Bhusawal, HEEP, Haridwar,
Dist Jalgaon, Dist Jalgaon,
Maharashtra-27, Pin-425307, India, Maharashtra-27, Pin-425307, India,
Email ID: palsh@bhel.in
Tel : +91 1334 28 1941
Sub: Manufacturer Authorization letter cum confirmation from OEM towards PQR Points for providing
Certificate for Guarantee & Warranty Services and supply of spare parts for the work
Installation, Testing and Commissioning of AAQMS Analyzers and Accessories of AAQMS Analyzers at
Chief/Deputy Engineer(Project) office, 1x660MW Bhusawal Thermal Power Station Unit 6, Bharat
Heavy Electricals Limited(BHEL), MSPGCL, Bhusawal, HEEP, Haridwar, Jalgaon Dist, Maharashtra-
for 3
Submission 13.06.2023.
Dear Sir s,
We, Airmotec Ag (a Group company of CHROMATOTEC Inc.), a manufacturer of BTEX Analysers duly
organized and existing under the laws of France with its principle office of business at 15 Rue d, Artigue
longue, 33240 Saint-Antoine-France hereby authorize our distributor M/s. Swan Technical Services Pvt. Ltd, A
subsidiary company of Swan Environmental Private Limited., 922 &935, Swami Ayyappa Co-operative Society,
Madhapur, Hyderabad-500081 to submit a bid the purpose of which is to provide the above Goods,
manufactured by us and to subsequently negotiate and sign the Contract.
No Company or firm or individual other than M/s. Swan Technical Services Pvt. Ltd. Hyderabad are
authorized to bid, and conclude the contract for the above goods manufactured by us against this specific
tender enquiry, without a written authorization letter from us.
M/s. Swan Technical Services Pvt. Ltd. Hyderabad has experienced engineers trained at our premises
and is capable to install and maintain our equipment. We hereby extend our full guarantee and warranty (03)
three years for the Goods and Services offered by the above firm on our behalf. We confirm the availability of
spare parts and consumables for at least ten (10) years following the initial supply of the instruments from the
date of placement of order.
Airmotec Ag (a Group company of CHROMATOTEC Inc.) hereby confirms that offering analyzers
models are upgraded / latest and meets all PQR points of tender. Our technical support to Swan Technical
Services Pvt. Ltd. Hyderabad, as and when required during Warranty and AMC for the equipment supplied by
us for this tender against.
Yours Sincerely,
Jean-Philippe AMIET
M.Sc. Sales and Customer Service Manager
AIRMOTEC AG S.A / CHROMATOTEC
27.CATALOGUES OF INSTRUMENTS
acoem.com
Approvals
• US EPA approval (EQSA-0809-188) • French approval LSCQA
Benefits
The Serinus® range of analysers have been designed • Latest firmware updates can easily be installed
using our experience & knowledge gained from using the USB flash memory drive
operating large air quality monitoring networks for
• Programming, viewing, downloading & emailing of
more than 45 years. The result, instruments that
data is made even simpler using optional Bluetooth
integrate seamlessly into continuous monitoring
connectivity combined with the Serinus Remote
networks.
Android App
• Reliable performance complemented with a two
• Built-in digital display measuring values & having
year warranty
function of measuring values transferred to
• Minimise time spent on site performing graphical trend display
maintenance through superior remote instrument
• Enhanced operator safety through the use of
control, diagnostic viewing & calibration
12 VDC internal voltages
• Comprehensive data logging & remote viewing of
• Reduced cost of spare parts, accessories &
over 200 operational parameters
consumable items through extensive use of
• Versatile interfacing through RS232, analog & standard components across the Serinus range
digital I/O & optional TCP/IP & Bluetooth
• Rack slide design makes accessing internal
• Easy setup through an intuitive menu system, components & removing the analyser from a rack
advanced GUI & a large alphanumeric keypad with cabinet easy
tactile keys
• AQMS power usage can be reduced due to the
• Instant status indication via illuminated instrument instrument’s low power demand & its ability to
status light buttons on the front panel operate over a wide temperature range.
acoem.com | 2
Specifications
Range: 0 - 20 ppm (autoranging)
Concentration units: mg/m3, μg/ m3, ng/m3, ppm, ppb or ppt
Noise: < 0.15 ppb
Lower detectable limit: < 0.3 ppb 0.2 % of concentration whichever is greater
Linearity: < 1 % of full scale
Precision: 0.5 ppb or 0.5 % of reading whichever is greater
Zero drift: 24 hours: < 0.5 ppb
7 days: < 0.5 ppb
Span drift: 24 hours: < 0.5 % of reading or < 0.5 ppb whichever is greater
Response time: 60 seconds to 95 %
STP reference: 0 °C, 20 °C, 25 °C at 101.3 kPa
Sample flow rate: 725 cc/min
Temperature range: 0 - 40 °C
Power: 100 - 240 VAC, 50 - 60 Hz (autoranging)
Power consumption: 255 VA (max at start-up)
180 VA (nominal)
Dimensions: 429 x 175 x 638 mm
Rack spacing: 3.5 RU
Weight: 18.1 kg
Measurement Cell
Reaction Cell
Hydrocarbon Kicker
Lamp Driver
acoem.com | 3
Communication Data logging
• #1 RS232 port (supports all protocols*) • 8 GB removable USB flash memory drive that
• #2 RS232 port (supports all protocols* & stores the internal data logger, event log,
multidrop) automatic/manual configuration backup &
• USB port (Advanced protocol only) automatic/manual parameter list save
• Bluetooth (Advanced protocol only) • Internal data logger (can log up to 12 of
• TCP/IP network port (optional, supports all 200+ parameters)
protocols*). • Logger interval (1 second to 24 hours)
• Storage capacity ~ 10 years
* Available protocols: Modbus (RTU/TCP), Bayern Hessen, EC9800 or Advanced
(set to 1 minute interval).
Specifications subject to change without notice. Images used are for illustrative purposes
only. All trademarks and registered trademarks are the property of their respective owners.
© 2023 Acoem and all related entities. All rights reserved. 20230220
acoem.com
Serinus 40 ®
Oxides of Nitrogen Analyser
acoem.com
Approvals
• US EPA approval (RFNA–0809–186) • French approval LSCQA
Benefits
The Serinus® range of analysers have been designed • Latest firmware updates can easily be installed
using our experience & knowledge gained from using the USB flash memory drive
operating large air quality monitoring networks for
• Programming, viewing, downloading & emailing of
more than 45 years. The result, instruments that
data is made even simpler using optional Bluetooth
integrate seamlessly into continuous monitoring
connectivity combined with the Serinus Remote
networks.
Android App
• Reliable performance complemented with a two
• Built-in digital display measuring values & having
year warranty
function of measuring values transferred to
• Minimise time spent on site performing graphical trend display
maintenance through superior remote instrument
• Enhanced operator safety through the use of
control, diagnostic viewing & calibration
12 VDC internal voltages
• Comprehensive data logging & remote viewing of
• Reduced cost of spare parts, accessories &
over 200 operational parameters
consumable items through extensive use of
• Versatile interfacing through RS232, analog & standard components across the Serinus range
digital I/O & optional TCP/IP & Bluetooth
• Rack slide design makes accessing internal
• Easy setup through an intuitive menu system, components & removing the analyser from a rack
advanced GUI & a large alphanumeric keypad with cabinet easy
tactile keys
• AQMS power usage can be reduced due to the
• Instant status indication via illuminated instrument instrument’s low power demand & its ability to
status light buttons on the front panel operate over a wide temperature range.
acoem.com | 2
Specifications
Range: 0 - 20 ppm (autoranging)
Concentration units: mg/m3, μg/ m3, ng/m3, ppm, ppb or ppt
Noise: < 0.2 ppb
Lower detectable limit: < 0.4 ppb
Linearity: ± 1 % of full scale
Precision: 0.4 ppb or 0.5 % of reading, whichever is greater
Zero drift: 24 hours: < 0.5 ppb,
7 days: < 0.5 ppb
Span drift: 7 days: < 1 % of reading or 0.5 ppb whichever is greater
Response time: 15 seconds to 95 %
STP reference: 0 °C, 20 °C, 25 °C at 101.3 kPa
Sample flow rate: 600 cc/min (total for 2 channels)
Temperature range: 0 - 40 °C
Power: 100 - 240 VAC, 50 - 60 Hz (autoranging)
Power consumption: 265 VA (max at start-up)
190 VA (nominal)
Dimensions: 429 x 175 x 638 mm
Rack Spacing: 3.5 RU
Weight: 21.9 kg
Measurement Cell
Reaction Cell
Delay Loop
Ozone Generator
Dryer
Auxiliary Valve Manifold
NO2 to NO Converter
acoem.com | 3
Communication Data logging
• #1 RS232 port (supports all protocols*) • 8 GB removable USB flash memory drive that
• #2 RS232 port (supports all protocols* & stores the internal data logger, event log,
multidrop) automatic/manual configuration backup &
• USB port (Advanced protocol only) automatic/manual parameter list save
• Bluetooth (Advanced protocol only) • Internal data logger (can log up to 12 of
• TCP/IP network port (optional, supports all 200+ parameters)
protocols*). • Logger interval (1 second to 24 hours)
• Storage capacity ~ 10 years (set to 1 minute
* Available protocols: Modbus (RTU/TCP), Bayern Hessen, EC9800 or Advanced
interval).
Specifications subject to change without notice. Images used are for illustrative purposes
only. All trademarks and registered trademarks are the property of their respective owners.
© 2022 Acoem and all related entities. All rights reserved. 20221214
acoem.com
Serinus 30 ®
Carbon Monoxide Analyser
acoem.com
Approvals
• US EPA approval (RFCA–0509–174) • French approval LSCQA
Benefits
The Serinus range of gas analysers have been • Programming, viewing, downloading & emailing of
designed using our experience and knowledge data is made even simpler using optional Bluetooth
gained from operating large air quality monitoring connectivity combined with Serinus Remote
networks for more than 40 years. The result, Android App
instruments that integrate seamlessly into
• Built-in digital display measuring values & having
continuous monitoring networks.
function of measuring values transferred to
• Reliable performance complemented with a two graphical trend display
year warranty
• Enhanced operator safety through the use of
• Minimise time spent on site performing 12 VDC internal voltages
maintenance through superior remote instrument
• Reduced cost of spare parts, accessories &
control, diagnostic viewing and calibration
consumable items through extensive use of
• Comprehensive data logging and remote viewing of standard components across the Serinus gas
over 200 operational parameters analyser range
• Versatile interfacing through RS232, USB, analog & • Rack slide design makes accessing internal
digital I/O & optional TCP/IP & Bluetooth components & removing the analyser from a rack
cabinet easy
• Easy setup through an intuitive menu system,
advanced GUI and a large alphanumeric keypad • AQMS power usage can be reduced due to the
with tactile keys instrument’s low power demand & its ability to
operate over a wide temperature range.
• Instant status indication via illuminated instrument
status light buttons on the front panel
acoem.com | 2
Specifications
Range: 0 to 200 ppm (autoranging)
Concentration units: mg/m3, μg/m3, ng/m3, ppm, ppb or ppt
Noise: < 0.02 ppm or 0.2 % of concentration reading whichever is greater
Lower detectable limit: < 0.04 ppm
Linearity: < 1 % of full scale (0 - 50 ppm)
Precision: 0.1 ppm or 0.1 % of reading whichever is greater
Zero drift: 24 hours: < 0.1 ppm
7 days: < 0.1 ppm
Span drift: 7 days: < 0.5 % of reading or 0.1 ppm whichever is greater
Response time: 60 seconds to 95 %
STP reference: 0 °C, 20 °C, 25 °C at 101.3 kPa
Sample flow rate: 1000 cc/min
Temperature range: 0 to 40 °C
Power: 100 - 240 VAC, 50 - 60 Hz (autoranging)
Power consumption: 260 VA (max at start-up)
150 VA (nominal)
Dimensions: 429 x 175 x 638 mm
Rack Spacing: 3.5 RU
Weight: 17.8 kg
DFU
CO-CO2 Converter
Detector Assembly
Measurement Cell
acoem.com | 3
Communication Data logging
• #1 RS232 port (supports all protocols*) • 8 GB removable USB flash memory drive that
• #2 RS232 port (supports all protocols* stores the internal data logger, event log,
and multidrop) automatic/manual configuration backup and
• USB port (Advanced protocol only) automatic/manual parameter list save
• Bluetooth (Advanced protocol only) • Internal data logger (can log up to 12 of 200+
• TCP/IP network port (optional, supports parameters)
all protocols*). • Logger interval (1 second to 24 hours)
• Storage capacity ~10 years (set to 1 minute
* Available protocols: Modbus (RTU/TCP), Bayern Hessen, EC9800 or Advanced
interval).
Specifications subject to change without notice. Images used are for illustrative purposes
only. All trademarks and registered trademarks are the property of their respective owners.
© 2022 Acoem and all related entities. All rights reserved. 20221005
acoem.com
Serinus® 31 B EN EF I T S
The Serinus range of analysers has been designed using our
Carbon Dioxide Analyser experience and knowledge gained from operating large air
quality monitoring networks for nearly 50 years. The result
is instruments that integrate seamlessly into continuous
monitoring networks.
DETECTOR ASSEMBLY
SOURCE TIMING ASSEMBLY
MEASUREMENT CELL
Specifications subject to change without notice. All images used are for illustrative purposes only.
All trademarks and registered trademarks are the property of their respective owners.
© 2022 Acoem and all related entities. All rights reserved. 20220730
Serinus 10 ®
Ozone Analyser
acoem.com
Approvals
• US EPA approval (EQOA-0809-187) • French approval LSCQA
Benefits
The Serinus range of analysers have been designed • Latest firmware updates can easily be installed
using our experience & knowledge gained from using the USB flash memory drive
operating large air quality monitoring networks for • Programming, viewing, downloading & emailing of
more than 45 years. The result, instruments that data is made even simpler using optional Bluetooth
integrate seamlessly into continuous monitoring connectivity combined with the Serinus Remote
networks. Android App
• Reliable performance complemented with a two • Built-in digital display measuring values & having
year warranty function of measuring values transferred to
• Minimise time spent on site performing graphical trend display
maintenance through superior remote instrument • Enhanced operator safety through the use of
control, diagnostic viewing & calibration 12 VDC internal voltages
• Comprehensive data logging & remote viewing of • Reduced cost of spare parts, accessories &
over 200 operational parameters consumable items through extensive use of
• Versatile interfacing through RS232, analog & standard components across the
digital I/O & optional TCP/IP & Bluetooth Serinus range
• Easy setup through an intuitive menu system, • Rack slide design makes accessing internal
advanced GUI & a large alphanumeric keypad with components & removing the analyser from a rack
tactile keys cabinet easy
• Instant status indication via illuminated instrument • AQMS power usage can be reduced due to the
status light buttons on the front panel instrument’s low power demand & its ability to
operate over a wide temperature range.
• Removable flash memory stores ~ 10 years of
data, including up to 12 individual parameters &
event logs. Operational parameters can also be
transferred to memory for easy retrieval
acoem.com | 2
Specifications
Range: 0 - 20 ppm (autoranging)
Concentration units: mg/m3, μg/m3, ng/m3, ppm, ppb or ppt
Noise: < 0.25 ppb
Lower detectable limit: < 0.5 ppb
Linearity: < 1 % of full scale
Precision: 0.5 ppb or 0.2 % of reading whichever is greater
Zero drift: 24 hours: < 0.3 ppb
7 days: < 0.3 ppb
Span drift: 7 days: < 0.5 % of reading or < 0.3 ppb whichever is greater
Response time: 30 seconds to 95 %
STP reference: 0 °C, 20 °C, 25 °C at 101.3 kPa
Sample flow rate: 500 cc/min
Temperature range: 0 - 40 °C
Power: 100 - 240 VAC, 50 - 60 Hz (autoranging)
Power consumption: 260 VA (max at start-up)
150 VA (nominal)
Dimensions: 429 x 175 x 638 mm
Rack spacing: 3.5 RU
Weight: 17.2 kg
Ozone Scrubber
Detector Assembly
Measurement Cell
Optical Bench
Lamp Driver
Measurement Lamp
acoem.com | 3
Communication Data logging
• #1 RS232 port (supports all protocols*) • 8 GB removable USB flash memory drive that
• #2 RS232 port (supports all protocols* & stores the internal data logger, event log,
multidrop) automatic/manual configuration backup &
• USB port (Advanced protocol only) automatic/manual parameter list save
• Bluetooth (Optional, Advanced protocol only) • Internal data logger (can log up to 12 of
• TCP/IP network port (optional, supports all 200+ parameters)
protocols*) • Logger interval (1 second to 24 hours)
• Storage capacity ~ 10 years
* Available protocols: Modbus (RTU/TCP), Bayern Hessen, EC9800 or Advanced
(set to 1 minute interval)
Specifications subject to change without notice. Images used are for illustrative purposes
only. All trademarks and registered trademarks are the property of their respective owners.
© 2023 Acoem and all related entities. All rights reserved. 20230728
acoem.com
Spirant TM
BAM
Particulate Monitor
acoem.com
Designations Operations
The Spirant™ BAM uses the beta ray attenuation
• Spirant™ BAM 1000
method to measure particulate concentration.
PM10: FEM (EQPM-0798-122) AS/NZS
3580.9.11:2008
Every hour, a small 14C (carbon - 14) element emits
• Spirant™ BAM 1100:
a constant source of high-energy electrons (known
PM2.5: Class III FEM, (EQPM-0308-170) AS/NZS
as beta rays) through a spot of clean filter tape.
3580.9.12:2013
These beta rays are detected and counted by a
sensitive scintillation detector to determine a zero
reading.
Features
The instrument automatically advances this spot of
• Long term unattended remote operation of up to
tape to the sample nozzle, where a vacuum pump
60 days between site visits
then pulls a measured and controlled amount of
• Concentration units: mg/m3, μg/m3 dust-laden air through the filter tape, loading it with
ambient dust.
• Automatic hourly span checks
acoem.com
Specifications
Accuracy: Exceeds US EPA Class III PM2.5 FEM standards
for additive and multiplicative bias
Measurement resolution: 0.1 μg/m3
Display Resolution: 1 μg/m3
Detection limit: (2σ) 1 hr: < 4.8 µg/m3
(3.6 μg/m3 typical)
(2σ) 24 hr: < 1.0 µg/m3
Range: 1 mg (1000 μg) default setting.
Settable from 0.1 mg to 10 mg
Optional ranges: Available on request
Measurement cycle time: 1 hour
Flow rate: 16.7 litres/minute adjustable 0 - 20 LPM range actual or standardised flow
Filter tape: Continuous glass fiber filter tape
Span check: Automatic 0.800 mg (typical)
span foil, verified hourly
Beta source: 14C (carbon - 14), 60 µCi ± 15 µCi
(< 2.22 x 106 Beq), half-life 5730 years
Beta detector type: Photomultiplier tube with organic plastic scintillator
Operating temperature: 0 to + 50 °C
Ambient temperature: - 40 to + 55 °C (BX - 596 AT sensor)
- 30 to + 50 °C (BX - 592)
Extended range of sensors available
Ambient humidity: 0 - 90 % RH, noncondensing
Sample humidity control: Active Smart Heater module, 10 - 99 % RH setpoint
Sampling Head: Dynamic Heated Sampling head measurement of PM2.5
with adjustable temperature 20-70 Deg C
Power supply: 100 - 230 VAC, 50/60 Hz.
Factory configured
Power consumption: 110 V: 262 W max with Medo pump and inlet heater running
(642 W with Gast pump)
230 V: 312 W max with Medo pump and inlet heater running
(717 W with Gast pump)
Dimensions: Weight: 310 x 430 x 400 mm
24.5 kg without external accessories
acoem.com
Communication Options
User interface RTPM
• Menu-driven interface, 8 line 40 character LCD • Real-time particulate monitor provides one minute
display & keypad measurements
Analog output Aurora™ Interface
• Isolated 0 - 1 VDC output standard • Enables interfacing of Spirant™ with Aurora™ 2000
• 0-1 V, 0 - 10 V,2-20 mA 4 - 20 mA, 0 - 16 mA switch Nephelometer for one minute measurements
selectable (requires Aurora™ 2000 Integrating Nephelometer)
Serial interface Sample inlets
• Multi Drop RS232 two-way serial port for PC or • PM10, PM2.5 & TSP available
modem communications
• USB Port/TCP/IP, Ethernet
Printer output
• Output only serial port for data or diagnostic
output to a PC or serial printer
Telemetry inputs
• Clock reset (voltage or contact closure), telemeter
fault (contact closure)
Alarm contact closures
• Data error, tape fault, flow error, power failure,
maintenance
Error reporting
• User-configurable available through serial port,
display, and relay outputs
Memory
• 4369 records (182 days at 1 record/hr)
Specifications subject to change without notice. Images used are for illustrative purposes
only. All trademarks and registered trademarks are the property of their respective owners.
© 2022 Acoem and all related entities. All rights reserved. 20230208
ACOEM Ecotech Industries Private Limited
Plot no 57, Sector II, Pithampur Industrial Area, Dhar, Madhya Pradesh, 454775. INDIA acoem.com
Serinus 44 ®
Ammonia Analyser
NO, NO2, NOx, NH3 Analyser
acoem.com
Approvals
• US EPA approval (RFNA–0809–186)
Benefits
The Serinus range of analysers have been designed • Removable flash memory stores ~10 years of
using our experience & knowledge gained from data, including up to 12 individual parameters &
operating large air quality monitoring networks for event logs. Operational parameters can also be
more than 45 years. The result, instruments that transferred to memory for easy retrieval
integrate seamlessly into continuous monitoring
networks. • Latest firmware updates can easily be installed
using the USB flash memory drive
• Guaranteed performance with a two year warranty
• Programming, viewing, downloading & emailing
• Minimise time spent on site performing
of data is made even simpler using Bluetooth
maintenance through superior remote instrument
connectivity combined with the Serinus Remote
control, diagnostic viewing & calibration
Android App
• Comprehensive data logging & remote viewing of
over 200 operational parameters • Enhanced operator safety through the use of
12 VDC internal voltages
• Versatile interfacing through RS232, analog &
digital I/O & optional TCP/IP & Bluetooth • Reduced cost of spare parts, accessories &
consumable items through extensive use of
• Easier setup through an intuitive menu system with
standard components across the Serinus range
“Quick Menu”, advanced GUI & a large keypad with
tactile keys • Rack slide design makes accessing internal
• Instant display of operational status using components & removing the analyser from
acoem.com | 2
Specifications
Range: 0 - 20 ppm (autoranging)
(analog ranges 0 - 50 ppb to 0 - 20 ppm)
(NH3 range dictated by external converter; usually ~2 ppm)
Concentration display: User selectable mg/m³, μg/m³, ppm, ppb or ppt
Noise: < 0.2 ppb
Lower detectable limit: < 0.4 ppb or 0.5 % of reading whichever is greater
Linearity: < 1 % of full scale
Precision: 0.4 ppb or 0.5 % of reading whichever is greater
Zero drift: 24 hours: < 0.4 ppb
7 days: < 0.4 ppb
Span drift: 7 days: < 1 % of reading or 0.4 ppb whichever is greater
STP reference: 0 °C, 20 °C, 25 °C at 101.3 kPa
Sample flow rate: 900 cc/min (total for 3 channels)
Temperature range: 0 - 40 °C
Power: 100 - 240 VAC, 50 - 60 Hz (autoranging)
Power consumption: 265 VA (max at start-up)
190 VA (after warm-up)
Dimensions: 429 x 175 x 638 mm
Rack spacing: 3.5 RU
Weight: 21.85 kg
acoem.com | 3
Communication Data logging
• USB port (digital communication) Removable USB flash memory that stores data in
• Bluetooth (digital communication via Android App) the following formats:
• TCP/IP Ethernet network connection (optional) • Instantaneous data from 1, 3, 5, 10, 30, or 60
• RS232 Port 1: Digital communication minute intervals
• RS232 Port 2: Multidrop port • Average data from 1, 3, 5, 10, 15, 30 minutes,
• Modbus RTU/TCP protocol, advanced 1, 4, 8, 12, or 24 hours
• 25 pin I/O port (analog outputs, analog inputs, • Data storage of 10 years of 12 parameters,
digital status inputs, digital status outputs). 1 minute data on 8 GB memory.
Specifications subject to change without notice. Images used are for illustrative purposes
only. All trademarks and registered trademarks are the property of their respective owners.
© 2022 Acoem and all related entities. All rights reserved. 20221216
acoem.com
TSP A73 / TSP A74 / TSP A76
Experts in gaz analysis
u ene
T ol Approved and installed by National US EPA*
z ene
lb en
Ethy
es
(m,p)
en
Xy l
Model A73022
s (o)
ene
Xyl Environment:
BTEX: 5 or 7 compounds
In non urban area 0.032 to 32.5 µg/m3 0-10 PPB
In urban area 0.32 to 325 µg/m3 0-100 PPB
In Fence line refinery 3.25 to 3250 µg/m3 = 0-1 PPM
e
xan
Indoor air
o h e Outdoor air
C ycl
BTEX + CALIB standard +(Styrene + cyclohexane)= A73022
BTEX (without calib) = A74022
BTEX + 1,3 -butadiene = A76022
Process:
Industrial Hygiene
Fence line
d i ene
ta
-
Option Purge & Trap (method 502-2) for water quality surveillance
3 bu A76022
1, Opti
:
on
WWW.CHROMATOTEC.COM
airTOXICBTX PID
a GC/PID for automatic monitoring of BTEX.
In air, water or soils
Technical specifications
Principle of the airTOXICPID BTEX analysis: up to 8 compounds
- Benzene
• This instrument uses a port valve with a single absorbent trap, and a
- Toluene
30 meter metallic 0.28 mm ID column.
- Ethylbenzene
• Minimum detection level as low as 10 ppt for Benzene or 1.3.Butadiene - Xylenes : Ortho, meta, para
(A76022) in ambient air. - Butadiene (model A76022)
- Cyclohexane
• Miniaturization, sensitivity, mobility and flexibility are its main features. - Styrene
Everything from the sample port up to the data storage is integrated in a Lower detection limit (LDL) in automatic mode :
19"-rack 5U.
≤ 0.01 ppb = 0.0325 µg/m3
Detection range and linearity: BENZENE
• Programmed gradient temperature up to 202°c for the column oven
and pressure/flow control of the carrier gas . 3.25 to 3250 µg/m3 = 0-1000 ppb
0.32 to 325 µg/m3 = 0-100 ppb
• Linearity on area with R2 > 0.995 0.032 to 32.5 µg/m3 =0-10 ppb
European range : 0,45 to 45 µg/m3 =0.1 to 14.5 ppb Relative standard variation : PRECISION
Better than 0.3 % over 48h (Retention Time)
• Before delivery the analyser is tested for one week by our Better than 2 % over 48 h on 1 ppb (Concentration)
quality control department. Results on LCD :
- Data storage
• Photo ionisation detector (PID), 10,6 eV lamp.
- 4 or 8 x 4-20 mA or 0/10 V output in option
• Self-cleaning of the lamp for high stability - MODBUS RTU / JBUS or Bayern Hessen protocol .
Cycle time:
• Bi-directionnal RS-232 C to transfer data and results to the internal 15 or 20 or 30 min
computer. Gas supply:
Nitrogen: 4 ml/min (inlet 3 bars; 1/8’’ swagelok)
• Vistachrom software enables the user to view and store data on a indus- Air or nitrogen for CALIB: 50 ml/min continuously
trial computer. It provides comfortable user friendly utilities to recalculate, and 180 ml/min in CALIB method
calibrate and export data and to configure the measurement.
Detector cleaning : 3 ml/min
15ml/min , Sample inlet (vacuum pump) ¼’’swagelok,
• The software allows the calculation of retention time, area, mass or
concentration profiles, in any measuring unit. Sample volume:
20 to 400 ml or more (programmable)
• CALIB standard in A73022 / Flow=50ml/min N2 or air Operation Temperature:
continuously and 180 ml/min for 6 minutes in calibration method (one per Room with air conditioning: 10 to 35°c
day) Computerized Electronic
CPU: Pentium III
• Valve for external gas cylinder calibration in A74022
4xUSB Connecting Port
• LCD DISPLAY
• Digital output: communication protocol. Two RS-232 ports
Display: 10’’ TFT Color LCD
Legally authorized software: Windows XP embeded
Theory Power supply:
- main 230V 50Hz or 115V 60 Hz
- battery 24V (option)
Photoionization is initiated by the absorption of short wavelength ultravio-
Electrical consumption:
let light by a molecule. This can lead to ionization as follows:
Average 150 VA, Peak 360 VA
R + hv => R+ + e-
Dimensions:
If the ionization potential of R is less than or equal to the energy of the Rack 482 mm (19")Height 222 mm (5U), depth 600 mm
photon, hv, then the species are ionized Weight:
The sensor consists of a sealed interchangeable ultraviolet lamp that emits a 18 kg =analyser ( 37 kg with packaging )
selected energy line.
Lamps with energies of 8.3, 9.5, 10.6 and 11.7 eV are available.
Part information : Model
PID is linear.
WWW.CHROMATOTEC.COM
AM-5800 Dynamic Dilution Calibrator
Overview
Based on microprocessor technology, the Dynamic Dilution Calibrator is developed for calibrating the gas analyzer and it
supports multi-path calibration. Equipped with high-accuracy mass flow controller and standard gas, this system can
provide calibration gas for zero point and span inspection of multiple gas components such as O 3 , NO, NO 2 , CO, SO 2 ,
Benzene, Toulene, Ethyl benzene, Xylene etc. Upto 4 gas sources can be provided.
Built-in programmable ozone generator is available optionally with the dynamic dilution calibrator. It can be used to calibrate
O 3 accurately and reliably. Also it can be used in GPT to produce NO 2 . Linear drive of multi-point section is adopted for ozone
generator to ensure the repeatability and accuracy of O 3 concentration; optional photometer can improve high-level of
accuracy control for ozone generator. Instrument is designed for fast response, high repeatability, high accuracy and ease of
operation. Using the ozone generator, quality control of lab & gas analyzer can be ensured.
Features
R Continuous self-checking with alarm function R High precise mass flow controller
R Bidirection RS232 port for remote control R Large dilution ratio and fast response
R Digital output working parameter R Quartz GPT chamber, multi interfaces for calibration gas
R USB and Ethernet interface R Ozone generator and ozone photometer are optional
R Colorful display and screen touch operation R Multi-functional operation by microprocessor
R Large memory and history data saved automatically R Task software is allowed to monitor test data in operation
Specifications
Item Parameter Specifications
Flow range of diluent gas (0~5) SLPM, (0~10) SLPM, (0~20) SLPM optional
Flow range of standard gas (0~50) sccm, (0~100)sccm, (0~200) sccmoptional
Accuracy of flow control ± 1%F.S.
Linearity ± 0.5%F.S.
Repeatability of flow control ± 0.2%F.S.
Ordering information :
Dynalab Wind Vane DWD 8601MX
B --- Brass epoxy coated body
A --- Aluminum epoxy coated body
S --- SS 316 body
AIR TEMPERATURE SENSOR MODEL -DWT 8102
Sensing : Standard Platinum RTD element PT1000,
mounted inside a weather shield
Range : - 40 degrees to + 60 degrees Celsius.
Resolution : 0.1 degrees Celsius.
Accuracy : + 0.2 degrees Celsius.
Output : Resistance
Weather Shield : ABS plastic molded Non Aspirated weather shield coated
with weather proof reflective white paint.
Size of body : 200(H) x 150 mm diameter(with weather shield).
Housing : Sensor mounted in a slotted tube on a Brass stem
Inside a weathershield. The sensor is supplied with
10 Meters shielded cable
Power requirement : 5V
PRINCIPLE OF OPERATION :
The sensor used for measurement is an RTD ( PT 1000). Here the resistance of the element varies with
temperature (increases with temperature), approximately 3.9 ohms/degree Celsius. The weather shield Is
provided to avoid direct heating of the sensor by sun’s radiation and to protect it from rain and snow.
Ordering Information :
Dynalab Temp Sensor with Shield DWT8102X
The case can be opened with one hand, and is protected against the
elements. Ethernet and a Grounding wire exits are provided on the bottom,
behind a protective door.
Comes with a mounting loop for tower/pole mounting, and a separate DIN
rail mount is also provided. Package also includes a PoE injector and power
supply unit.
NetBox
mANT30 series
mANT30 is a professional class 5 GHz 30dBi dish antenna, built to the highest industry
standards. Built to seamlessly accomodate our Basebox series products, but can be used for
any pole mounted wireless device due to the adequate length of the included FlexGuide cable.
Two antennas are available, with a standard type mount (MTAD-5G-30D3), and with a
precision alignment mount (MTAD-5G-30D3-PA). The antennas come packaged with all
necessary accessories and cables.
Electrical Specifications
Frequency Range 4.7-5.875 GHz Horizontal polarization
Gain 30 dBi typically
MTAD-5G-30D3 Polarization Dual (Vertical and Horizontal)
(With standard type mount) 3dB Beamwidth +/-2.5 deg
Standards Complies with EN 302 326 DN1, DN2, DN3, DN5
VSWR ≤ 1.4 typ, ≤ 1.8 max
Port to Port Isolation >40dB min
Front-to-Back Ratio >30 dB
Cross Polarization >40 dB
Power Rating 100 watts
Impedance 50 ohms
+/- 20 deg (MTAD-5G-30D3),
Elevation adjustment range
+/- 15 deg (MTAD-5G-30D-PA)
Physical/Environmental Specifications
Diameter x Depth 70 x 45cm (27.5 x 17.8in)
5.7kg (12.6 lbs) PA and 4.8kg (10.7 lbs)
Weight neto
standard version
Reflector Aluminum
Outdoor Rating ETSI EN 300 019-2-4
Wind Survivability 201kph (125mph)
Vertical polarization
Wind Load (125 mph) 181.4kg (400 lbs)
Operating Temperature -50°C to 80°C(-49°F to 158°F)
(MTAD-5G-30D3): 3 to 7cm (1.2 to 2.75in)
FlexGuide Pole Mount Diameter Range
(MTAD-5G-30D-PA): 3 to 10cm (1.2 to 3.9in)
Connector (2) RP-SMA Female (outside thread)
Packaged size 73x73x20cm (29x29x8in)
(MTAD-5G-30D3): 7.5 kg (16.5 lbs),
Packaged weight
(MTAD-5G-30D3-PA): 8.4 kg (18,5)
Can directly mount Basebox and other future
Compatible with RouterBOARD devices, or accept any pole-
mounted device
FlexGuide RPSMA RF Cables (RP-SMA-male
to RP-SMA-male) x 2pcs; Bracket for mounting
MTAD-5G-30D3-PA BASEBOX series radio; Self-Bonding Tape for
(With precision alignment mount) Package includes
insulating the RF cables x 2 slices; Precise
alignment mechanisms
(PA Version only)
Note: Basebox radio not included, available separately.
mANT30
13th MAR 2024,
Our Ref: SBA-JC/SEPL/UPS SALE-EMERSON-VERTIV/181/2023-24
To,
M/s. Swan Environmental Pvt Ltd,
Plot No: 922 & 935, SACS,
Madhapur, Hyderabad. TS.
BATTERY CALUCULATION
************************************************************************************
3KVA/200AH-10 BATTERIES AC room controlled temperature is recommended as 25 Deg.C for UPS batteries.
We hope above are in line with your requirements and please don’t hesitate to contact us for any
further clarifications pls feel free to contact on 9849750976, vsrishylam@sbatechnologies.co.in,
Note: Happy to Announce Our New Service Station Opened at Ayyappa Society,
Madhapur, Hyd.
Raju
Support In Sales
Mobile No: 7680099302