PROTECTION SERVICE UNIT

NETWORK PROTECTION DIVISION - MINDANAO SYSTEM OPERATIONS


NR LINE DIFFERENTIAL RELAY SETTING SHEET PAGE 1 OF 5
===================================================================================================
LOCATION : AGUS6 SUBSTATION CNTL NO. : 7LI1AG6-BLO-M1(87L)-NRPCS931S-REV0
EQUIPMENT : BALOI 138KV LINE 1 DATE : FEBRUARY 7, 2024
BREAKER NO. : 7-04CB04/24AG6 SUPERSEDES :-
RELAY TYPE : NR PCS931S - MAIN 1 CT RATIO : 2000:5
DEVICE NO. : 87L/21L/67 I_RATED : 680A Primary per TL Unification
==================================================================================================
LINE DIFFERENTIAL RELAY SETTING SHEET
STATION : AGUS6 CIRCUIT : BALOI 138kV LINE 1 PAGE 2 OF 5
f
k
V
I
I
I
f
f

f
f

X1L = 0.63
R1L = 0.11
X0L = 2.02
R0L = 0.47
X0M = 1.24
R0M = 0.35
Ll = 4
phi1 = 80
Re_K0 = 0.74
Im_K0 = -0.05

I_DPFC = 0.43 I_FD = 173


I_ROC = 0.58

Z0_Comp = 0.74
Z2_Comp = 0.74

I_Bias = 0.51 Ibias = 204


I_CTS = 2.55
CT_corr = 1

XC1 = 31126
XC0 = 43822
Z_LReac = 212
Z_LGReac = 40
Z_RReac = 212
Z_RGReac = 40
LINE DIFFERENTIAL RELAY SETTING SHEET
STATION : AGUS6 CIRCUIT : BALOI 138kV LINE 1 PAGE 3 OF 5

Z_DPFC = 0.45
En_Z_DPFC = “0 : Disabled”

R_blinder = 14.6

Z_PG1 = 0.48
R1_PE = 2.07
T1 = 0.0

T1 = 0.0
Z_PP1 = 0.55
R1_PP = 1.78

Z_PG2 = 1.44
R2_PE = 5.04
T2E = 0.5
T2E = 0.5

Z_PP2 = 1.44
R2_PP = 3.96
T2P = 0.5
T2P = 0.5

Z_PG3 = 4.97
R3_PE = 14.6
T3E = 1.2

Z_PP3 = 4.97
R3_PP = 11.48
T3P = 1.2

Re_K0 = 0.74
Im_K0 = -0.05
phi1 = 80
Z_PG2 = 1.44
R2_PE = 5.04

I_PSBR = 1.87
LINE DIFFERENTIAL RELAY SETTING SHEET
STATION : AGUS6 CIRCUIT : BALOI 138kV LINE 1 PAGE 4 OF 5

I_SOTF = 19.1

I_51P = 2.55 Ip = 1020


t_VTS = 0.8

TMSp_ = 0.27

I_51G = 0.51 Ig = 204


t_VTS = 0.8

TMSg_ = 0.53
LINE DIFFERENTIAL RELAY SETTING SHEET
STATION : AGUS6 CIRCUIT : BALOI 138kV LINE 1 PAGE 5 OF 5
===================================================================================================
REMARKS: NEW SETTINGS. TRANSFERED AG6-BLO L1 TO BAY-04 CB04 FROM BAY-02 CB08. (MSUP)

- ALL RELAY FEATURE NOT MENTIONED IS SET TO DISABLED/WITHOUT.


- ALL BINARY INPUTS/OUTPUTS, ALARMS & LEDS ARE TO BE CONFIGURED BY THE FIELD COMMISSIONING ENGR.
- PLEASE UPLOAD TO PROJECT SENTINEL OF ALL SETTINGS WITH TEST RESULTS AFTER IMPLEMENTATION.
- *** TO BE DETERMINED BY THE FIELD COMMISSIONING ENGINEER.

PREPARED BY: REVIEWED BY: APPROVED BY:

J.S. MAG-ABO A.A. EDURIA R.B. BAGUNDOL


NETWORK PROTECTION PR. ENGR. NETWORK PROTECTION SUPV. NETWORK PROT. MANAGER

IMPLEMENTED BY: DATE IMPLEMENTED: ____________

____________________________ I.R.D. PANERIO H.B.Y. MANREZA


DEV. MAINTENANCE PRIN. ENGR. OIC-SYST. & DEV. MAINT. MANAGER MAINT. & TESTING MANAGER