Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

A brand of the

5-35kV 1/C EPR MV-105 EASY GLIDER™ (Tape Shield)


Medium Voltage Commercial & Industrial Cables

Description Design Parameters


Prysmian's Easy Glider cable is designed to facilitate
TM CONDUCTOR: Class B compact concentric strand
conduit installation without the application of pulling aluminum alloy 1350 or compact concentric soft drawn
lubricant. Single conductor cable with stranded copper annealed copper per ASTM.
or aluminum conductor, triple extruded insulation system CONDUCTOR SHIELD: Extruded thermosetting
consisting of a thermosetting semiconducting conductor semiconducting shield which is free stripping
shield, high dielectric strength EPROTENAXTM EPR insulation, from the conductor and bonded to the insulation.
thermosetting semiconducting insulation shield, helically INSULATION: Natural high dielectric strength
applied bare copper tape shield, and black low coefficient EPROTENAX™ EPR-based insulation, combined
of friction, PVC jacket. with other materials and agents that enhance
the electrical and mechanical characteristics
Specifications Ratings assuring extended cable life.
AEIC- AEIC CS8 INSULATION SHIELD: Extruded thermosetting
ICEA- ICEA S-93-639 semiconducting shield with controlled adhesion
ICEA- ICEA S-97-682 to the insulation providing the required balance
UL- UL-1072 Type MV-105 between electrical integrity and ease of stripping.
Sunlight Resistant METALLIC SHIELD: Helically applied non-magnetic
For CT USE ( 1/0 AWG & Larger) copper tape(s) over the insulation shield with a
ICEE- IEEE 383 Flame Test (1/0 AWG and Larger) nominal overlap of 25%.
ICEE- IEEE 1202 Flame Test (250 MCM and Larger)
JACKET: Black, sunlight resistant, low coefficient
For 105°C continuous, 140°C emergency, of friction, polyvinyl chloride (PVC) jacket tightly
250°C short-circuit operation. applied over the copper tape.

Options Installation
- Strandseal®
- Compressed or compact stranded conductors Conduit in Air Direct Buried
- Colored Jackets
- LLDPE*, CPE or LSOH Jacket Underground Duct Isolated in Air
- Oil Resistant jacket
- Standard PVC jacket With Messenger Wet Locations
- Multiplex cables
- CSA C68.10 (FT4 250 MCM and larger)
B130_MV105_Easy_Glider_2017-10-03

Dry Locations Industrial


- -40°C Cold Impact and Cold Bend
In Cable Tray
*UL does not recognize LLDPE as MV-105

Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 1
A brand of the

25kV 1/C EPR MV-105 EASY GLIDER™(Tape Shield)


100/133% Medium Voltage Commercial & Industrial Cables

Insulation Minimum
Insulation Conductor Insulation Jacket Cable
Shield Bending † Ampacity
Product Number Conductor Thickness Diameter Diameter Diameter Weight
Diameter Radius (Amps)
(mils) (in) (in) (in) (lbs/kft)
(in) (in)
(A) (B) (C) (D) ‡105°C In Duct ‡105°C In Air
25kV 100% Copper One Conductor
TBD 1 AWG CU 260 0.299 0.85 0.90 1.07 760 13 185 250
TBD 1/0 AWG CU 260 0.341 0.89 0.95 1.11 857 14 215 290
TBD 2/0 AWG CU 260 0.376 0.92 0.98 1.14 967 14 245 330
TBD 3/0 AWG CU 260 0.423 0.97 1.03 1.19 1106 15 275 380
TBD 4/0 AWG CU 260 0.479 1.03 1.08 1.25 1277 15 315 445
TBD 250 MCM CU 260 0.522 1.08 1.13 1.30 1432 16 345 490
TBD 350 MCM CU 260 0.622 1.18 1.23 1.40 1809 17 415 605
TBD 500 MCM CU 260 0.742 1.30 1.35 1.52 2353 19 500 755
TBD 750 MCM CU 260 0.917 1.48 1.54 1.76 3379 22 610 970
TBD 1000 MCM CU 260 1.071 1.64 1.69 1.91 4242 23 690 1160
25kV 133% Copper One Conductor
TBD 1 AWG CU 320 0.299 0.98 1.04 1.20 894 15 245 330
TBD 1/0 AWG CU 320 0.341 1.03 1.08 1.24 994 15 215 290
TBD 2/0 AWG CU 320 0.376 1.06 1.12 1.28 1109 16 245 330
TBD 3/0 AWG CU 320 0.423 1.11 1.16 1.33 1254 16 275 380
TBD 4/0 AWG CU 320 0.479 1.16 1.22 1.38 1430 17 315 445
TBD 250 MCM CU 320 0.522 1.21 1.27 1.43 1591 18 345 490
TBD 350 MCM CU 320 0.622 1.31 1.37 1.53 1979 19 415 605
TBD 500 MCM CU 320 0.742 1.43 1.49 1.65 2535 20 500 755
TBD 750 MCM CU 320 0.917 1.62 1.67 1.90 3588 23 610 970
TBD 1000 MCM CU 320 1.071 1.77 1.83 2.05 4468 25 690 1160

†Ampacities are based on the following:


PRODUCT NOTES: Three Phase Operation
The above dimensions are approximate and In Duct per 2017 NEC Table 310.60(C)(77): Three single conductor cables in plastic ‡EPROTENAX™ EPR-insulated cables are capable
subject to normal manufacturing tolerances. duct, direct-buried, 105°C conductor temperature, 20°C ambient temperature, earth of operating at 105°C. However, the maximum
RHO of 90°C-cm/Watt, and 100% load factor, and shields short-circuited. operating temperature of the cable should be
Isolated in Air per 2017 NEC Table 310.60(C)(69): Insulated single conductor isolated based on the maximum operating temperature
in air, 105°C conductor temperature, and 40°C ambient temperature, and shields of the cable accessories to be used.
grounded at one point only.
In Cable Tray per 2017 NEC 392.80(B)(2)(b): Single conductor cables, sizes 1/0 AWG
and larger, installed in a single layer in an uncovered table tray, with a maintained
space of not less than one cable diameter between individual conductors, the
ampacities shall not exceed the allowable ampacities stated in 2017 NEC Table
310.60(C)(69) (Copper), “Isolated in Air” values noted above.
B130_MV105_Easy_Glider_2017-10-03

Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 8
A brand of the

25kV 1/C EPR MV-105 EASY GLIDER™(Tape Shield)


100/133% Medium Voltage Commercial & Industrial Cables

Insulation Minimum
Insulation Conductor Insulation Jacket Cable
Shield Bending † Ampacity
Product Number Conductor Thickness Diameter Diameter Diameter Weight
Diameter Radius (Amps)
(mils) (in) (in) (in) (lbs/kft)
(in) (in)
(A) (B) (C) (D) ‡105°C In Duct ‡105°C In Air
25kV 100% Aluminum One Conductor
TBD 1 AWG AL 260 0.299 0.84 0.90 1.07 584 13 145 195
TBD 1/0 AWG AL 260 0.336 0.88 0.94 1.10 632 14 165 225
TBD 2/0 AWG AL 260 0.379 0.93 0.98 1.15 687 14 190 260
TBD 3/0 AWG AL 260 0.423 0.97 1.03 1.19 754 15 215 300
TBD 4/0 AWG AL 260 0.479 1.03 1.08 1.25 834 15 245 345
TBD 250 MCM AL 260 0.522 1.08 1.13 1.30 910 16 270 380
TBD 350 MCM AL 260 0.622 1.18 1.23 1.40 1074 17 330 475
TBD 500 MCM AL 260 0.742 1.30 1.35 1.52 1304 19 400 590
TBD 750 MCM AL 260 0.917 1.48 1.54 1.76 1773 23 490 765
TBD 1000 MCM AL 260 1.071 1.64 1.69 1.91 2138 24 565 920
25kV 133% Aluminum One Conductor
TBD 1 AWG AL 320 0.299 0.98 1.04 1.20 719 15 145 225
TBD 1/0 AWG AL 320 0.336 1.20 1.08 1.24 770 15 165 225
TBD 2/0 AWG AL 320 0.379 1.06 1.12 1.28 830 16 190 260
TBD 3/0 AWG AL 320 0.423 1.11 1.16 1.33 901 16 215 300
TBD 4/0 AWG AL 320 0.479 1.16 1.22 1.38 987 17 245 345
TBD 250 MCM AL 320 0.522 1.21 1.27 1.43 1069 18 270 380
TBD 350 MCM AL 320 0.622 1.31 1.37 1.53 1243 19 330 475
TBD 500 MCM AL 320 0.742 1.43 1.49 1.65 1486 20 400 590
TBD 750 MCM AL 320 0.917 1.62 1.67 1.90 1983 23 490 765
TBD 1000 MCM AL 320 1.071 1.77 1.83 2.05 2364 25 565 920

†Ampacities are based on the following:


PRODUCT NOTES: Three Phase Operation
The above dimensions are approximate and In Duct per 2017 NEC Table 310.60(C)(78): Three single conductor cables in plastic ‡EPROTENAX™ EPR-insulated cables are capable
subject to normal manufacturing tolerances. duct, direct-buried, 105°C conductor temperature, 20°C ambient temperature, earth of operating at 105°C. However, the maximum
RHO of 90°C-cm/Watt, and 100% load factor, and shields short-circuited. operating temperature of the cable should be
Isolated in Air per 2017 NEC Table 310.60(C)(70): Insulated single conductor isolated based on the maximum operating temperature
in air, 105°C conductor temperature, and 40°C ambient temperature, and shields of the cable accessories to be used.
grounded at one point only.
In Cable Tray per 2017 NEC 392.80(B)(2)(b): Single conductor cables, sizes 1/0 AWG
and larger, installed in a single layer in an uncovered table tray, with a maintained
space of not less than one cable diameter between individual conductors, the
ampacities shall not exceed the allowable ampacities stated in 2017 NEC Table
310.60(C)(70) (Aluminum), “Isolated in Air” values noted above.
B130_MV105_Easy_Glider_2017-10-03

Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 9
A brand of the

35kV 1/C EPR MV-105 EASY GLIDER™(Tape Shield)


100/133% Medium Voltage Commercial & Industrial Cables

Insulation Minimum
Insulation Conductor Insulation Jacket Cable
Shield Bending † Ampacity
Product Number Conductor Thickness Diameter Diameter Diameter Weight
Diameter Radius (Amps)
(mils) (in) (in) (in) (lbs/kft)
(in) (in)
(A) (B) (C) (D) ‡105°C In Duct ‡105°C In Air
35kV 100% Copper One Conductor
20148401 1/0 AWG CU 345 0.341 1.08 1.13 1.29 1011 16 215 290
20196582 2/0 AWG CU 345 0.376 1.11 1.17 1.33 1165 16 245 330
TBD 3/0 AWG CU 345 0.423 1.16 1.21 1.38 1312 17 275 380
20148394 4/0 AWG CU 345 0.479 1.21 1.27 1.43 1443 18 315 445
20182346 250 MCM CU 345 0.522 1.26 1.32 1.48 1653 18 345 490
20148395 350 MCM CU 345 0.622 1.36 1.42 1.58 1989 19 415 605
20148396 500 MCM CU 345 0.742 1.48 1.54 1.70 2542 21 500 755
20182345 750 MCM CU 345 0.917 1.67 1.72 1.95 3670 24 610 970
TBD 1000 MCM CU 345 1.071 1.82 1.88 2.10 4555 26 690 1160
35kV 133% Copper One Conductor
20148397 1/0 AWG CU 420 0.341 1.22 1.27 1.43 1214 18 215 290
20196581 2/0 AWG CU 420 0.376 1.25 1.31 1.47 1279 19 245 330
TBD 3/0 AWG CU 420 0.423 1.30 1.35 1.52 1428 19 275 380
20148398 4/0 AWG CU 420 0.479 1.35 1.41 1.57 1669 19 315 445
20166698 250 MCM CU 420 0.522 1.40 1.46 1.62 1837 20 345 490
20148399 350 MCM CU 420 0.622 1.50 1.56 1.78 2342 22 415 605
20148400 500 MCM CU 420 0.742 1.62 1.68 1.90 2924 23 500 755
20161987 750 MCM CU 420 0.917 1.81 1.86 2.09 3906 26 610 970
TBD 1000 MCM CU 420 1.071 1.96 2.02 2.24 4808 27 690 1160

†Ampacities are based on the following:


PRODUCT NOTES: Three Phase Operation
The above dimensions are approximate and In Duct per 2017 NEC Table 310.60(C)(77): Three single conductor cables in plastic ‡EPROTENAX™ EPR-insulated cables are capable
subject to normal manufacturing tolerances. duct, direct-buried, 105°C conductor temperature, 20°C ambient temperature, earth of operating at 105°C. However, the maximum
RHO of 90°C-cm/Watt, and 100% load factor, and shields short-circuited. operating temperature of the cable should be
Isolated in Air per 2017 NEC Table 310.60(C)(69): Insulated single conductor isolated based on the maximum operating temperature
in air, 105°C conductor temperature, and 40°C ambient temperature, and shields of the cable accessories to be used.
grounded at one point only.
In Cable Tray per 2017 NEC 392.80(B)(2)(b): Single conductor cables, sizes 1/0 AWG
and larger, installed in a single layer in an uncovered table tray, with a maintained
space of not less than one cable diameter between individual conductors, the
ampacities shall not exceed the allowable ampacities stated in 2017 NEC Table
310.60(C)(69) (Copper), “Isolated in Air” values noted above.
B130_MV105_Easy_Glider_2017-10-03

Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 10
A brand of the

35kV 1/C EPR MV-105 EASY GLIDER™(Tape Shield)


100/133% Medium Voltage Commercial & Industrial Cables

Insulation Minimum
Insulation Conductor Insulation Jacket Cable
Shield Bending † Ampacity
Product Number Conductor Thickness Diameter Diameter Diameter Weight
Diameter Radius (Amps)
(mils) (in) (in) (in) (lbs/kft)
(in) (in)
(A) (B) (C) (D) ‡105°C In Duct ‡105°C In Air
35kV 100% Aluminum One Conductor
TBD 1/0 AWG AL 345 0.336 1.07 1.13 1.29 825 16 165 225
TBD 2/0 AWG AL 345 0.379 1.11 1.17 1.33 886 16 190 260
TBD 3/0 AWG AL 345 0.423 1.16 1.21 1.38 959 17 215 300
TBD 4/0 AWG AL 345 0.479 1.21 1.27 1.43 1047 18 245 345
TBD 250 MCM AL 345 0.522 1.26 1.32 1.48 1131 18 270 380
TBD 350 MCM AL 345 0.622 1.36 1.42 1.58 1309 19 330 475
TBD 500 MCM AL 345 0.742 1.48 1.54 1.70 1557 21 400 590
TBD 750 MCM AL 345 0.917 1.68 1.77 2.01 2159 25 490 765
TBD 1000 MCM AL 345 1.071 1.82 1.88 2.10 2450 26 565 920
35kV 133% Aluminum One Conductor
TBD 1/0 AWG AL 420 0.336 1.21 1.27 1.43 987 18 165 225
TBD 2/0 AWG AL 420 0.379 1.25 1.31 1.47 1054 18 190 260
TBD 3/0 AWG AL 420 0.423 1.30 1.35 1.52 1131 19 215 300
TBD 4/0 AWG AL 420 0.479 1.35 1.41 1.57 1226 19 245 345
TBD 250 MCM AL 420 0.522 1.40 1.46 1.62 1315 20 270 380
TBD 350 MCM AL 420 0.622 1.50 1.56 1.78 1606 22 330 475
TBD 500 MCM AL 420 0.742 1.62 1.68 1.90 1875 23 400 590
TBD 750 MCM AL 420 0.917 1.81 1.86 2.09 2300 26 490 765
TBD 1000 MCM AL 420 1.071 1.96 2.02 2.24 2704 27 565 920

†Ampacities are based on the following:


PRODUCT NOTES: Three Phase Operation
The above dimensions are approximate and In Duct per 2017 NEC Table 310.60(C)(78): Three single conductor cables in plastic ‡EPROTENAX™ EPR-insulated cables are capable
subject to normal manufacturing tolerances. duct, direct-buried, 105°C conductor temperature, 20°C ambient temperature, earth of operating at 105°C. However, the maximum
RHO of 90°C-cm/Watt, and 100% load factor, and shields short-circuited. operating temperature of the cable should be
Isolated in Air per 2017 NEC Table 310.60(C)(70): Insulated single conductor isolated based on the maximum operating temperature
in air, 105°C conductor temperature, and 40°C ambient temperature, and shields of the cable accessories to be used.
grounded at one point only.
In Cable Tray per 2017 NEC 392.80(B)(2)(b): Single conductor cables, sizes 1/0 AWG
and larger, installed in a single layer in an uncovered table tray, with a maintained
space of not less than one cable diameter between individual conductors, the
ampacities shall not exceed the allowable ampacities stated in 2017 NEC Table
310.60(C)(70) (Aluminum), “Isolated in Air” values noted above.
B130_MV105_Easy_Glider_2017-10-03

© PRYSMIAN - A Brand of The Prysmian Group 2017. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form,
either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any
specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued October 2017.

Prysmian Group
700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com
137 Commerce Drive | Johnstown, Ontario K0E 1T1 11