Professional Documents
Culture Documents
3 Generator Protection1
3 Generator Protection1
Generator Protection
By
Prof. Dr. Mousa A. Abd-Allah
1
5/16/2022
Generator Faults
Electrical Mechanical
Stator insulation failure Overload Failure of prime mover Low condenser vacuum
Overvoltage Unbalanced load Lubrication oil failure Loss of boiler firing
Rotor faults Loss of excitation Over speeding Rotor distortion
Loss of synchronism Excessive vibration
Generator faults
Abnormal
Stator faults Rotor faults running
conditions
2
5/16/2022
Causes overheating
Overloading Use overcurrent protection
Y-connected Alternator
-connected Alternator
3
5/16/2022
(1)
Main CB of
generator
(6)
Operation (2)
of alarm
Field CB
and/or
indicator
Differential
relay trip
(5) (3)
Turn on CO2 Neutral CB
gas if if it is
provided present
(4)
Shut down
the
primeover
If fault point x is nearer to neutral point, then Vbx is not sufficient to drive enough If, and relay
cannot operate. Thus part of stator windings remains unprotected.
Thus with resistive grounded, stator windings get partly protected against earth fault
4
5/16/2022
So, earth resistance value, relay setting and current rating of earth resistance must be
carefully selected.
Ex: A generator is protected by restricted earth fault protection. The generator ratings are
13.2kV, 10MVA. The percentage of winding protected against phase to ground fault is
85%. The relay setting is such that it trips for 20% out of balance. Calculate the resistance
to be add in the neutral to ground connection.
Solution
10𝑥106
The full load current is; 𝐼= = 437.386 𝐴
3𝑥13.2𝑥103
20
The minimum operating current with 20% out of balance is; 𝐼𝑜 = 437.386𝑥 100 = 87.477 𝐴
13.2𝑥103 𝐼𝑜 𝑅
𝑉𝑝ℎ = = 7621.02 𝑉 % 𝑜𝑓 𝑤𝑖𝑛𝑑𝑖𝑛𝑔 𝑢𝑛𝑝𝑟𝑜𝑡𝑒𝑐𝑡𝑒𝑑 = 𝑥100
3 𝑉
87.477𝑥𝑅
∴ 15 = ∴ 𝑅 = 13.068 𝛺
7621.02
5
5/16/2022
6
5/16/2022
At earth fault, stray capacitance is bypassed, which increases the monitoring current,, which
can be operate protective tool.
This scheme compensate the 15-20% of stator winding to give 100% protection
At normal conditions, the CTs currents are equal., so no current flows in the relay, and it will
not operate.
At SC, unequal currents will flow and the difference in the currents will flow in relay, and it
will operates.
7
5/16/2022
A second fault to earth will short circuit the part of field winding and may there by
produce an unsymmetrical field system.
Such an unsymmetrical system gives rise to unbalanced forces on the rotor and results in
excess pressure on the bearings and the shaft distortion due to vibrations.
Rotor earth fault protection and rotor temp. indications are essential and are provided to
large rating generators.
8
5/16/2022
An earth fault at any part of the winding gives rise to the field
current, which is detected by the sensitive relay.
9
5/16/2022
Loss of excitation may lead to loss of synchronism and slightly increase in speed.
Machine starts behaving as induction generator, draws reactive power from the
system. So, protection is necessary.
10
5/16/2022
11