Mẫu Phiếu Thao Tác Khôi Phục Tc c11 Vào Vận Hành

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

Vote: / /

Page number: /

PHỤ LỤC 1. MẪU PHIẾU THAO TÁC

(CHALEUN SEKONG
ENERGY- NK3 HPP)
OPERATION SHEET
OPERATION WORKSHOP

Operation ticket name : Restore TC C11/Factory and put it into operation


Vote writer: .......................................................... Position:
Vote reviewer: ...................................................... Position:..............................................................
Vote Supervisor: ..................................................Position:..............................................................
.....................................................................................................................................................................
Vote operator: …...................................................... Position:...............................................................
.....................................................................................................................................................................
Purpose of operation: : Restore TC C11/Factory and put it into operation
Intend time:
Begin: .................... h .......... Day..................Month ............... Year....................................................
End: ……........... h ........... Day ..................Month ............... Year ...................................................
The unit recommends the operation: Repair workshop.............................................................................
Necessary conditions for implementation: (if any)
1. ...............................................................................................................................................................
2.................................................................................................................................................................
3.................................................................................................................................................................
Note: (if any)
1..................................................................................................................................................................
2..................................................................................................................................................................
3..................................................................................................................................................................
3..................................................................................................................................................................
Vote: / /

Page number: /

Delivery and acceptance of electrical lines and equipment before operation: (if any)
Time Workshop Full name Content

Sequence of operation items:


Locatio
Sequence of operations Time Person
n
Item
Mad Get
Step Content Begin End Command
e order

I NK3 1 The unit registers to put the


equipment to work. All work
sheets have been locked,
people and vehicles have
withdrawn from the scene, all
mobile grounding devices have
been removed, confirming that
the equipment is ready to
restore power.
2 Remove signs and barriers

3 Close AB TUC11/Factory

4 Close control source, close


resource, Close DCL 171-1
5 Close control source, close
resource, Close DCL 131-1

6 Close control source, close


resource, Close DCL 132-1

7 Close control source, close


resource, Close MC 171 to
pulse Bus bar C11/Factory
Vote: / /

Page number: /

8 Close control source, close


resource, Close 131 to pulse
transformer T1

9 Close control source, close


resource, Close 132 to pulse
transformer T2

10 Close MC 931 to pulse Bus bar


C91

11 Synchronize MC 932 to close


the loop
12 Close MC 941 and check that
it is closed well
13 Close MC 942 and check that
it is closed well

14 Close MC 941 and check that


it is closed well
15 Close MC 941 and check that
it is closed well
16 Restore electricity for self-use

17 Tell A0 to return generator sets


H1, H2, H3

Delivery and acceptance of electrical lines and equipment after operation: (if any)
Time Workshop Full name Content

Day.........Month........Year....... Day.........Month........Year.......

Vote writer Vote reviewer

(Sign and write full name) (Sign and write full name)
Vote: / /

Page number: /

Abnormal events during operations:………………………………….................................................


……………………………………………………………………………………………………………
Người thực hiện thao tác
Ngày.........tháng........năm.......

Supervisor The operator

(Sign and write full name) (Sign and write full name)

Diagram: (attached if necessary)