PHỤ LỤC 1.

MẪU PHIẾU THAO TÁC

CHALEUN SEKONG Vote: / /


ENERGY- NK3 HPP
OPERATION SHEET
OPERATION WORKSHOP Page number: /

Operation ticket name: Restore MC 171 and put it into operation....................................................


Operation ticket name : Isolate Bus bar C11/Facrory for repair
Vote writer: .......................................................... Position:...................................................................
Vote reviewer: ...................................................... Position:..............................................................
Vote Supervisor: ..................................................Position:..............................................................
.....................................................................................................................................................................
Vote operator: …...................................................... Position:...............................................................
.....................................................................................................................................................................
Purpose of operation: Put MC 171 into operation after processing is complete......................................
Intend time:
Begin: .................... h .......... Day..................Month ............... Year....................................................
End: ……........... h ........... Day ..................Month ............... Year ...................................................
The unit recommends the operation: Repair workshop.............................................................................
Necessary conditions for implementation: (if any)
1. ...............................................................................................................................................................
2.................................................................................................................................................................
3.................................................................................................................................................................
Note: (if any)
1..................................................................................................................................................................
2..................................................................................................................................................................
3..................................................................................................................................................................
3..................................................................................................................................................................
Delivery and acceptance of electrical lines and equipment before operation: (if any)
Time Workshop Full name Content

Vote: / /

Page number: /

Sequence of operation items:


Location Sequence of operations Time Person

Item Begi Get


Step Content Made End Command
n order

I NK3 1 The unit registers to put the


equipment to work. All work
sheets have been locked,
people and vehicles have
withdrawn from the scene, all
mobile grounding devices have
been removed, confirming that
the equipment is ready to
restore power.

2 Remove signs and barriers

3 Restore control source,


resource, Close DCL 171-7
4 Restore control source,
resource, Close DCL 171-1
5 Restore control power, power,
Close MC 171 electrical pulse
Bus bar C11/Factory
6 Close MC 131 electrical pulse
of transformer T1

7 Close MC 132 electrical pulse


of transformer T2
8 Close MC 931 electrical pulse
of bus bar C91

9 Synchronize MC 932, closing


the loop.
10 Closing MC 941 Check for
good closin
11 Closing MC 942 Check for
good closin
12 Closing MC 971 Check for
good closin
13 Closing MC 972 Check for
good closin
14 Restore electricity for self-use

15 Tell A0 to return generator unit


H1, H2, H3

Delivery and acceptance of electrical lines and equipment after operation: (if any)
Time Workshop Full name Content

Day.........Month........Year....... Day.........Month........Year.......

Vote writer Vote reviewer

(Sign and write full name) (Sign and write full name)

Abnormal events during operations:………………………………….................................................


……………………………………………………………………………………………………………
Person performing the operation
Day.........Month........Year.......

Supervisor The operator

(Sign and write full name) (Sign and write full name)
Diagram: (attached if necessary) Vote: / /

Page number: /

You might also like