SHOMOUL HOLDING COMPANY W.L.L.
Project Management:
Al Zaid Engineering
AL - ZAID ﺍﻟﺰﻳﺪ
E
250x200
Consultants (ZEC)
C
Z
ENGINEERING P.O. Box 20179 Riyadh 11455, KSA
FAD 90 L/s CONSULTANTS ﻟﻺﺳﺗﺷﺎﺭﺍﺕ ﺍﻟﻬﻧﺩﺳﻳﺔ
Riyadh, KSA
Lead Consultant:
VD ZONE SERVED BY FAHU-RF-04 SHAREKAT ALMOHANEDSOON
ALISTESHAREYOON WE SHARIKOH
LEISTESHARAT ALHANDASEYA
C O N S U L T I N G E N G I N E E R S Euro Marché center
King Abdulla road & Osman Ibn Afan road junction
Riyadh, Saudi arabia
V
750x500
800x650
Y2 Construction Supervision:
WASTE STORAGE EAD 100 L/s
GF-002
250x200
Main Contractor:
VD
1200x750
250x200
P.O. Box: 612, Riyadh 11421
1200x900
W 400x500 EAD
VD FD 12L Notes/Legends:
F&B 1. REFER TO 0001 SERIES DRAWINGS FOR GENERAL NOTES, SYMBOLS AND
1400x1200 EAD ABBREVIATIONS.
1100x900 GM-031
2. REFER TO 5000 SERIES DRAWINGS FOR MISCELLANEOUS DETAILS.
SHAFT 3. REFER TO 7000 SERIES DRAWINGS FOR SCHEMATIC RISER DIAGRAM.
VD FDM-SH-M075 4. REFER TO 8000 SERIES DRAWINGS FOR BUILDING MANAGEMENT SYSTEM.
Y1 5. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE SPECIFIED.
6. ALL PIPE SIZES SHOWN ARE NOMINAL PIPE DIAMETERS.
1200x1000 1700x1200 FAD 7. THIS DRAWING MUST BE READ IN CONJUNCTION WITH THE PROJECT
SPECIFICATIONS, CIVIL, STRUCTURAL, ARCHITECTURAL, AND STANDARD DETAILS
AND ALL ELECTRO- MECHANICAL DRAWINGS.
BOH CORRIDOR VD FD 8. PROVIDE SLEEVE WITH FIRE SEAL FOR ALL PIPES CROSSING FIRE-RATED
GF-041 CONCRETE WALLS, SLABS OR ANY OTHER FIRE-RATED PARTITION.
9. PROVIDE VOLUME CONTROL DAMPERS TO ALL DUCT BRANCHES & AS NECESSARY
SHAFT
FOR PROPER BALANCING.
M-SH-M089 10. PROVIDE FIRE DAMPERS FOR ALL DUCTS CROSSING FIRE RATED WALLS OR
SLABS.
11. ALL DUCTS HAVING FIRE DAMPERS SHALL BE PROVIDED WITH ACCESS DOORS IN
DUCTS.
12. COORDINATE STRUCTURAL OPENINGS WITH STRUCTURAL DRAWINGS. ANY
SHAFT
600x500
MISMATCH BETWEEN ME & ST OPENINGS AND SLEEVES SHALL BE REPORTED TO
900x400
M-SH-M016 ENGINEER.
13. PROVIDE JACKETING FOR ALL INSULATED PIPE & DUCT WORK EXPOSED TO VIEW.
14. PROVIDE CEILING ACCESS PANEL UNDERNEATH EACH FCU TERMINAL, VALVES, &
FIRE/SMOKE/MOTORIZED DAMPERS., VOLUME DAMPERS, VAV, REHEAT, FCU,
VALVES,
BALANCING VALVES, IN COORDINATION WITH ARCHITECTURE.
15. PROVIDE SOUND ATTENUATORS & DUCT LINERS WHERE REQUIRED SO AS TO
#2 SG 750x750 COMPLY WITH THE SPECIFIED SPACE NOISE LEVEL.
C 2400 L/s EACH 16. PROVIDE ACOUSTIC FLEXIBLE DUCT CONNECTION AT AIR OUTLETS BRANCH
X CONNECTION OF MAXIMUM 1.5 M LONG.
17. CONTRACTOR TO PROVIDE ROOM THERMOSTAT AS REQUIRED BY CONTROL
VD VD DRAWINGS. THERMOSTATS SHALL BE LOCATED ABOVE LIGHTING SWITCHES AT
1.5M. VERIFY EXACT LOCATION WITH INTERIOR DESIGN. LOCATE THERMOSTAT
OUT
1000x1300 OF DIRECT SUN EXPOSURE AND SHALL NOT BE SUBJECT TO THE DIRECT
DISCHARGE OF A SUPPLY OUTLET.
18. INSTALL EQUIPMENT LIKE PUMPS, AHUS, HEAT EXCHANGERS, AIR SEPARATORS,
EXPANSION TANKS, ETC… ON CONCRETE PADS. INSTALL ALL EQUIPMENT AS PER
1000x1300 MANUFACTURER’S RECOMMENDATION.
19. TERMINATE/CONNECT CONDENSATE DRAIN PIPE FROM ALL INDOOR UNITS TO
NEAREST FLOOR DRAIN/DRAIN POINT.
20. CONDENSATE DRAIN PIPING SHALL BE LAID WITH 1% SLOPE & SHALL BE
SHAFT
INSULATED.
M-SH-M017 200x150 21. PROVIDE P TRAP FOR CONDENSATE DRAIN PIPING AS PER MISC. DETAILS.
FAD 90 L/s 22. ALL DUCTWORK DIMENSIONS NOTED ON PLANS REFER TO THE CLEAR INSIDE
OPENING REQUIRED.
SHAFT 23. ALL EXHAUST DUCT OPENING, FRESH AIR DUCT OPENING & RETURN AIR DUCT
M-SH-M015 OPENING SHALL BE INSTALLED WITH ALUMINUM WIRE MESH & VOLUME DAMPER.
VD 24. DAMPERS SHALL BE LOW LEAKAGE TYPE, WITH AMCA 511-CLASS 1 SEAL.
25. CONTRACTOR TO PROVIDE 6 MM SQUARE MESH SCREEN ON ALL DUCT AND WALL
OPENINGS IN CEILING SPACE.
26. CONTRACTOR TO PROVIDE EXPANSION FITTINGS AS REQUIRED AND WHERE PIPES
OR DUCTS CROSS BUILDING EXPANSION JOINTS.
27. SERVICES INVERT LEVELS SHALL BE CHECKED AND VERIFIED AGAINST ALL OTHER
SERVICES BEFORE INSTALLATION.
28. EXECUTION OF WORKS ON SITE SHOULD BE BASED ON FINAL APPROVED SHOP
DRAWINGS
29. ALL FLEXIBLE DUCTS SHALL BE PROVIDED WITH VOLUME DAMPER
900x400
30. CONTRACTOR TO INSTALL MOTORIZED SMOKE DAMPERS ON THE SUPPLY
600x500
AND RETURN DUCTS OF AHUs AND FAHUs OF CAPACITIES GREATER THAN
7080 L/S TO ISOLATE THE SYSTEM IN CASE OF SMOKE DETECTION
31. AHU's LOCATION AT ROOF IS SUBJECT TO FINAL COORDINATION WITH AR/FLS
Y
14L Contractor ( Nesma & Partners):
CHECKED BY:
APPROVED BY:
RETAIL
SHAFT EDO 650 X 350 GM-040
M-SH-M090 595 L/s
VD VD RFI REF:
SHAFT
M-SH-M065 400x250 550x350 FDO 750 X 350
VD 700 L/s
600x350
General Key Plan:
400x300 NORTH
15L SHAFT
M-SH-E008 VD VD
8 16 24 32 40 48
MECCA
200x150
7 15 23 31 39 47 55
F&B
GM-035
6 14 22 30 38 46 54 61
5 13 21 29 37 45 53 60 66
4 12 20 28 36 44 52 59 65
IDF ROOM ELEC. ROOM JANITOR ROOM MALL
2 10 18 26 34 42 50 57 63
SHAFT
z M-SH-M048
SHAFT
1 9 17 25 33 41 49 56 62
M-SH-M046
400x300
400x250
Project Name:
VD
50% Detailed Design
400x300
FDO 550 X 300
345 L/s
APRIL 2022
400x250
VD EDO 550 X 250
260 L/s
AA
REFER TO SHEET-322122-DAR-DD1-M2-ZM-GF-DR-MV-1105-13-00
SHAFT
MS-SH-M114
ORIGINATOR PHASE Module Zone Level Type Discipline Number Partial No. REV
1 2 3 4 5 6 L01
7 L02
8 9 L03 10 L04 DAR DD1 M2 MS GF DR MV 1105 05 00