95

110
320
BRACKET PLATE

320
DETAILS OF TOP PLATE

210

210
320

320

236
400 DETAILS OF BOTTOM BASE PLATE
3600

NOTE:
1. All dimensions are in millimetre.
2. Tolerance shall be ±5% as per IS.

27 3. Material : M.S.
Ø1
4. Finishing : Hot dip galvanized.
G.T.P of Tubular Supporting Structure
5. M.S pipe of outer diameter 127mm, thickness
8 50

5.40mm.
236 6. M.S plates used for tubular pipe, base plate and
400
bracket plates shall confirm to IS 2062 with yield
DETAIL X­X
FOR SURGE MONITOR FIXING strength 250N/mm² and ultimate tensile strength
410N/mm².
7. Foundation bolts shall confirm to M16 of grade 4.6
2000

400mm in concrete shall confirm to IS 5624.


8. Surge Arrester housing bolts shall be M10 of grade
4.6 shall confirm to IS1363 Part 2.
9. Permissible working load - 150kg Vertical load with
400 equivalent horizontal load of 110kg at 3.6m height
50 8

with maximum horizontal deflection less than 23mm


at 3.6m height.
10. All welds are of 6mm thick fillet weld shall confirm
27 to IS 800(2007) and IS 816(1969).
Ø1
11.Breaking load - 400kg vertical load and 300kg
horizontal load at 3.6m height.
DETAIL Y­Y
FOR STEPS
KERALA STATE ELECTRICITY BOARD LTD

127
320

ELEVATION