Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

12/30/2015 Safety integrity level ­ Wikipedia, the free encyclopedia

Safety integrity level


From Wikipedia, the free encyclopedia

Safety integrity level (SIL) is defined as a relative level of risk­reduction provided by a safety function, or
to specify a target level of risk reduction. In simple terms, SIL is a measurement of performance required
for a safety instrumented function (SIF).

The requirements for a given SIL are not consistent among all of the functional safety standards. In the
European functional safety standards based on the IEC 61508 standard four SILs are defined, with SIL 4
the most dependable and SIL 1 the least. A SIL is determined based on a number of quantitative factors in
combination with qualitative factors such as development process and safety life cycle management.

Contents

1 Assignment

2 Problems with the use of SIL

3 Advantages for managers

4 Certification

5 SIL in safety standards

6 See also

7 References

8 Textbooks

9 External links

Assignment
Assignment of SIL is an exercise in risk analysis where the risk associated with a specific hazard, that is
intended to be protected against by a SIF, is calculated without the beneficial risk reduction effect of the
SIF. That "unmitigated" risk is then compared against a tolerable risk target. The difference between the
"unmitigated" risk and the tolerable risk, if the "unmitigated" risk is higher than tolerable, must be
addressed through risk reduction of the SIF. This amount of required risk reduction is correlated with the
SIL target. In essence, each order of magnitude of risk reduction that is required correlates with an increase
in one of the required SIL numbers.

There are several methods used to assign a SIL. These are normally used in combination, and may include:

https://en.wikipedia.org/wiki/Safety_integrity_level 1/5
12/30/2015 Safety integrity level ­ Wikipedia, the free encyclopedia

Risk matrices
Risk graphs
Layers of protection analysis (LOPA)

Of the methods presented above, LOPA is by far the most commonly used by large industrial facilities.

The assignment may be tested using both pragmatic and controllability approaches, applying guidance on
SIL assignment published by the UK HSE.[1] SIL assignment processes that use the HSE guidance to ratify
assignments developed from Risk Matrices have been certified to meet IEC EN 61508

Problems with the use of SIL


There are several problems inherent in the use of safety integrity levels. These can be summarized as
follows:

Poor harmonization of definition across the different standards bodies which utilize SIL
Process­oriented matrics for derivation of SIL
Estimation of SIL based on reliability estimates
System complexity, particularly in software systems, making SIL estimation difficult to impossible

These lead to such erroneous statements as, "This system is a SIL N system because the process adopted
during its development was the standard process for the development of a SIL N system", or use of the SIL
concept out of context such as, "This is a SIL 3 heat exchanger" or "This software is SIL 2". According to
IEC 61508, the SIL concept must be related to the dangerous failure rate of a system, not just its failure rate
or the failure rate of a component part, such as the software. Definition of the dangerous failure modes by
safety analysis is intrinsic to the proper determination of the failure rate.[2]

SIL is for electrical controls only and does not relate directly to the caT architecture in EN 62061. It
appears to be a precursor to PL ratings that are now the new requirements which encompass hydraulic and
pneumatic valves.

Advantages for managers


Because SIL has a simple number scheme to represent its levels (1–4), a high­level understanding of each
level is typically all that is necessary to convey SIL at management levels. This saves management from
having to understand the technical aspects of SIL, while allowing them to discuss their concerns.

Certification
The International Electrotechnical Commission's (IEC) standard IEC 61508 defines SIL using requirements
grouped into two broad categories: hardware safety integrity and systematic safety integrity. A device or
system must meet the requirements for both categories to achieve a given SIL.

The SIL requirements for hardware safety integrity are based on a probabilistic analysis of the device.In
order to achieve a given SIL, the device must meet targets for the maximum probability of dangerous
failure and a minimum safe failure fraction. The concept of 'dangerous failure' must be rigorously defined

https://en.wikipedia.org/wiki/Safety_integrity_level 2/5
12/30/2015 Safety integrity level ­ Wikipedia, the free encyclopedia

for the system in question, normally in the form of requirement constraints whose integrity is verified
throughout system development. The actual targets required vary depending on the likelihood of a demand,
the complexity of the device(s), and types of redundancy used.

PFD (probability of failure on demand) and RRF (risk reduction factor) of low demand operation for
different SILs as defined in IEC EN 61508 are as follows:

SIL PFD PFD (power) RRF


1 0.1–0.01 10−1 – 10−2 10–100
2 0.01–0.001 10−2 – 10−3 100–1000
3 0.001–0.0001 10−3 – 10−4 1000­10,000
4 0.0001–0.00001 10−4 – 10−5 10,000–100,000

For continuous operation, these change to the following. (Probability of failure per hour)

SIL PFH PFH (power) RRF


1 0.00001­0.000001 10−5 – 10−6 100,000–1,000,000
2 0.000001­0.0000001 10−6 – 10−7 1,000,000–10,000,000
3 0.0000001­0.00000001 10−7 – 10−8 10,000,000–100,000,000
4 0.00000001­0.000000001 10−8 – 10−9 100,000,000–1,000,000,000

Hazards of a control system must be identified then analysed through risk analysis. Mitigation of these risks
continues until their overall contribution to the hazard are considered acceptable. The tolerable level of
these risks is specified as a safety requirement in the form of a target 'probability of a dangerous failure' in a
given period of time, stated as a discrete SIL.

Certification schemes are used to establish whether a device meets a particular SIL.[3] The requirements of
these schemes can be met either by establishing a rigorous development process, or by establishing that the
device has sufficient operating history to argue that it has been proven in use.

Electric and electronic devices can be certified for use in Functional Safety applications according to IEC
61508, providing application developers the evidence required to demonstrate that the application including
the device is also compliant. IEC 61511 is an application­specific adaptation of IEC 61508 for the Process
Industry sector. This standard is used in the petrochemical and hazardous chemical industries, among
others.

SIL in safety standards


The following standards use SIL as a measure of reliability and/or risk reduction.

ANSI/ISA S84 (Functional safety of safety instrumented systems for the process industry sector)
IEC EN 61508 (Functional safety of electrical/electronic/programmable electronic safety related
systems)
IEC 61511 (Safety instrumented systems for the process industry sector)
https://en.wikipedia.org/wiki/Safety_integrity_level 3/5
12/30/2015 Safety integrity level ­ Wikipedia, the free encyclopedia

IEC 61513 (nuclear industry)

IEC 62061 (safety of machinery)


EN 50128 (railway applications – software for railway control and protection)
EN 50129 (railway applications – safety related electronic systems for signalling)
EN 50402 (fixed gas­detection systems)
ISO 26262 (automotive industry)
MISRA, various (guidelines for safety analysis, modelling, and programming in automotive
applications)
Defence Standard 00­56 Issue 2 – accident consequence

The use of a SIL in specific safety standards may apply different number sequences or definitions to those
in IEC EN 61508.[4]

See also
ALARP
Spurious trip level
HIPPS (High Integrity Pressure Protection System)

There is a whole family of C­level standards based more or less on IEC 61508 that also uses SIL, e.g.,
62061, 26262.

References
[5] [6]

1. M. Charlwood, S Turner and N. Worsell, UK Health and Safety Executive Research Report 216, "A
methodology for the assignment of safety integrity levels (SILs) to safety­related control functions implemented
by safety­related electrical, electronic and programmable electronic control systems of machines", 2004. ISBN 0­
7176­2832­9
2. F. Redmill, "Understanding the Use, Misuse, and Abuse of SILs"
http://www.csr.ncl.ac.uk/FELIX_Web/3A.SILs.pdf with capture date of 11 October 2010
3. CASS Scheme, Conformity Assessment of Safety Systems, http://www.cass.uk.net/
4. F. Redmill, "Understanding the Use, Misuse, and Abuse of SILs"
http://www.csr.ncl.ac.uk/FELIX_Web/3A.SILs.pdf with capture dates of 9 July 2010 and 11 October 2010
5. Marszal, Edward, "Safety Integrity Level Selection – Systematic Methods Including Layer of Protection
Analysis", The Instrumentation, Systems, and Automation Society, Research Triangle Park, NC, USA, 2002.
6. Mitchell, KJ, Longendelpher, TM, Kuhn, MC, "Safety Instrumented Systems Engineering Handbook", Kenexis,
Columbus, OH, USA, 2010.

Textbooks
D. Smith, K. Simpson, "Safety Critical Systems Handbook – A Straightforward Guide to Functional Safety,
IEC 61508 (2010 Edition) and Related Standards" (3rd Edition, ISBN 978­0­08­096781­3, 270 Pages).

M. Punch, "Functional Safety for the Mining Industry – An Integrated Approach Using AS(IEC)61508,
AS(IEC)62061 and AS4024.1." (1st Edition, ISBN 978­0­9807660­0­4, in A4 paperback, 150 pages).
www.marcuspunch.com (http://www.marcuspunch.com)
https://en.wikipedia.org/wiki/Safety_integrity_level 4/5
12/30/2015 Safety integrity level ­ Wikipedia, the free encyclopedia

M.J.M. Houtermans, "SIL and Functional Safety in a Nutshell (Risknowlogy Best Practices Series, 1st
Edition, eBook in PDF, ePub, and iBook format, 40 pages). * SIL and Functional Safery in a Nutshell
(http://risknowlogy.com/product/sil­functional­safety­nutshell/)

H. Hartmann, H. Thomas, E. Scharpf, "Practical SIL Target Selection ­ Risk Analysis per the IEC 61511
Safety Lifecycle" ISBN 978­1­934977­03­3 [1] (http://www.exida.com/Books/SIL­Target­Selection­Risk­
Analysis­per­the­IEC­61511­Safety­Lifecycle)

M. Medoff, R. Faller, "Functional Safety ­ An IEC 61508 SIL 3 Compliant Development Process, (Third
Edition)" ISBN 978­1­934977­08­8 [2] (http://www.exida.com/Books/Functional­Safety­An­IEC­61508­
SIL­3­Compliant­Development­Process)

External links
61508.org (http://www.61508.org) The 61508 Association
IEC Safety Zone (http://www.iec.ch/functionalsafety) The IEC Functional safety zone
Functional Safety, A Basic Guide (http://www.ida.liu.se/~snt/teaching/SCRTS/IEC61508_Guide.pdf)
Functional Safety and IEC 61508: A basic guide
SIL Made Simple (http://docs.google.com/viewer?
a=v&pid=explorer&chrome=true&srcid=0B5PSPJfG9S5kMzhhZDM4YjMtYjhhMC00NDZhLTgzZ
TAtNDkzYTk3MGJmNDhh&hl=en_US&authkey=CJqWsYEJ) – White Paper presented at Valve
World 2010
Safety Integrity Level Manual (http://files.pepperl­
fuchs.com/selector_files/navi/productInfo/doct/tdoct0713a_eng.pdf) Pepperl+Fuchs SIL Manual

Retrieved from "https://en.wikipedia.org/w/index.php?title=Safety_integrity_level&oldid=694629031"

Categories: Safety Risk

This page was last modified on 10 December 2015, at 13:43.


Text is available under the Creative Commons Attribution­ShareAlike License; additional terms may
apply. By using this site, you agree to the Terms of Use and Privacy Policy. Wikipedia® is a
registered trademark of the Wikimedia Foundation, Inc., a non­profit organization.

https://en.wikipedia.org/wiki/Safety_integrity_level 5/5

You might also like