Professional Documents
Culture Documents
EV-T100 SCR Motor Controller, Description, Adjustments, Troubleshooting, Repairs, and Theory
EV-T100 SCR Motor Controller, Description, Adjustments, Troubleshooting, Repairs, and Theory
Four SERVICE MANUAL sections are required for This section has the following components:
the complete Description, Checks, Adjustments, Re-
a. A “Description” of the EV–T100 Motor Con-
pairs, and Troubleshooting of this motor controller:
troller.
• EV–T100 TRANSISTOR MOTOR CON- b. A series of “Status Code Charts” that describe
TROLLER, Description, Adjustments, an indication of a fault and its possible causes
Troubleshooting, Repairs, and Theory, 2200 when the code is shown on the instrument pan-
SRM 581 el display.
• TROUBLESHOOTING AND ADJUST- c. Checks and replacement of the components of
MENTS WITH A COMPUTER For the motor controller are described in “Repairs”.
EV–100ZX And EV–T100 Motor Controllers,
d. A basic “Theory Of Operation” on how a tran-
2200 SRM 597
sistor motor controller operates.
• EV–T100 TRANSISTOR MOTOR CON- An electronic diagnostic and adjustment device can also
TROLLER, Parameter Tables, 2200 SRM 596 be used to check and adjust the control cards. This elec-
• ELECTRICAL SYSTEM, Repairs, Checks tronic diagnostic and adjustment device is called a
And Adjustments, 2200 SRM 560 “Hand Set” and is described later in this section. A com-
puter with the control software installed has access to all
This section describes the operation and the functions of function registers on the control cards. The Hand Set has
the EV–T100 motor controller. The EV–T100 series of access to less function registers on the control card, but
motor controllers, used to control the operation of elec- it can access all of the functions necessary for operation
tric lift trucks, are made by the General Electric Com- on the lift truck.
pany.
A description and the replacement of the instrument
The “EV–T100” identify the controllers that are a tran- panel display is also included in the repair section.
sistor electronic motor controller and have diagnostic Most of the components of the EV–T100 motor control-
control cards. These control cards can use an adapter for ler can not be repaired, but must be replaced. This sec-
a serial cable that will connect to a serial port on a per- tion describes the procedures for using the electronic
sonal computer for checks, adjustments, and trouble- diagnostic and adjustment devices for checking and ad-
shooting. justing the operation of the motor controller.
a. A Cable Kit, Control Card to Computer, is re- There are electrical components that are not part of the
quired (Hyster Part No. 1358471). motor controller, but give input signals to it. These com-
ponents include the following:
b. The HYTECH software for a personal com-
puter is available on a 3.5 inch diskette (Hyster a. Key switch
Part No. 897702). b. START switch (earlier production units only).
c. The Cable Kit and the 3.5 inch diskette with the c. Brake switch
HYTECH software are available from your d. Foot switch
dealer for Hyster lift trucks.
e. Seat switch
These control cards have logic circuits and registers that f. Direction (FORWARD and REVERSE)
control and keep a record of the operations of the motor switches
controller. The registers also keep a record of possible
malfunctions of the motor controller that can indicate g. Accelerator potentiometer
the problems during troubleshooting. h. Guidance and steering systems
1
EV–T100 Motor Controller
Checks and replacement of these electrical components HP = MOSFET Pump Controller, 24 to 48 VDC,
are described in ELECTRICAL SYSTEM, Repairs, 600 Amp
Checks And Adjustments, 2200 SRM 560.
The normal configuration for 72 to 80 volt lift trucks
Model Number Data For EV–T100 Controller that have a transistor controller for both the traction
and hydraulic pump motors:
The model numbers for the EV–T100 controller indi-
cate the following information: JH = IGBT Traction Controller, 24 to 80 VDC,
Example: with Battery Discharge Indicator (BDI).
IC3645EVT100 JH
(01) (02) JY = IGBT Traction Controller, 24 to 80 VDC,
without Battery Discharge Indicator (BDI).
(01) The first series of letters and numbers indicate the
basic catalog number of the controller. LP = IGBT Pump Controller, 24 to 80 VDC, 450
Amp
(02) These letters indicate the control card options:
This series of motor controllers have an output to oper-
JH = Traction Controller, IGBT*, 600 Amp, 24 to
ate a digital display with four digits. A digital display
80 VDC, Automatic PLUGGING/Regenerative
unit (instrument panel display) is available for the in-
Braking, with Battery Discharge Indicator
strument panel of some lift trucks. An adapter for a seri-
(BDI).
al cable that will connect to a RS–232–C serial port on a
JY = Traction Controller, IGBT*, 600 Amp, 24 to personal computer (PC) can be used for checks and ad-
80 VDC, Automatic PLUGGING/Regenerative justments. A Hand Set with a digital display is also
Braking, without Battery Discharge Indicator available. All of the control settings are set using a PC or
(BDI). the Hand Set.
LP = Pump Controller, IGBT, 450 Amp, 24 to 80 The control card is a printed circuit board with elec-
VDC tronic parts in a plastic case. The position of the control
HP = Pump Controller, MOSFET*, 600 Amp, 24 cards in the controllers can be seen in FIGURE 3. Two
to 80 VDC machine screws at the bottom of the plastic case fasten
the control card to the mount plate.
The normal configuration for 36 to 48 volt lift trucks
that have a transistor controller for both the traction The control card has two 6–pin plugs (PA and PB) that
and hydraulic pump motors: connect the signal wires between the parts of the con-
troller and the control card. A terminal strip with six
JH = MOSFET Traction Controller, 24 to 48
screw connections are inputs from control components
VDC, with Battery Discharge Indicator (BDI).
of the lift truck. A 14–pin plug (PZ) connects the control
JY = MOSFET Traction Controller, 24 to 48 card to the functions for SCR 1, SCR 2, and SCR 5. See
VDC, without Battery Discharge Indicator FIGURE 4. Plug PY is a 14–pin plug that connects the
(BDI). instrument panel display or a PC or the Hand Set to the
*MOSFET = Metal Oxide Silicon Field Effect Transistor control card. Some pins of plug PY are also used to con-
*IGBT= Insulated Gate Bipolar Transistor nect the control card to the control card for the hydraulic
(See the THEORY OF OPERATION section for a descrip- pump motor. The functions of the of the signal wires are
tion of these power transistors.) described in TABLE 1. through TABLE 7.
2
EV–T100 Motor Controller
13
12
3
14
15 2
1
17
7 6 5
11 10 9 8
TRANSISTOR CONTROL FOR BOTH TRACTION
MOTOR AND HYDRAULIC PUMP MOTOR
16
12
1
17
3
EV–T100 Motor Controller
2
17
8
3 4 11 9 7
14
6
5
13
2
17
8
3 4 11 9 7
10. CONTACTOR 1A
1. TRANSISTOR MOTOR CONTROLLER 11. FUSE 2, HYDRAULIC PUMP CIRCUIT
(ALSO SEE FIGURE 3.) 12. STEERING PUMP CONTACTOR
2. FIELD WEAKENING CONTACTOR (UNDER FUSE PANEL 17)
3. FORWARD DIRECTION CONTACTOR (F) 13. HYDRAULIC PUMP CONTACTOR
4. REVERSE DIRECTION CONTACTOR (R) 14. ELECTRONIC DRIVER, HYDRAULIC
5. REGENERATIVE BRAKING CONTACTOR (RB) PUMP CONTACTOR
6. DIODE D7 ASSEMBLY, 15. TMM1 MODULE
REGENERATIVE BRAKING 16. TRANSISTOR CONTROLLER,
7. FUSE 4, POWER STEERING CIRCUIT HYDRAULIC PUMP MOTOR
8. CONTACTOR L (ALSO SEE FIGURE 3.)
9. FUSE 1, TRACTION CIRCUIT 17. FUSE PANEL (FU 7, FU 3, FU 5, FU 6)
FIGURE 2. TYPICAL CONFIGURATIONS OF THE EV–T100 MOTOR CONTROLLER IN
E2.00–3.20XM (E45–65XM) LIFT TRUCKS
4
EV–T100 Motor Controller
1. POWER
TRANSISTOR TR1
2. SUPPRESSOR
ASSEMBLY FOR TR1 1
3. CAPACITOR C1 6, 7
(C1a, C1b, C1c)
4. CONTROL CARD
5. SUPPRESSOR
ASSEMBLY FOR
DIODES D3 AND D4
6 & 7. LOCATION OF
DIODES D3 AND D4 2 5
3 3
1
7
2
3
6
3
3 3
5
1. CONTROL CARD
(TRACTION OR HYDRAULIC PUMP)
2. TB SCREW TERMINALS (6)
3 3. PLUG GUIDES
4. PLUG PA (6–PIN) (WIDE GUIDES)
4 5. PLUG PB (6–PIN) (CLOSE GUIDES)
6. PLUG PY (14–PIN)
7. PLUG PZ (14–PIN)
12668
12671 3
5
EV–T100 Motor Controller
6
EV–T100 Motor Controller
TABLE 2. Terminal And Plug Wire Connections For Hydraulic Pump Control Card LP
With: Transistor Control of Hydraulic Pump, Regenerative Braking, Power Steering On Demand, Premium Display, GE Battery
Discharge Indicator (BDI) with Lift Interrupt, Brush Wear and Temperature indicators
NOTE: TABLE 1. and TABLE 2. are components of the same controller option.
Plug or Wire Color or
Terminal Wire Number Function
No.
PA1 GRN/GRY Signal wire between pump control card and brush wear indicator,steering pump.
PA2 BLU–D/YEL Signal wire between pump control card and brush wear indicator,steering pump.
PA3 ORN/PNK Signal wire between pump control card and temperature switch, traction motor.
PA4 BLU–D/PNK Signal wire between pump control card and brush wear indicator, traction motor.
PA5 GRN/PUR Signal wire between pump control card and brush wear indicator, traction motor.
PA6 ORN/YEL Signal wire between pump control card and temperature switch, hydraulic pump motor.
PB1 BRN Supply voltage from Fuse 3
PB2 — Not Used.
PB3 BLU–L To 50 and then to PA2 on traction control card.
PB4 — Not Used.
PB5 — Not Used.
PB6 — Not Used.
TB1 — Not Used.
TB2 GRY To circuit board for control lever, hydraulic pump.
TB3 BLU–D/GRN To circuit board for control lever, hydraulic pump.
TB4 10 Battery supply voltage from TB4 on traction control card.
TB5 — Not Used.
TB6 BLU–D To circuit board for control lever, hydraulic pump.
PY1 — Not Used.
PY2 — Not Used.
PY3 — Not Used.
PY4 BLK–3 To instrument panel display number 10 (PGND) input (ground).
PY5 WHT–3 To instrument panel display number 2 (P5) input.
PY6 — Not Used.
PY7 — Not Used.
PY8 — Not Used.
PY9 — Not Used.
PY10 BRN/ORN Signal wire to PY10 on traction control card.
PY11 BRN/PNK Signal wire to PY9 on traction control card.
PY12 BRN/WHT Signal wire to PY8 on traction control card.
PY13 WHT–4 To instrument panel display number 7 (P13) input.
PY14 BLK–4 To instrument panel display number 6 (P14) input.
PZ1 WHT/BRN Battery negative.
PZ2 VIO Signal wire from TR1 thermal protector.
PZ3 BRN Signal wire for voltage check across TR1.
PZ4 RED Signal wire to gate for TR1.
PZ5 WHT/VIO Signal wire from TR1 thermal protector.
PZ6 — Not Used.
PZ7 — Not Used.
PZ8 — Not Used.
PZ9 BLU Signal wire for voltage check across TR1.
PZ10 98 BLU–D/GRY Signal wire between pump control card and brush wear indicator, hydraulic pump motor.
PZ11 99 GRN/PNK Signal wire between pump control card and brush wear indicator, hydraulic pump motor.
PZ12 GRN Signal wire from motor current sensor.
PZ13 YEL Signal wire from motor current sensor.
PZ14 WHT Signal wire for battery voltage check.
7
EV–T100 Motor Controller
8
EV–T100 Motor Controller
TABLE 4. Terminal And Plug Wire Connections For Hydraulic Pump Control Card LP
With: Transistor Control of Hydraulic Pump, Regenerative Braking, Power Steering On Demand, full GE Display option, GE
Battery Discharge Indicator (BDI) with Lift Interrupt, Brush Wear and Temperature indicators
NOTE: TABLE 3. and TABLE 4. are components of the same controller option.
Plug or Wire Color or
Terminal Wire Number Function
No.
PA1 GRN/GRY Signal wire between pump control card and brush wear indicator,steering pump.
PA2 BLU–D/YEL Signal wire between pump control card and brush wear indicator,steering pump.
PA3 ORN/PNK Signal wire between pump control card and temperature switch, traction motor.
PA4 BLU–D/PNK Signal wire between pump control card and brush wear indicator, traction motor.
PA5 GRN/PUR Signal wire between pump control card and brush wear indicator, traction motor.
PA6 ORN/YEL Signal wire between pump control card and temperature switch, hydraulic pump motor.
PB1 BRN Supply voltage from Fuse 3
PB2 — Not Used.
PB3 BLU–L To 50 and then to PA2 on traction control card.
PB4 — Not Used.
PB5 — Not Used.
PB6 — Not Used.
TB1 — Not Used.
TB2 GRY To circuit board for control lever, hydraulic pump.
TB3 BLU–D/GRN To circuit board for control lever, hydraulic pump.
TB4 10 Battery supply voltage from TB4 on traction control card.
TB5 — Not Used.
TB6 BLU–D To circuit board for control lever, hydraulic pump.
PY1 BLK–4 GE instrument panel display number 4 (PY1).
PY2 WHT–4 GE instrument panel display number 3 (PY2).
PY3 ORN GE instrument panel display number 1 (PY3).
PY4 BLK–3 GE instrument panel display number 2 (PY4) (ground).
PY5 — Not Used.
PY6 — Not Used.
PY7 — Not Used.
PY8 — Not Used.
PY9 — Not Used.
PY10 BRN/ORN Signal wire to PY10 on traction control card.
PY11 BRN/PNK Signal wire to PY9 on traction control card.
PY12 BRN/WHT Signal wire to PY8 on traction control card.
PY13 — Not Used.
PY14 — Not Used.
PZ1 WHT/BRN Battery negative.
PZ2 VIO Signal wire from TR1 thermal protector.
PZ3 BRN Signal wire for voltage check across TR1.
PZ4 RED Signal wire to gate for TR1.
PZ5 WHT/VIO Signal wire from TR1 thermal protector.
PZ6 — Not Used.
PZ7 — Not Used.
PZ8 — Not Used.
PZ9 BLU Signal wire for voltage check across TR1.
PZ10 98 BLU–D/GRY Signal wire between pump control card and brush wear indicator, hydraulic pump motor.
PZ11 99 GRN/PNK Signal wire between pump control card and brush wear indicator, hydraulic pump motor.
PZ12 GRN Signal wire from motor current sensor.
PZ13 YEL Signal wire from motor current sensor.
PZ14 WHT Signal wire for battery voltage check.
9
EV–T100 Motor Controller
10
EV–T100 Motor Controller
11
EV–T100 Motor Controller
12
EV–T100 Motor Controller
REGISTER PARAMETERS just the parameters for the control card. There is a de-
scription of the code numbers for the different control
General cards in the “Parameter Tables”. These tables have the
correct setting numbers for the parameters on each con-
The control cards have an electronic device called an
trol card.
EEPROM (Electrically–Erasable–Programmable–
Read–Only–Memory). The EEPROM has a number of
CONTROL CARD, CHECKS AND
memory elements called registers. These registers can ADJUSTMENTS
have electronic data stored in them to control an opera-
A Personal Computer (PC) or a Hand Set is used to per-
tion. The range of data that can be stored in the registers
mit Authorized Personnel to make the following
is called a parameter. A parameter is a measurement
checks and adjustments:
number that works with other measurement numbers
(parameters) to define a system. The EEPROM in the • Check the system status codes for both traction
control card is a control system for the operation of the and hydraulic pump SCR systems
lift truck.
• Check for status codes that are not regular nor
WARNING constant
Each register in each control card has a range of • Check the state of charge of the battery on mo-
numbers so that the control card can be used on dif- tor controllers with type ZH and ZY control
ferent models of lift trucks. This variation is needed cards
for lift trucks of different sizes and operating volt-
ages. Adjustment of the register to the wrong num- • Check the hourmeter readings on the traction
ber for your lift truck model can cause the truck to circuit and hydraulic pump SCR controllers
operate differently than normal. This different op- • Monitor or adjust the following control func-
eration of the truck can cause an injury. tions:
Do NOT adjust any of the registers without using ♦ Creep Speed
the parameters shown in EV–T100 TRANSISTOR ♦ Controlled Acceleration and 1A Time
MOTOR CONTROLLER, Parameter Tables. ♦ Current Limit
♦ Steering pump time delay and define signal
NOTE: EV–T100 TRANSISTOR MOTOR CON- input (seat switch or directional switch) (This
setting also controls the time delay for the
TROLLER, Parameter Tables, 2200 SRM 596 show
seat switch.)
the permitted ranges and the default setting for each
♦ Plugging distance (Current)
control function. The Factory Set Parameters are the
♦ Accelerator pedal position, plug range or
recommended settings for new units. These settings will disable
give satisfactory performance for most applications. ♦ 1A drop out current or disable
♦ Field Weakening drop–out
Some functions can be adjusted within the permitted
♦ Field Weakening pick–up
range to change the lift truck operation for a specific
♦ Regenerative Braking current limit
application. Adjustment of a register to a number that is
♦ Regenerative Braking drop–out
different than the factory setting is allowed, but follow
♦ Speed limit points (SL1, SL2 and SL3)
the instructions carefully and stay within the minimum
♦ Internal resistance compensation for battery
and maximum limits. Adjustments other than the facto- state of charge indication
ry settings will cause the lift truck to operate differently ♦ Battery voltage (36/48V is auto ranging)
and can cause increased wear of parts.
• Selection of type of card operation:
Function Numbers ♦ Traction circuit with Field Weakening
♦ Traction circuit with Regenerative Braking
The Function Numbers are code numbers for the differ- and Field Weakening
ent parameters that can be set for the control cards. The ♦ High or low current limit for all of the above
Personal Computer or the Hand Set must be used to ad- functions
13
EV–T100 Motor Controller
HAND SET
1
How To Check And Adjust The Registers
The Hand Set can be used with the EV–100 series motor
controllers. The Hand Set is used to access the registers 2
for the traction or pump motor functions, indicate status
codes (possible faults) and make adjustments to the op-
erating limits set in the control cards. Some of the regis-
ters in the “ZX” series of control cards can not be ac-
cessed with the Hand Set. The Hand Set can access the
registers that control the operation of the lift truck. The 3
values for the limits on the control card functions must
PLUG WIRING
be set with either a PC or the Hand Set. The Hand Set has
MOD. PLUG
a Light Emitting Diode (LED) display, a keypad for data PLUG PY
entry and an adjustment knob for changing function val- 1 9
2 6
ues. See FIGURE 6. 3 3
4 4
NOTE: The vehicle will operate with the Hand Set con- 5 5
nected, however, the adjustment knob MUST be set 6 8
fully clockwise to make sure the control can operate at 7 1
8 2
maximum speed. 4
This section has the control card checks and adjustments 5 6
that can be made using the Hand Set. The control card
checks and adjustments are usually made with the con-
trol card installed in the lift truck. Bench checks and ad- 12657
justments can also be made with the control card con- 1. ADJUSTMENT 4. COIL CORD
nected as shown in FIGURE 8. The checks show the KNOB 5. PLUG PY (14 PIN)
stored setting numbers that have been stored for the dif- 2. LED DISPLAY 6. MODULAR PLUG
ferent control card functions. This section also includes 3. KEYPAD (8–PIN Hand Set)
a description of each of the different functions. Use the FIGURE 6. HAND SET
adjustment knob on the Hand Set to adjust the function
How To Scroll Through The Fault Codes And
settings. See FIGURE 6. Clear Them (See FIGURE 7.)
The EV100ZX controller has function registers (31
through 47) that store the last 16 status codes that caused
the operation of the lift truck to stop and the battery
charge at the time the fault occurred. (A PMT fault is re-
set by turning the key switch to OFF and then to ON.)
The first of the 16 status codes will be overwritten each
time a new status code occurs. The stored status can be
cleared from the register by using the Hand Set. (The PC
software programs clears the fault register automatical-
ly.) Use the procedure in FIGURE 7. to access and clear
the fault code registers with the Hand Set:
14
EV–T100 Motor Controller
15
EV–T100 Motor Controller
MALE TO FEMALE PLUG B (CABLE END) PLUG Y (CABLE END) PLUG Z (CABLE END)
DB9 SOCKET TO PC
1 2 3 4 5 1 2 3 1 2 3 4 5 6 7 1 2 3 4 5 6 7
6 7 8 9
4 5 6 8 9 10 11 12 13 14 8 9 10 11 12 13 14
NOTE: If a PC is used,
a 12–volt battery that
can supply 50 milliamps
can be used instead of
1 the power supply.
1. SHIELDED SERIAL CABLE ASSEMBLY (HYSTER PART NO. 1358470) D–9 SERIAL CABLE,
MALE TO FEMALE (STANDARD COMPUTER EXTENSION CABLE)
2. ADAPTER CABLE (HYSTER PART NO. 1358469)
When The Hand Set Is Connected To A connected or disconnected to a control card that is
Control Card Installed In A Lift Truck installed in a lift truck, raise the drive wheels. Then
turn the key switch to OFF, disconnect the battery
WARNING
and discharge capacitor C1.
Prevent movement of the lift truck when making
checks and adjustments. Before the Hand Set is
16
EV–T100 Motor Controller
17
EV–T100 Motor Controller
NOTE: If the vehicle is operated with the Hand Set con- check the label at the top edge of each card case. There
nected, make sure to set the Adjustment Knob fully are some painted letters and numbers followed by letters
clockwise to make sure the control can operate at top on the lower part of the label. The last two letters identi-
speed. fy the type of card installed. The following types of con-
trol cards are used:
Disconnect the plug at connection Y on the control card
to disconnect the Hand Set. Connect the plug for the in- JH = Traction Controller with three–wire
strument panel display at connection Y. potentiometer and with Battery Discharge
Indicator (BDI).
Function Numbers 48 through 62.
(The seat switch must be closed.) JY = Traction Controller with three–wire
potentiometer and without Battery
1. Turn the key switch to ON after the Hand Set is Discharge Indicator (BDI)
connected to the traction card. (Turn the key switch
to OFF after the Hand Set is connected to the hy- LP or HP = Pump Motor Controller
draulic pump card.) These same letters are also shown in the “Parameter
Think of the CONT key equaling 47. Push and hold the Tables” and in the section headings for the control cards
CONT key plus the additional key number above 47 to for the traction motor and hydraulic pump motor.
total the required Hand Set number. Close the seat TRACTION CONTROL CARDS
switch and the key switch. Example: for Function Num- (LABEL LETTERS – JH AND JY)
ber 48, push the CONT and key 1 (47+1=48, 47+2=49,
47+3=50, 47+5=52, etc.). The display will show the se- NOTE: These control cards are used with the motor
lected register. After one second, the display will show controllers that control the speed of the traction motor.
the parameter that has been set in that register.
WARNING
NOTE: HS Numbers 47, 51, 55 and 59 are the registers If any of the parameters are changed, the operators
for the MODE numbers and are not used. Do not try to must be told that the lift truck will operate differ-
set these numbers with the Hand Set. ently.
2. Push and hold the CONT key for one second. The dis- Do not adjust the parameters outside of the range
play number will blink. of numbers shown in the “Parameter Tables”. Pa-
rameters set outside of the ranges can cause dam-
3. To change the parameter, check for the correct pa- age to the components of the traction system and
rameter for that register in the “Parameter Tables”.
can cause the lift truck to operate differently than
Change the parameter by turning the Adjustment Knob
normal. This different operation of the lift truck
on the Hand Set. The display will continue to blink as the can result in personal injury.
setting changes.
Function Number 1
4. Push and hold the STORE key for one second. When
STORED STATUS CODE
the new parameter is set (stored), the display will stop
(Push 1)
blinking.
This register contains the last status code of a possible
5. Push and hold the ESC key for one second. The dis-
PMT fault that caused the lift truck to stop operation.
play will show “8888”. To check or set another register,
These codes can be removed from the display by turning
do Steps 1 through 3. To return to normal operation (run
the key switch to OFF. The code will be stored in regis-
mode), push and hold ESC again for one second or
ters in the control card. This status code will be replaced
longer.
with the same status code if another possible PMT fault
FUNCTION NUMBER DESCRIPTIONS occurs. The status code can be cleared from memory by
adjusting the setting number to zero. The number must
The following pages have descriptions for the different be stored by pushing the STORE key for one second.
Function Numbers. The setting for each function is spe- Adjustment of the values this register does not change
cific for each control card. To identify the control card, the operation of the lift truck.
18
EV–T100 Motor Controller
Function Number 2
WARNING
CREEP SPEED
(Push 2) A parameter set greater than the number shown in
the “Parameter Tables” will make the lift truck
This register permits the adjustment of the creep speed slow at a rate faster than normal. A parameter set
of the lift truck. The range of adjustment is from 0 (5%) at less than the number shown will make the lift
to 255 (15%). The percent values are the SCR 1 “ON truck have a slower plugging effect. This different
Time”. A constant creep speed frequency will be main- operation of the truck can result in injury. A faster
tained when the accelerator input voltage is between 3.7 plugging rate can also damage the control system or
and 3.5 volts (a potentiometer resistance value between the traction motor.
6K and 4.7K ohms).
The number for this parameter for the current value of
Function Number 3 this register must be found if the Pedal Position Plug
CONTROLLED ACCELERATION AND 1A (Function Number 16) will not be used. To find the num-
TIME ber for the current value, use the following information:
(Push 3) Range 200 to 1000 amps
Setting Range 0 to 255
This register permits the adjustment of the maximum
Resolution 3.14 amps per set unit
rate of acceleration. The setting determines the time al-
lowed to reach maximum SCR speed after the accelera- Example: Setting of 20=263A (EV–100)
tor is set for maximum speed from stop. The control will 20 x 3.14A = 62.8A or 63A
stay in SCR acceleration for between 0.77 second (set- 63A + 200A (range min) =
ting 8) and 21.5 seconds (setting 255) before the 1A con- 263A
tactor will close. The numbers in () are the parameters Function Number 6
for the times shown. The 1A contactor will automati- 1A DROP OUT CURRENT
cally close 0.2 second after the controlled acceleration (Push 6)
stops. The speed control input is less than 0.5 volt (ac-
celerator potentiometer set at less than 50 ohms). Do not This register permits the adjustment of the parameter for
adjust the number in the register to less than the mini- the current value at which the 1A contactor will dee-
mum setting of 8. nergize (open). The 1A contactor will open and the mo-
tor torque will be limited to SCR current to prevent mo-
Function Number 4 tor currents that are too high. A value of 255 will disable
CURRENT LIMIT the 1A Drop Out function.
(Push 4)
Function Number 7
This register permits the adjustment of the current limit FIELD WEAKENING PICK UP
of the motor controller. The current rating of the motor (Push 7)
controller will determine the range of adjustment for
CAUTION
this register. See the “Parameter Tables”. Do not ad-
just the register to any number other than the factory set- A setting HIGHER than the setting shown in the
ting. “Parameter Tables” will make the Field Weakening
Contactor energize too soon. This operation can
Function Number 5 damage the traction motor.
PLUGGING DISTANCE (CURRENT)
This register permits the adjustment of the current value
(Push 5)
at which the FW contactor will energize (close). This
This register permits the adjustment of the distance it parameter permits the FW contactor to close when the
takes to stop the lift truck when plugging. A parameter lift truck has returned to approximately 150% of its run-
set to higher numbers makes the lift truck stop faster. ning current with a full load on a level surface.
Lower numbers decrease the plugging for a longer stop- Do NOT set this register to a number greater than
ping distance. the number set by Function Number 8. If this regis-
19
EV–T100 Motor Controller
ter is set to a number less than 5, the Field Weaken- This parameter permits adjustment of the percent ON
ing function will be deenergized. time at which the control will start to energize the regen-
erative braking circuit. The percent ON time can be be-
Function Number 8 tween 0% and 95%. This adjustment sets the speed
FIELD WEAKENING DROP OUT where regenerative braking will start. This parameter
(Push 8) prevents the controller from energizing the regenerative
braking circuit when motor current is too low.
CAUTION
A parameter set HIGHER than the number shown Function Number 11 and 12
in the “Parameter Tables” will make the Field SPEED LIMIT 1 and 2 (SL1 and SL2)
Weakening Contactor remain energized at high (Not Used)
currents. This operation can cause motor heating Function Number 13
and damage the traction motor. SPEED LIMIT 3 (SL3)
(Push 13)
This register permits adjustment of the current value at
which the FW contactor will deenergize (open). This pa- This parameter permits adjustment of the speed limit
rameter permits the FW contactor to open when the lift (maximum battery volts to the motor). The range is 0%
truck requires more than 300% of the running current to 96%. The adjustment sets the speed limit for the time
with a full load on a level surface. when the input signal from the SL3 limit switch is re-
ceived by the control card. This signal can be a signal
Function Number 9
from the sensor in the traction motor or the hydraulic
REGENERATIVE BRAKING CURRENT LIMIT
pump motor. If the sensor shows that a motor is too hot,
(Push 9)
the control will decrease the maximum motor speed to
WARNING this speed setting. The SL3 limit switch is a normally
closed switch connected to battery negative. When the
A parameter set greater than the number shown in
switch opens, it enables the speed limit function. A set-
the “Parameter Tables” will make the lift truck
ting of 0 will disable the speed limit function. This zero
slow at a rate faster than normal. A parameter set
setting will permit top speed when no limit switch is
at less than the number shown will make the lift
connected. A zero setting will not slow the motor with
truck have a slower regenerative braking effect.
an input from the sensor and can damage the motor.
This different operation of the truck can result in
Some models of lift trucks do not use this function. This
personal injury. A faster regenerative braking rate
function is activated by Status Codes –90 and –93.
can also damage the control system or the traction
motor. Function Number 14
INTERNAL RESISTANCE COMPENSATION
This register permits adjustment of the Regenerative (Push 14)
Braking current limit. The higher the current limit set-
ting, the shorter the stopping distance. The shorter stop- CAUTION
ping distance causes faster wear on the drive train and Adjusting this function setting to the wrong num-
brushes of the traction motor. ber can cause battery damage.
Function Number 10 This register is used when the control card has the Bat-
REGENERATIVE BRAKING START tery Discharge Indicator (BDI) function. Control cards
(Push 10) that have BDI are type ZH control cards. The “Parame-
ter Tables” show the parameters for a battery in average
CAUTION
condition.
A parameter set greater than the number shown in
the “Parameter Tables” can prevent regenerative For the best use of your battery energy, the register can
braking. The lift truck will remain in the plugging be adjusted using the following procedure. However,
mode longer and increase brush wear in the trac- you must use the procedure to change the parameter in
tion motor. the register as the battery changes during months the
20
EV–T100 Motor Controller
battery is used or battery damage can occur. Setting the Function Numbers GREATER THAN 15
parameter too low for your battery can allow the battery
NOTE: For registers greater than 15, think of the
to discharge below the minimum specific gravity value.
CONT key as equal to 15. Push and hold the CONT key
This minimum specific gravity is the specification given
plus the additional key number above 15 to total the re-
by the battery manufacturer to prevent battery damage.
quired register number. Example: for Function 18, push
Using the following procedure to adjust the parameter: the CONT key and key 3 (15+3=18). The display will
show the selected function. After one second, the dis-
a. Operate the lift truck on a normal work cycle. play will show the setting number that has been set for
Travel at medium speeds. that register.
NOTE: The Seat Switch must be OPEN for Function
b. When lift interrupt occurs, stop the lift truck
Numbers 16 through 30.
and wait for approximately 10 minutes.
Function Number 16
c. Check the specific gravity of several battery PEDAL POSITION PLUG
cells. If the specific gravity is between 1.140 (Push CONT and 1)
and 1.150, the setting is correct for that battery.
This register permits adjustment of the range for pedal
If the specific gravity reading is high, adjust the
position plugging. The parameter in this register permits
parameter in the register to a lower number. If
the pedal position to control the plugging current and the
the specific gravity reading is low, adjust the
plugging distance. The current value set by this register
parameter to a higher number.
is enabled as the accelerator is returned to the creep
NOTE: It can be necessary to charge the battery and do speed position. There is maximum plugging current
Steps 1 through 3 again to get an accurate number for when the accelerator is in the maximum speed position.
your battery. To disable the pedal position plugging function, adjust
the current value to the same current value as the plug-
Function Number 15 ging distance current. See the description in Function
BATTERY VOLTS Number 5.
(Push 15)
Example: If Plugging Distance Current (Function Num-
This register permits adjustment for the operating volt- ber 5) is set at 500 amps, then set pedal plugging current
age of the lift truck. The adjustment also permits correct to 500 amps. The pedal position will have no effect on
operation of the Battery Discharge Indicator function the plugging distance with this setting.
for lift trucks equipped with BDI. For the controller and Use the following information to adjust the current
BDI to operate correctly, the parameter shown in the value:
Tables for the Register Parameters must be entered. Range 100 to 930 amps
Battery Volts Parameter Parameter Range 0 to 255
36 volts Between 32 and 44 Resolution 3.2A per set unit
48 volts Between 45 and 69
Example: Parameter of 20 = 164 amps
72 volts Between 70 and 80
20 x 3.2A = 64A
80 volts Between 81 and 183
64A+100(range min)=164A
36/48 volts Between 184 and 250
No BDI Between 251 and 255
Function Number 17
NOTE: If the parameter is set to a number other than the CARD TYPE SELECTION
number shown for your lift truck in Tables for the Regis- (Push CONT and 2)
ter Parameters, a status code of –15 or –16 will occur.
Make sure the battery is fully charged and battery con- WARNING
nector has good connections before making this adjust- Wrong parameters entered into the register in
ment. This check is especially important when adjusting Function Number 17 can cause the truck to operate
for 36/48 volt operation (numbers 184 to 250). differently than normal. This different operation of
21
EV–T100 Motor Controller
the truck can cause an injury. NEVER set Function Function Number 21
Number to a parameter that is not shown for your MAINTENANCE SPEED LIMIT
lift truck. (Push CONT and 6)
This register can be set by the service person to control
This register permits the selection of the card type used the speed limit (maximum battery volts to the motor)
for your lift truck application. when the Maintenance Alert (Status Code –99) is acti-
vated by the control card. The range for this register is 0
Function Number 18 to 180.
STEERING PUMP TIME DELAY
(Push CONT and 3) Function Numbers 22 through 26
TEMPORARY DATA REGISTERS
WARNING These registers can be read with the Hand Set, but the
A parameter set lower than the number shown in data in them changes during lift truck operation. Do not
the “Parameter Tables” can permit the steering change the parameters in registers for Function numbers
pump to stop if the seat switch opens momentarily 22 through 26.
during normal operation. There is no power steer-
ing if the steering pump stops. The sudden and dif- CAUTION
ficult steering effort that is not expected can cause Function 25 (temporary storage register for fault
injury or property damage. data) and Function 26 (temporary storage register
for battery charge data) must not be changed by the
user to any number above zero. Any number above
This register permits the selection of the input for the
zero can cause the instrument panel display to not
steering pump contactor. Closing the seat switch or the
operate correctly and the lift truck can become dis-
FWD/REV switch can be the input. The parameter also
abled.
sets the time delay for the contactor to open after the
switch opens. Function Number 27
STOP PLUGGING SET POINT
NOTE: There is no delay time for the contactor to close (Push CONT and 12)
after receiving the input signal from the seat switch or
the FWD/REV switch. Parameters in the 0–128 range The PLUGGING function normally stops when the ON
adjust the delay after the seat switch opens. Parameters time of TR1 decreases to 15%. This function permits a
in the 129–255 range adjust the delay after the FWD/ decrease of the STOP PLUGGING set point to a percent
REV switch opens. Adjust the setting to the number of ON time between 13.4% and 6.8%.
shown in “Parameter Tables”. Function Number 28
FAULT INDICATOR POINTER REGISTER
Function Number 19
MAINTENANCE ALERT (Tens/Units) Th1s register can be read with the Hand Set. Function
(Push CONT and 4) number 28 is the fault indicator pointer and must be
set to zero when all faults or malfunctions have been
This register can be set by the service person to give a fixed or removed from the controller.
Status Code –99 when scheduled maintenance is re- Function Number 29
quired. The range for this register is 0 to 99 hours. HOURMETER (Tens/Units)
(Push CONT and 14)
Function Number 20
MAINTENANCE ALERT (Thousands/Hundreds) This register has the data for the accumulated operating
(Push CONT and 5) hours of the lift truck. This register is not normally
changed unless a new control card is installed. If a new
This register can be set by the service person to give a control card is installed, the total hours from the old con-
Status Code –99 when scheduled maintenance is re- trol card must be entered so that the total operating hours
quired. The range for this register is 100 to 9900 hours. of the lift truck is correctly recorded.
22
EV–T100 Motor Controller
a. Low performance for handling fragile loads. This register permits the adjustment of the current value
at which the FW contactor will energize (close). This
b. Medium speed for less consumption of battery parameter permits the FW contactor to close when the
charge during a work shift. lift truck has returned to approximately 150% of its run-
ning current with a full load on a level surface. The mini-
c. Higher performance with higher consumption mum parameter is zero. Do not set the number in the reg-
of battery charge during a work shift. ister greater than the number in the register for Function
Number 53.
d. Maximum lift truck performance with higher
consumption of battery charge. Function Number 50
SPEED LIMIT 1
The four performance levels can be set to any level up to (Push CONT and 3 while the key switch and seat
the maximum limits. Two or more adjacent perfor- switch are closed)
mance levels can be set to the same limits. The perfor-
mance levels must be set at the same or in ascending or- This parameter permits adjustment of the speed limit
der (from turtle to rabbit). The register interlocks will (maximum battery volts to the motor). The range is 0%
not permit a higher performance level setting toward the to 96%. There is no speed limit switch for this function.
turtle than the adjacent registers toward the rabbit. This function will be disabled if the parameter in the reg-
ister is set to zero. Do not set the number in the register to
NOTE: The Seat Switch must be CLOSED for Func- less than the parameter for Function Number 54. Do not
tion Numbers 48 through 62. set the number in the register greater than 180.
23
EV–T100 Motor Controller
This register permits the adjustment of the maximum This register permits the adjustment of the maximum
rate of acceleration in MODE 2. The parameter deter- rate of acceleration in MODE 3. The parameter deter-
mines the time allowed to reach maximum SCR speed mines the time allowed to reach maximum SCR speed
after the accelerator is set for maximum speed from after the accelerator is set for maximum speed from
stop. The control will stay in SCR acceleration for 2.6 stop. The control will stay in SCR acceleration for 1.8
seconds (setting 30) before the 1A contactor will close. seconds (setting 20) before the 1A contactor will close.
The numbers in () are the parameters for the times The numbers in () are the parameters for the times
shown. The 1A contactor will automatically close 0.2 shown. The 1A contactor will automatically close 0.2
second after the controlled acceleration stops. The second after the controlled acceleration stops. The
speed control input is less than 0.5 volt (accelerator po- speed control input is less than 0.5 volt (accelerator po-
tentiometer set at less than 50 ohms). Do not set the tentiometer set at less than 50 ohms). Do not set the
number in the register to less than the parameter for number in the register to less than the parameter for
Function Number 56. Do not set the number in the regis- Function Number 60. Do not set the number in the regis-
ter greater than the number in the register for Function ter greater than the number in the register for Function
Number 48. Number 52.
Function Number 53
Function Number 57
FIELD WEAKENING PICK UP
FIELD WEAKENING PICK UP
(Push CONT and 6 while the key switch and seat
(Push CONT and 10 while the key switch and seat
switch are closed)
switch are closed)
This register permits the adjustment of the current value
at which the FW contactor will energize (close). This This register permits the adjustment of the current value
parameter permits the FW contactor to close when the at which the FW contactor will energize (close). This
lift truck has returned to approximately 150% of its run- parameter permits the FW contactor to close when the
lift truck has returned to approximately 150% of its run-
ning current with a full load on a level surface. Do not set
the number in the register to less than the parameter for ning current with a full load on a level surface. Do not set
Function Number 49. Do not set the number in the regis- the number in the register to less than the parameter for
Function Number 53. Do not set the number in the regis-
ter greater than the number in the register for Function
Number 57. ter greater than the number in the register for Function
Number 61.
Function Number 54
SPEED LIMIT 1 Function Number 58
(Push CONT and 7 while the key switch and seat SPEED LIMIT 1
switch are closed) (Push CONT and 11 while the key switch and seat
switch are closed)
This parameter permits adjustment of the speed limit
(maximum battery volts to the motor). The range is 0% This parameter permits adjustment of the speed limit
to 96%. There is no speed limit switch for this function. (maximum battery volts to the motor). The range is 0%
This function will be disabled if the parameter in the reg- to 96%. There is no speed limit switch for this function.
ister is set to zero. Do not set the number in the register to This function will be disabled if the parameter in the reg-
less than the parameter for Function Number 58. Do not ister is set to zero. Do not set the number in the register
set the number in the register greater than the number in greater than the number in the register for Function
the register for Function Number 50. Number 58.
24
EV–T100 Motor Controller
This register permits the adjustment of the current value Function Number 3
at which the FW contactor will energize (close). This CONTROLLED ACCELERATION
parameter permits the FW contactor to close when the (Push 3)
lift truck has returned to approximately 150% of its run- This register permits the adjustment of the maximum
ning current with a full load on a level surface. Do not set rate of acceleration. The parameter determines the time
the number in the register to less than the parameter for allowed to reach maximum SCR speed after the switch
Function Number 57. Do not set the number in the regis- closes. This parameter determines how fast the hydrau-
ter greater than 110. lic functions will begin to operate. The control will stay
in SCR operation for 0.1 to 22 seconds after the switch
PUMP CONTROL CARD closes.
(LABEL LETTER LP)
Function Number 4
NOTE: This control card is used with the motor con- CURRENT LIMIT
troller that controls the speed of the motor for the hy- (Push 4)
draulic pump.
This register permits the adjustment of the current limit
WARNING of the control. The current limit is normally set at the
If any of the register parameters are changed, the maximum (255).
operators must be told that the lift truck will oper- Function Number 7
ate differently. CONTROLLED ACCELERATION
COMPENSATION
Do not adjust the register parameters outside of the
(Push 7)
range shown in the Tables for the Register Parame-
ters. Settings outside the ranges can cause damage This register permits the adjustment of the rate (in se-
to the components of the hydraulic system and dif- conds) that it takes for the controller to add the internal
25
EV–T100 Motor Controller
resistance compensation voltage that is applied to to to 0%. A parameter set over the maximum parameter
motor. This function will add 0.375 volts to the motor at can cause the motor or controller to become too hot.
the rate of time set in the register until the total (current x
Function Numbers Greater Than 15
resistance) compensation voltage has been added.
NOTE: For registers greater than15, push and HOLD
Range 0.0015 to 0.383 seconds the CONT key and the additional key number above 15
Set 0 to 255 to total the required register number. Example: for Func-
Resolution 0.375 volts per set unit tion Number 18, push CONT key and key 3 (15+3=18).
Example: A parameter of 20 = 0.032 seconds The display will show the selected register. After one
second, the display will show the parameter that has
Example: If 2.08 volts is set in Function Number 16 and
been set in that register.
added to the motor, this example would require 0.18 se-
conds to add a total of 2.08 volts. NOTE: The Seat Switch must be OPEN for Function
(2.08 volts/0.375 volts per unit)0.032 seconds = 0.1775 Numbers 16 through 30.
or 0.18 seconds
Function Number 16
Function Number 11 INTERNAL RESISTANCE COMPENSATION
SPEED LIMIT 1 (SL1) (Push CONT and 1)
(Slow Speed) – Tilt and Slow Auxiliary This register is used to give the pump speed better stabil-
(Push 11) ity by increasing the motor voltage during heavy loads.
This register permits the adjustment of the speed limit This parameter is set using the information from the
speed torque curve of the motor used. See the correct
(maximum battery volts applied to the motor). When
switch SL–1 is closed, the signal to TB2 on the control- setting in the “Parameter Tables”.
ler card causes the controller to apply the limit on battery The voltage selected will be added to the motor for each
volts to the motor. 100 ampere increment starting with the parameter set in
Function Number 2. The voltage selected will be added
Function Number 12
in steps of 0.375 volts until the entire voltage is added.
SPEED LIMIT 2 (SL2)
For example, a parameter of 10 will add 2.28 volts in six
(Medium Speed) – Slow Lift and Medium
steps of 0.375 volts each.
Auxiliary
(Push 12) Function Number 17
CARD TYPE SELECTION
This register permits the adjustment of the speed limit (Push CONT and 2)
(maximum battery volts applied to the motor). When
switch SL–2 is closed, the signal to TB3 on the control- WARNING
ler card causes the controller to apply the limit on battery Wrong parameters entered into the register in
volts to the motor. Function Number 17 can cause the truck to operate
differently than normal or cause damage to the con-
Function Number 13
troller. This different operation of the truck can re-
SPEED LIMIT 3 (SL3)
sult in personal injury. NEVER set Function Num-
(Push 13)
ber 17 to a parameter that is not shown for your lift
Not Connected. truck.
Function Number 14 This register permits the selection of the card type used
SPEED LIMIT 4 (SL4) for your lift truck application. See the correct setting in
Fast Lift the “Parameter Tables”.
(Push 14) Function Numbers 18 through 28
TEMPORARY DATA REGISTERS
This register uses SL4 limit switch for an input to TB6.
This function permits adjustment of the speed limit These registers can be read with the Hand Set, but the
(maximum battery volts to the motor). The range is 96% data in them changes during lift truck operation. Do not
26
EV–T100 Motor Controller
change the parameters in registers for Hand Set numbers Function Number 49
21 through 27. Hand Set number 28 is the fault indi- SPEED LIMIT 2
cator pointer and must be set to zero when all faults (Push CONT and 2 while the key switch and seat
or malfunctions have been fixed or removed from switch are closed)
the controller. This register permits the adjustment of the speed limit
for the hydraulic pump in MODE 1. The minimum pa-
CAUTION rameter is zero. Do not set the number in the register
Function 25 (temporary storage register for fault greater than the number in the register for Function
data) and Function 26 (temporary storage register Number 53.
for battery charge data) must not be changed by the
Function Number 50
user to any number above zero. Any number above
SPEED LIMIT 3
zero can cause the instrument panel display to not
(Push CONT and 3 while the key switch and seat
operate correctly and the lift truck can become dis-
switch are closed)
abled.
This parameter permits adjustment of the speed limit
(maximum battery volts to the motor). The range is 0%
Function Number 29 to 96%. There is no speed limit switch for this function.
HOURMETER (Tens/Units) This function will be disabled if the parameter in the reg-
(Push CONT and 14) ister is set to zero. Do not set the number in the register to
less than the parameter for Function Number 54. The
This register has the data for the accumulated operating maximum number in the register is 255.
hours of the hydraulic system. This register is not nor-
Function Number 52
mally changed unless a new control card is installed. If a
CONTROLLED ACCELERATION
new control card is installed, the total hours from the old
(Push CONT and 5 while the key switch and seat
control card must be entered so that the total operating
switch are closed)
hours of the hydraulic system is correctly recorded.
This register permits the adjustment of the maximum
Function Number 30 rate of acceleration in MODE 2. The parameter deter-
HOURMETER (Thousands/Hundreds) mines the time allowed to reach maximum SCR speed
(Push CONT and 15) from stop. Do not set the number in the register to less
than the parameter for Function Number 56. Do not set
This register has the data for the accumulated operating the number in the register greater than the number in the
hours of the lift truck. This register is not normally register for Function Number 48.
changed unless a new control card is installed. If a new Function Number 53
control card is installed, the total hours from the old con- SPEED LIMIT 2
trol card must be entered so that the total operating hours (Push CONT and 6 while the key switch and seat
of the lift truck is correctly recorded. switch are closed)
This register permits the adjustment of the speed limit
Function Number 48 for the hydraulic pump in MODE 2. Do not set the num-
CONTROLLED ACCELERATION ber in the register to less than the parameter for Function
(Push CONT and 1 while the key switch and seat Number 49. Do not set the number in the register greater
switch are closed) than the number in the register for Function Number 57.
27
EV–T100 Motor Controller
to 96%. There is no speed limit switch for this function. less than 8. Do not set the number in the register greater
This function will be disabled if the parameter in the reg- than the number in the register for Function Number 56.
ister is set to zero. Do not set the number in the register to
Function Number 61
less than the parameter for Function Number 58. Do not
SPEED LIMIT 2
set the number in the register greater than the number in
(Push CONT and 14 while the key switch and seat
the register for Function Number 50.
switch are closed)
Function Number 56 This register permits the adjustment of the speed limit
CONTROLLED ACCELERATION for the hydraulic pump in MODE 4. Do not set the num-
(Push CONT and 9 while the key switch and seat ber in the register to less than the parameter for Function
switch are closed) Number 57. Do not set the number in the register greater
than 110.
This register permits the adjustment of the maximum
rate of acceleration in MODE 3. The parameter deter- Function Number 62
mines the time allowed to reach maximum SCR speed SPEED LIMIT 3
from stop. Do not set the number in the register to less (Push CONT and 14 while the key switch and seat
than the parameter for Function Number 60. Do not set switch are closed)
the number in the register greater than the number in the
This parameter permits adjustment of the speed limit
register for Function Number 52.
(maximum battery volts to the motor). The range is 0%
Function Number 57 to 96%. There is no speed limit switch for this function.
SPEED LIMIT 2 This function will be disabled if the parameter in the reg-
(Push CONT and 10 while the key switch and seat ister is set to zero. The maximum number in the register
switch are closed) is 255.
28
EV–T100 Motor Controller
Regenerative Braking — 70 through –76 ly every two seconds. Every third “flash” of the display
will indicate the battery charge instead of the status
Truck Management — 90 through –99
code.
Hydraulic Pump Control — 117 through –157 The control card senses the following malfunctions:
NOTE: 1. A blank display on the instrument panel dis- • input voltages that are too high or too low,
play or the Hand Set, during operation, can mean that the • input voltages that have the wrong polarity,
diode D7 for regenerative braking has a short–circuit.
The indication for this malfunction is an open traction • input voltages in the wrong sequence or
power fuse. If D7 has a short–circuit, there is a short–cir- • correct input voltages that occur at the wrong
cuit across the battery as soon as the regenerative brak- time.
ing contactor closes and will cause the power fuse to
open. If D7 is open, the regenerative braking will not op- NOTE: A status code display does not always mean that
erate and the plugging will be too quick. there is a malfunction. A temporary operating condition
can cause a status code display.
NOTE 2. A short–circuit in the 1A contactor coil will The status codes all have a dash (–) before the numbers.
cause the lift truck to suddenly stop when operating at
If the battery is disconnected, the dash (–) will be miss-
the higher speeds. The lift truck operates correctly until
ing on the display of the Hand Set when a battery is con-
the 1A contactor is energized. When the 1A contactor is
nected again. If a status code number is indicated on the
energized, the traction motor then stops and the direc-
digital display, checks and adjustments cannot be done.
tion contactors will open.
See TABLE 8. and the following Status Code Charts to
NOTE 3. If the coil of the Field Weakening contactor find and correct the malfunction. There are no checks or
has a short–circuit, the lift truck will operate normally adjustments for the status codes. These code numbers
until the FW contactor is energized. Then the lift truck are only codes to help identify a possible malfunction.
will lose power and the direction contactors will open. TABLE 8. has a short description of the different status
codes.
The control card in the motor controller has a
troubleshooting system that continuously checks the There is a Status Code Chart in this section for each
static and operating conditions of the control and power status code. These charts have a more complete descrip-
circuits for the motor. The control card will indicate a tion of the status code, the circuit that has generated the
status code on a display connected to plug PY if the input for the status code, the symptom and the possible
troubleshooting circuits find a condition that is not nor- causes.
mal. Some lift trucks can have an instrument panel dis- REGISTER MAPS
play that will indicate the status codes from the control
cards for the traction motor and hydraulic pump motor. The information in the Register Maps shown in
TABLE 9. and TABLE 10. is not needed by most ser-
Different control cards are used in the electric lift trucks. vice people. This additional technical information is for
A replacement control card must have the same part service engineers who have special troubleshooting re-
number as the control card that was removed. A bad quirements. These registers and their descriptions are
control card can not be repaired by service persons and designed by the General Electric Company. Many of
must be replaced. these registers are programmed by Hyster Company to
do certain functions. These register maps as pro-
Status Codes (See TABLE 8.) grammed by Hyster Company are shown in the section,
The status codes are code numbers for malfunctions that EV–T100 TRANSISTOR MOTOR CONTROL-
the control card can sense. The control card will indicate LER, Paramter Tables, 2200 SRM 596.
this code number on the digital display of the instrument NOTE: The number of the EEPROM register is off–set
panel display (optional on some units) or the display on by one from the PC Register Number and the Function
a Hand Set. The control card will illuminate the numbers Number in the Register Map Tables. The EEPROM be-
of the status code on the display. The status codes are gins its count from zero (0) while the PC and Hand Set
twice illuminated (“flash”) on the display approximate- begin their count from one (1).
29
EV–T100 Motor Controller
* Not used on all models of lift trucks. Status Codes in this group will flash on the display.
NOTE: Motor speed is decreased when a status codes –41 or –141 are indicated.
30
EV–T100 Motor Controller
31
EV–T100 Motor Controller
32
EV–T100 Motor Controller
33
EV–T100 Motor Controller
34
EV–T100 Motor Controller
35
EV–T100 Motor Controller
TABLE 10. REGISTER MAP FOR CONTROL CARD ZP (HYDRAULIC PUMP) (Continued)
EEPROM PC Hand Function Access Restrictions
Register Function Set (HS) By:
Number Number Function
Number
36
EV–T100 Motor Controller
TABLE 10. REGISTER MAP FOR CONTROL CARD ZP (HYDRAULIC PUMP) (Continued)
EEPROM PC Hand Function Access Restrictions
Register Function Set (HS) By:
Number Number Function
Number
37
EV–T100 Motor Controller
TABLE 10. REGISTER MAP FOR CONTROL CARD ZP (HYDRAULIC PUMP) (Continued)
EEPROM PC Hand Function Access Restrictions
Register Function Set (HS) By:
Number Number Function
Number
38
EV–T100 Motor Controller
39
EV–T100 Motor Controller
40
EV–T100 Motor Controller
NEGATIVE
NEGATIVE
41
EV–T100 Motor Controller
42
EV–T100 Motor Controller
43
EV–T100 Motor Controller
44
EV–T100 Motor Controller
45
EV–T100 Motor Controller
No change between code –23 and code –24. Do all of the Possible
C1 RB D4 D3
Cause checks for this Status Code. If the problem is not found,
do the checks in code –23.
Possible Cause
Most common cause is that the contacts on one of the direction +
contactors or the RB contactor does not close correctly to make
R
an electrical connection. – F
Circuit Clean the contact of the direction contactors and the RB contactor
F R
Traction with alcohol. New contacts can have a surface condition that D7
prevents conducting electric current. Check that the contacts
T2
close correctly. 1A
Malfunction of coil circuit for Forward and Reverse contactor. TR1
Check for welded contacts or contactors that do not close
correctly.
Malfunction of RB contactor. NOTE: The PS coil does not apply when the
lift truck has “On–Demand power steering.
Check that the contacts and contactor will close correctly.
Check for an open circuit or loose connections between the
positive side of the RB contactor coil and PB2. +
Open motor circuit. +
F +
R
Check for an open circuit or loose connections in the motor circuit 1A +
from the A1 connection to the A2 connection on the SCR control PB4 +
panel. L
PB5 +
PS
Malfunction of the 1A, RB, PS, or FW contactors. PB6 FW +
Do the checks described in Status Code –23. PB2 RB
PB3
PA1
PZ8
46
EV–T100 Motor Controller
47
EV–T100 Motor Controller
48
EV–T100 Motor Controller
49
EV–T100 Motor Controller
50
EV–T100 Motor Controller
51
EV–T100 Motor Controller
Yes only close when the key switch is opened and closed.
C1 RB D4 D3
Possible Cause
Malfunction of TR1.
Check for open circuit or loose connections between
transistor and PZ4 (RED wire). +
The OFF time for TR1 is not within specifications. No field R
test is possible. Replace TR1 after the other checks have – F
Circuit been done and no other problem is found.
F R
Traction D7
T2
1A
TR1
52
EV–T100 Motor Controller
Circuit Check from the current sensor to the control card for open A2
or loose connections.
Traction
Power cables are connected wrong in motor circuit.
Check that the power cables are connected correctly in the
motor circuit.
53
EV–T100 Motor Controller
54
EV–T100 Motor Controller
Yes only close when the key switch is opened and closed.
C1 RB D4 D3
Possible Cause
Bad connection or not regular connection in battery
power circuit.
Emergency power disconnect opened during +
regenerative braking.
R
Line contactor L opened during regenerative braking. – F
Circuit
Check the power fuse and battery connections that can F R
Traction open during regenerative braking. D7
1A
TR1
55
EV–T100 Motor Controller
56
EV–T100 Motor Controller
57
EV–T100 Motor Controller
Traction motor brushes are worn. The sensor has closed to BRUSH WEAR SENSOR
battery negative.. TRACTION MOTOR
A1
Circuit Replace the brushes.
ARMATURE
58
EV–T100 Motor Controller
59
EV–T100 Motor Controller
Circuit
Hydraulic
Pump P
Contactor
T2
60
EV–T100 Motor Controller
61
EV–T100 Motor Controller
62
EV–T100 Motor Controller
–
Circuit
Hydraulic
TR1
Pump
63
EV–T100 Motor Controller
64
EV–T100 Motor Controller
REPAIRS
13
12
3
14
15 2
1
17
7 6 5
11 10 9 8
TRANSISTOR CONTROL FOR BOTH TRACTION
MOTOR AND HYDRAULIC PUMP MOTOR
16
12
1
17
65
EV–T100 Motor Controller
2
17
8
3 4 11 9 7
14
6
5
13
2
17
8
3 4 11 9 7
10. CONTACTOR 1A
1. TRANSISTOR MOTOR CONTROLLER 11. FUSE 2, HYDRAULIC PUMP CIRCUIT
(ALSO SEE FIGURE 3.) 12. STEERING PUMP CONTACTOR
2. FIELD WEAKENING CONTACTOR (UNDER FUSE PANEL 17)
3. FORWARD DIRECTION CONTACTOR (F) 13. HYDRAULIC PUMP CONTACTOR
4. REVERSE DIRECTION CONTACTOR (R) 14. ELECTRONIC DRIVER, HYDRAULIC
5. REGENERATIVE BRAKING CONTACTOR (RB) PUMP CONTACTOR
6. DIODE D7 ASSEMBLY, 15. TMM1 MODULE
REGENERATIVE BRAKING 16. TRANSISTOR CONTROLLER,
7. FUSE 4, POWER STEERING CIRCUIT HYDRAULIC PUMP MOTOR
8. CONTACTOR L (ALSO SEE FIGURE 3.)
9. FUSE 1, TRACTION CIRCUIT 17. FUSE PANEL (FU 7, FU 3, FU 5, FU 6)
FIGURE 10. TYPICAL CONFIGURATIONS OF THE EV–T100 MOTOR CONTROLLER IN
E2.00–3.20XM (#45–65XM) LIFT TRUCKS
66
EV–T100 Motor Controller
GENERAL actuator bar to release the seat brake when the op-
erator in not in the seat. Put the test equipment so
The parts in the EV–T100 motor controller module can that you can see it from the operator area. You can
not be repaired. Any component that has a fault must be operate the controls with your hand and also make
replaced. The status codes will normally indicate the the voltage measurements.
component that has a fault. The procedures described in
this section for the motor controller module are to check Make sure you disconnect the battery and separate
that the indicated fault is correct. the connector before you disassemble any part of the
controller. The capacitor C1 stores electrical energy
The replacement of the contactor contacts is a normal
and can cause injury if a person discharges a capaci-
maintenance procedure. Disassembled views of the
tor through parts of the body. Capacitor C1 is physi-
contactors are shown in this section.
cally three capacitors connected in parallel to be-
The repair of the connectors to the control card is de- come one large capacitor. AFTER the battery is dis-
scribed in this section. connected, make sure you also discharge the capaci-
tor C1. Put a 100 ohm 2 watt resistor across the posi-
WARNING tive (+) and negative (–) of the capacitor for a mini-
Some voltage measurements must be made with the mum of three seconds.
SRO circuit complete. Make sure the drive wheels
are raised from the surface before doing NOTE: The bolts and screws connected to the elec-
troubleshooting. If you are working alone, put a tronic components are normally metric sizes. Make sure
weight in the seat to close the seat switch. If your lift that you use the correct fastener for the part that has been
truck has a seat brake, use a block behind the lower disassembled.
1. POWER
TRANSISTOR TR1
2. SUPPRESSOR
ASSEMBLY FOR TR1 1
3. CAPACITOR C1
(C1a, C1b, C1c)
4. CONTROL CARD
5. SUPPRESSOR
ASSEMBLY FOR 6, 7
DIODES D3 AND D4
6 & 7. LOCATION OF
DIODES D3 AND D4 2 5
3 3
67
EV–T100 Motor Controller
1
2
18
3 1. CAPACITOR C1 (3)
2. CONTROL CARD
3. BASE PLATE
17 4. SUPPRESSOR, POWER
TRANSISTOR
16 5. POWER TRANSISTOR TR1
ASSEMBLY
6. HEAT SINK, DIODES
15 7. DIODE MODULE D3
8. DIODE MODULE D4
14 9. TERMINAL POST
10. FLEXIBLE BUS BAR
11. CURRENT SENSOR
13 12. FLEXIBLE BUS BAR
4 13. TERMINAL POST
12 7
14. BUS BAR
8 15. BUS BAR
6 5
16. BUS BAR
17. SUPPRESSOR, DIODES D3
9
AND D4
18. CAPACITOR SUPPORT
ASSEMBLY (2)
11 10 10
FIGURE 12. CONFIGURATION OF THE EV–T100 MOTOR CONTROLLER MODULE
68
EV–T100 Motor Controller
69
EV–T100 Motor Controller
70
EV–T100 Motor Controller
2
1
1 6
3
4 4
4
5
3 3
12180
2 1
5
6 1. POWER TERMINALS
1. POWER TERMINALS 2. CONTACTS
2. NC CONTACTS 3. SUPPRESSOR
3. NO CONTACTS 4. COIL TERMINALS
4. COIL TERMINALS 5. MOUNT BRACKET
5. MOUNT BRACKET 6. COIL
6. COIL
FIGURE 19. TYPICAL CONTACTOR
FIGURE 18. DIRECTION CONTACTOR ASSEMBLY (REGENERATIVE BRAKING
SHOWN)
71
EV–T100 Motor Controller
5
4 9
11
8
14
4 10
1. BASE–MAGNET 7 6
13
2. COIL 21
3. FRAME–MAGNET 22
4. BUS
5. BUS 20
6. SPACER 12 21
7. CLAMP–BUS
8. BUS 3 17 20 22
9. COVER 18 17
10. BUS 19
11. BUS 18
12. SPRING–RETURN 2 18
19
13. ARMATURE
17 18
14. BASE–BUS
15. CARRIER–MOVABLE TIP 15, 17
16. BUSHING–PLUNGER 3 16
17. TIP–MOVABLE
18. SEAT–SPRING 1
15,
19. TIP SPRING 16
20. INSULATION–UPPER BUS
21. NUT
12180
22. WASHER 2
Coil. Check the coil with an ohmmeter for an open cir- ohmmeter to the opposite terminals and measure the re-
cuit or a short–circuit. Replace the coil if it is damaged. sistance. Use the highest resistance indication.]
Make sure the coil wires are connected again to the cor-
rect terminals. The coils in the contactors for the hydrau- CONTROL CARD
lic pump and the regenerative braking have an external NOTE: Do NOT remove the circuit board from the case
suppressor. The coil and the suppressor can be checked when replacing a control card. There are no internal re-
separately with an ohmmeter. [A suppressor diode (and pairs that can be made by service personnel. The control
sometimes a resistor in series) is part of the coil. The di- card and case must be replaced as a unit. There are spe-
ode will cause the ohmmeter to indicate a difference in cial repair services available that can repair damaged
resistance in one direction. Reverse the probes of the control cards. See your dealer for Hyster lift trucks.
72
EV–T100 Motor Controller
1
7
2
3
6
3
3 3 1. CONTROL CARD
(TRACTION OR
5 HYDRAULIC PUMP)
2. TB SCREW
TERMINALS (6)
3. PLUG GUIDES
4. PLUG PA (6–PIN)
(WIDE GUIDES)
3 5. PLUG PB (6–PIN)
4 (CLOSE GUIDES)
6. PLUG PY (14–PIN)
7. PLUG PZ (14–PIN)
12668 3 12671
73
EV–T100 Motor Controller
Brush Wear Indicators ing correctly. The thermal switch can be replaced if it is
damaged. However, the motor must be disassembled to
The brush wear indicators illuminate when the motor replace the thermal switch.
brushes must be replaced. The sensor wires for the brush
wear indicators are an insert in the brush material when
it is made. The sensor wires are insulated from the brush
WARNING
material. When the brush wears within approximately Prevent damage and injury if the lift truck moves.
1.5 mm (0.060 in) of the brush lead, the insulation be- Raise the drive wheels from the floor during these
tween the sensor wire and the brush material is de- tests.
stroyed. The connection between the brush and the sen-
sor wire causes the indicator to illuminate. Disconnect the sensor wires, one at a time, from outside
of the motor case. Touch the end of the sensor wire to
The operation of the brush wear indicators can be
battery negative. The warning light will illuminate if the
checked during periodic maintenance. The battery must
circuit is operating correctly. The motor brushes must be
be removed from the lift truck for access to the motors.
replaced when they are worn. If equipped with brush
Disconnect the sensor wires from the outside of the mo- wear indicators, the condition of the commutator and
tor case. Touch the ends of the sensor wires together. the motor brushes must still be checked during periodic
The warning light will illuminate if the circuit is operat- maintenance.
74
EV–T100 Motor Controller
75
EV–T100 Motor Controller
to the gate. When the gate signal is applied, the transis- frequency is high, there is more heat generated in the
tor permits current flow. When the gate signal is MOSFET or IGBT and more power loss. The control-
stopped, the current flow through the transistor stops. ler for the hydraulic pump operates at a lower frequen-
cy of 2 kHz because the operation of the hydraulic sys-
NOTE: Too much heat will quickly destroy a power
tem prevents hearing the lower frequency noise.
transistor. A difficult design problem has been to de-
velop a semi–conductor material that will permit a
large current flow (example: 400 amperes) and be able 1 2
to quickly start and stop the current flow. Most of the
D S
heat generated within a power transistor comes from
the transition between the ON and OFF conditions. S
The transition time for a good power transistor is
approximately 75 nanoseconds (a nanosecond = one
billionth of a second). G
1 2 D = DRAIN
D S S = SOURCE
G = GATE
TP = THERMAL PROTECTOR
G S
FIGURE 25. TYPICAL IGBT ARRANGEMENT
76
EV–T100 Motor Controller
Traction Circuit
OFF OFF OFF
50% The control card supplies approximately 5.0 volts to
AVERAGE
MOTOR the accelerator potentiometer for the traction circuit.
BATTERY VOLTAGE
VOLTAGE (SPEED) When the accelerator potentiometer is connected and
10%
correctly adjusted, the voltage is 3.5 to 3.7 volts when
0% measured between the accelerator potentiometer and
TIME LOW SPEED battery negative. This voltage is measured at the slow-
50% est speed (CREEP speed) of the lift truck and the ac-
SPEED celerator potentiometer is at its highest resistance. The
100%
ON ON ON accelerator potentiometer decreases this voltage by de-
AVERAGE
OFF OFF MOTOR creasing the resistance between the control card and
VOLTAGE
(SPEED) battery negative. This accelerator voltage controls the
50% oscillator in the control card when the accelerator po-
BATTERY tentiometer is moved by the operator. The oscillator
VOLTAGE controls the ON time of TR1 and controls the travel
speed of the lift truck. When the accelerator pedal is
0% pushed farther down, the control voltage to the control
TIME card decreases. The maximum ON time (fast travel
MEDIUM SPEED
speed) occurs when the control voltage is 0.0 to 0.2
MAXIMUM
OFF OFF SPEED volts. Most lift trucks are equipped with a by–pass cir-
100% 96%
cuit (1A) that is energized when the accelerator voltage
ON ON ON decreases to less than 1.0 volts. The 1A by–pass circuit
AVERAGE disables the TR1 control and applies battery voltage di-
MOTOR
50% VOLTAGE rectly to the traction motor.
(SPEED)
The maximum average voltage to the motor gives the BASIC CIRCUIT OPERATION
highest operating speed. This voltage occurs when the
The controller is energized when the battery is con-
ON time is long compared to a short OFF time. This
nected. A resistor across the terminals of the line con-
maximum speed sends approximately 96% of the bat-
tactor L is an electrical path to charge the capacitor C1
tery voltage to the motor. Most EV–T100 motor con-
in approximately two seconds. The controller then
trollers have a 1A by–pass contactor and a field weak-
makes start–up checks.
ening contactor to increase the maximum travel speed
of the lift truck. The 1A by–pass contactor also permits NOTE: Capacitor C1 is physically three capacitors
full battery power to the motor during full speed opera- connected in parallel to become one large capacitor.
77
EV–T100 Motor Controller
NOTE: This motor controller is equipped with a line Pulse Monitor Trip (PMT)
contactor between the positive power cable of the bat- (Traction Circuit Only)
tery and the motor controller. This line contactor is the
primary battery disconnect if an electrical fault is The PMT circuit is part of the control card function.
sensed by the motor controller. When the SRO checks are complete, the control card
checks for three conditions that can cause uncontrolled
operation of the lift truck:
SRO Circuit (Traction Circuit Only)
• The PMT circuit checks that the voltage across
TR1 is between 12% and 88% of the battery volt-
The lift truck is equipped with a safety circuit, called
age. If the voltage across TR1 stays at a low volt-
the ”Static Return to OFF” (SRO) circuit, that prevents
age, there is a fault in the traction circuit. A short–
the operation of the lift truck if the starting sequence is
circuit across TR1 or the contacts on contactor
not correct. The function of the SRO circuit is to make
1A welded closed, will cause this fault. The line
sure the operator is in the seat and ready to operate the
contactor L will not close.
controls. The starting sequence:
• If the control card senses a short–circuit (low
a. The operator must be on the operator’s seat and voltage) across diode D3, the line contactor L
the seat switch closed. (The seat switch closes will not close. A direction contactor will not
when the weight of the operator is on the seat.) close.
ÉÉÉ
switch each send a signal voltage to a timer circuit.
indicates positive voltage.
Both voltages must be sent to the timer circuit before
the timer will send a voltage signal to terminal TB3 on
the control card. The timer circuit has a six second de- ÉÉÉ indicates battery negative.
lay if the seat switch is opened. This delay permits the INDUCTION CURRENT FROM THE
operator to change position in the seat without causing MOTOR
the lift truck to stop. The voltages from the parts to the
SRO circuit are sent to the control card. The SRO cir- When a DC motor is controlled by a pulsed circuit, the
cuit is reset when the START switch or a direction magnetic field in the armature and motor field is con-
switch is momentarily opened. tinuously expanding and decreasing. This expansion
and decrease of the magnetic field can be lost energy
for doing work unless the controller is designed to use
The control card must sense battery voltage at termi- this energy. A capacitor C1 and a diode D3 is added to
nals TB4 and TB3 (seat switch closed), and at TB2 the circuit for this purpose.
(START switch), before a voltage signal at TB5 or TB6
or the control card will not permit a direction contactor Capacitor C1 is charged as a temporary storage for part
to close. of the battery energy during the TR1 OFF time.
78
EV–T100 Motor Controller
TR1 ON TIME: Capacitor C1 discharges and adds When TR1 goes OFF, the decreasing magnetic field
to the battery current to motor. At a current draw of generates a voltage and current in the motor. Diode D3
100 amps and 50% ON time, approximately 50 permits the current to flow through the field and arma-
amps comes from the battery and 50 amps comes
from the capacitor C1.
ture again to do work. See FIGURE 27. (This current is
often called the “flyback current.”) The torque of a DC
motor is directly proportional to the amount of current
50 amps 50 amps flow through it. This control changes battery current at
2 battery voltage into a higher motor current at lower
ÉÉ
3
100 amps motor voltage. Motor current will be higher than bat-
6
+
ÉÉ1 tery current draw except when TR1 is operating at
ÉÉ
4 maximum ON time. Most of the motor current comes
É ÉÉ
–
É
F R from the battery at high speeds. (High current draw
É ÉÉ ÉÉ
5
from the battery is to be avoided if possible, because it
É ÉÉ ÉÉ ÉÉ
É
F R is less efficient.) The 1A by–pass contactor is closed at
É ÉÉ ÉÉ
maximum speeds to by–pass TR1 and connect the bat-
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉ ÉÉ
tery voltage directly across the motor. The 1A by–pass
circuit is described later in this section.
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉ ÉÉ
7 8
É
When TR1 is ON, capacitor C1 discharges its energy
and adds to the current flow from the battery through
the motor.
TR1 OFF TIME: Capacitor C1 charges from the
battery. The decreasing magnetic field in the motor CONTROL CARDS
circuit generates a voltage and current. Diode D3
permits the current to flow through the field and The control cards for the traction circuit and the hy-
armature again to do work. draulic circuit will be described separately in the fol-
lowing paragraphs.
NOTE: The configuration of the controller divides the
É
2 base plate into three groups:
50 amps 3
É
100 amps
6 a. Traction controller group
É
+ 1
4 b. Contactor group
ÉÉ É F
The three groups of components are fastened to the
R
ÉÉ É
mounting plate on the counterweight. Typical control-
ÉÉ É
ler configurations are shown in FIGURE 3. (If the tran-
ÉÉ É
sistor controller for the hydraulic pump motor is not
used, a single contactor for the hydraulic pump motor
ÉÉÉÉÉÉ
ÉÉ É
7
8 is installed in that position.)
The control card makes the SRO and PMT checks as
1. BATTERY 5. MOTOR FIELD
2. LINE CONTACTOR 6. DIODE D3 part of the logic sequence. The control card only per-
3. CAPACITOR C1 7. TR1 mits lift truck operation when no fault is sensed. The
4. MOTOR ARMATURE 8. CONTACTOR 1A control card checks and controls the functions de-
NOTE: The current flows in this illustration are an scribed in the following paragraphs.
example. Actual current flows depend on the Control Card Adjustments (Traction Circuit)
operating conditions.
The control card checks the current in the traction cir-
FIGURE 27. INDUCTION CURRENT
cuit and controls the current to prevent damage. The
control card has several control adjustments.
79
EV–T100 Motor Controller
The control card for the traction circuit has a control nected between the positive terminal and the contactor
adjustment called “CREEP”. This adjustment controls A1 terminal.
the minimum current level in the traction circuit when
the direction contactors are closed. This adjustment The 1A By–pass Circuit permits the battery to be con-
can be changed to meet the needs of a specific applica- nected directly to the traction motor. This circuit dis-
tion. The CREEP adjustment controls how far the ac- connects the control of the TR1 circuit and is used for
celerator pedal moves between the closing of the maximum power from the traction motor. When the
START switch and the application of enough power to battery is connected to the traction motor through the
move the lift truck. This adjustment is only made after 1A by–pass circuit, the maximum voltage available to
the adjustment between the accelerator pedal and the the traction motor is increased by approximately 4%.
accelerator potentiometer is correct. The control card controls the operation of the 1A cir-
cuit. A 1A TIME adjustment permits the controller to
The “C/A” (Controlled Acceleration) adjustment
begin the operation of the traction motor before the 1A
controls the maximum rate that the average voltage is
contactor closes. This time delay prevents full battery
increased by the controller to accelerate the traction
current being applied across the traction motor when it
motor. This maximum rate of acceleration is not con-
is not rotating. (Full battery voltage applied across a
trolled by the accelerator pedal for maximum accelera-
stalled traction motor causes a large current draw. This
tion. A high rate of acceleration increases the wear on
large current draw causes a large amount of heat in the
the brushes of the traction motor. The acceleration time
motor and wastes battery energy.) This adjustment also
can be adjusted for the operating conditions of the user.
permits smoother operation of the lift truck. The con-
The acceleration rate can be adjusted to give a smooth
trol card begins 1A TIME when the accelerator volt-
acceleration for better load handling.
age is decreased to less than 1.0 volts. 1A TIME is
normally 1 to 3 seconds. The full battery power is
1 available to the traction motor through the 1A circuit
after the time delay 1A TIME.
2 2
ÉÉ
3
1. SENSOR WIRES
6
ÉÉ
2. SENSOR SHUNT
+ 1
É ÉÉ
4
FIGURE 28. MOTOR CURRENT SENSOR
É ÉÉ ÉÉ F R
– 5
The “C/L” (Current Limit) adjustment will control
É ÉÉ ÉÉ É
ÉÉ
ÉÉÉÉ
É ÉÉ ÉÉ É
ÉÉ
F R
the pulse length if the current flow reaches the limit set
by the adjustment. The traction circuit has a current
É ÉÉ ÉÉÉÉ
É
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉ
sensor in the power circuit in series with the traction
É
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉ
motor. All of the current that flows through the traction 7 8
É É
motor flows through the current sensor. The current
sensor is a shunt with two sensor wires connected. See
FIGURE 28. The metal of the shunt has a small resis- 1. BATTERY
2. LINE CONTACTOR
tance between the two sensor wires. This small resis- 3. CAPACITOR C1
tance sends a signal voltage to the control card. This 4. MOTOR ARMATURE
signal voltage increases as the motor current increases. 5. MOTOR FIELD
The control card compares the signal voltage with the 6. DIODE D3
7. TR1
C/L current limit adjustment. When the signal voltage 8. CONTACTOR 1A
reaches the limit set on the C/L, the control card re-
duces the pulse width. The current sensor is found con- FIGURE 29. 1A BY–PASS CIRCUIT
80
EV–T100 Motor Controller
“PLUG”. The “PLUGGING” function uses the trac- current through the armature again. This reduction of
tion motor as an electric brake to slow or stop a lift the opposite induction current permits the lift truck to
truck. When a lift truck is being stopped, the motion of stop more smoothly.
the lift truck causes the traction motor to rotate and op-
erate like a generator. The voltage generated across the
The control card for the traction circuit has a PLUG
motor armature changes polarity. Plugging uses the re-
adjustment. This adjustment controls the maximum ap-
verse polarity of the current flow generated by the ar-
plication of the plugging current. The position of the
mature of the traction motor to decrease the speed of
accelerator pedal controls the plugging distance up to
the lift truck. Plugging generates heat in the traction
the maximum application. This adjustment can be
motor.
changed as needed for an operator. The shorter the
plugging distance, the faster is the wear on the traction
motor brushes.
É
maximum application of regenerative braking during
operation. The position of the accelerator pedal by the
É
9 6
operator controls the plugging distance up to the limit
É
+ 1 3
4 set by the REGEN C/L adjustment.
É É F R
É É
– 5
Regenerative Braking. When a lift truck is being
É É ÉÉÉ
ÉÉ F R stopped, energy is generated by the traction motor. The
É
É É ÉÉÉÉ
lift truck causes the traction motor to rotate and operate
É ÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉ
like a generator. Plugging uses battery energy in oppo-
É 7
sition to the energy generated by the traction motor.
É É ÉÉ
8 This energy generates heat in the traction motor. Lift
trucks used in heavy duty operations can generate
1. BATTERY enough heat to damage the traction motors and cause
2. LINE CONTACTOR the motor brushes to wear rapidly.
3. CAPACITOR C1
4. MOTOR ARMATURE
5. MOTOR FIELD
Regenerative braking returns the energy generated by
6. DIODE D3
7. TR1 the traction motor to the battery. The regenerative
8. CONTACTOR 1A braking contactor opens during regenerative braking.
9. DIODE D4 When the voltage generated by the traction motor is
10. CURRENT SENSOR, TRACTION CIRCUIT
less than the battery voltage, the lift truck will be mov-
FIGURE 30. PLUGGING CIRCUIT ing slowly. The contactor for regenerative braking then
closes and plugging is used to stop the slower moving
lift truck. Regenerative braking generates less heat in
the traction motor and reduces brush wear. Another
Plugging is energized when the direction switches in
electric circuit must be added to the motor controller to
the direction control lever is moved to the opposite di-
control this operation. The energy generated during re-
rection from which the lift truck is traveling. The direc-
generative braking must be controlled within limits so
tion contactors will change to their opposite positions
that the parts of the electric circuit are not damaged.
and reverse the current flow through the motor field.
The adjustments used to control regenerative braking
The current generated in the traction motor now flows
are:
opposite to the current flow from the battery. The lift
truck will stop very quickly if the induction current is
not controlled. A diode D4 permits part of the induc- REGEN C/L (Regenerative Braking Current Limit)
tion current from the armature to flow with the battery REGEN D.O. (Regenerative Braking Drop Out)
81
EV–T100 Motor Controller
82
EV–T100 Motor Controller
É
11 to make the lift truck go up the slope.
É
2 3
Accelerator Control
ÉÉ É 6
ÉÉ É
The control card supplies approximately 5.0 volts
+ 1
É ÉÉ É
4 through terminal PZ6 to the accelerator potentiometer.
É ÉÉ É
F R The voltage from the accelerator potentiometer (volt-
– age divider) is sensed at terminal TB1 of the control
É ÉÉ ÉÉ É
RES
10 signal at terminal TB1 to control the speed of the lift
É ÉÉ ÉÉÉÉ ÉÉÉÉÉÉ
ÉÉ É
F R
truck.
É ÉÉ ÉÉÉÉÉÉ É
É
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉ
The voltage signal from the accelerator potentiometer
9 is 0–5 volts. The voltage is normally adjusted to
É
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉ 7
8 3.5–3.7 volts. At 3.50–3.7 volts, the lift truck will
É ÉÉ
1. BATTERY É move at CREEP speed. The 1A TIME will begin its
cycle at 1.0 volts so that the 1A contactor can close.
2. LINE CONTACTOR The maximum speed of the lift truck when operating in
3. CAPACITOR C1 the transistor control range occurs when the voltage is
4. MOTOR ARMATURE
5. MOTOR FIELD 0.0–0.2 volts. The 1A contactor applies battery voltage
6. DIODE D3 directly to the traction motor.
7. TR1
8. CONTACTOR 1A TRANSISTOR CONTROL
9. FIELD WEAKENING (FW) CONTACTOR (HYDRAULIC PUMP MOTOR)
10. FIELD WEAKENING (FW) RESISTOR
11. CURRENT SENSOR, TRACTION CIRCUIT The control card for the hydraulic pump motor is not
FIGURE 32. FIELD WEAKENING CIRCUIT the same as the control card for the traction circuit.
This control card has a different label. The electronic
function for speed control is the same, but the many
functions necessary for control of a traction circuit are
not needed for the hydraulic pump motor. A contactor
If the lift truck begins to travel up a ramp, the armature
is not used in the power circuit. The 325 ampere fuse
current will increase. When the armature current in-
for the hydraulic pump circuit is found on the bus bar
creases 2.75–3.0 times the minimum armature current,
near above the contactor 1A.
the F.W.D.O. will open the field weakening contactor.
If the accelerator pedal is moved to a slower speed, the This control card does not have an SRO check nor a
control card will open the field weakening contactor. PMT check. The TR1 is in parallel with the TR1 of the
traction circuit. If TR1 for the hydraulic circuit has a
“RAMP START” is a function of the EV–T100 con- short–circuit, the line contactor L1 will open. The main
trol card for the traction circuit. This function permits control valve is an open center valve and the hydraulic
an operator to stop a lift truck with a load when going function will stop when the hand lever is returned to
up a slope. If the operator does not change the direction the NEUTRAL position. The transistor controller for
controls, the lift truck can be started again on the slope. the hydraulic pump motor controls the motor at three
A lift truck will often roll backward a little distance speeds:
when starting again on a slope. If the operator does not
Speed 1 is for the TILT function and for optional func-
change the direction controls, the control card will not
tions that require the third or fourth spool of the main
sense the reverse operation of the motor armature and
control valve (slow speed for some attachments).
will apply enough power to go up the slope. If the op-
erator has changed the direction controls, the control Speed 2 is for the low speed LIFT function and high
card will sense that the expected operation is PLUG- speed operation of an optional function that requires
GING when the lift truck rolls backward. The control the third spool of the main control valve.
83
EV–T100 Motor Controller
Speed 4 is only for the high speed LIFT function. spring holds the contacts of a switch closed, the switch
This speed applies full battery voltage across the hy- is called normally closed (NC).
draulic pump motor. The SPD 3 adjustment is not used. Some lift trucks have an transistor control for the hy-
The control card sends three reference voltages to the draulic pump motor. Some lift trucks also have an elec-
switches controlled by the linkage to the main control tronic driver that energizes the coil for the hydraulic
valve. When a contact on a switch is closed, the refer- pump contactor.
ence voltage is connected with battery negative and the Lift trucks are equipped with contactors for regenera-
control card senses the change in the reference voltage. tive braking, 1A, and field weakening circuits. These
The voltage controlled oscillator in the control card contactors have contactors with one set of normally
causes TR1 to operate at a certain frequency (see the open contacts. See FIGURE 33. When the lift truck
paragraphs that describe Electronic Speed Controls). does not have an transistor controller for the hydraulic
The speeds of operation can be adjusted for an operat- pump motor, the hydraulic pump contactor also has
ing application. one set of NO contacts.
A typical set of direction contactors are shown in
FIGURE 34. The direction contactors (FORWARD
2 and REVERSE) each have two sets of NC and NO
1
contacts. When a coil for a direction contactor is ener-
6 gized, the NO contacts close and the NC contacts open.
3
This design prevents the contacts from being closed in
the wrong sequence.
1 3 1
4
2 1 1
5
1. POWER TERMINALS
2. CONTACTS 4 4
3. SUPPRESSOR
4. COIL TERMINALS
5. MOUNT BRACKET 5
6. COIL 2 2
12180
FIGURE 33. TYPICAL CONTACTOR
ASSEMBLY (REGENERATIVE BRAKING
SHOWN)
6
1. POWER TERMINALS
2. NC CONTACTS
CONTACTORS 3. NO CONTACTS
4. COIL TERMINALS
Contactors are switches, controlled by electromagnets, 5. MOUNT BRACKET
that close and open a power circuit. The control card 6. COIL (THE SUPPRESSOR IS ADDED
has internal electronic drivers and the electronic driv- TO THE OUTSIDE OF THE COIL)
ers control the current to the coils of the electromag- FIGURE 34. DIRECTION CONTACTOR
nets for the contactors. The electromagnetic field in the
coil moves the armature against spring pressure to CIRCUIT PROTECTION
close the contact. When the coil is deenergized, the
Traction Circuit Fuse
spring pressure moves the armature and opens the con-
tacts. When a spring holds the contacts of a switch The 500 ampere fuse for the traction circuit is found on
open, the switch is called normally open (NO). If a the motor controller between the (+) bus bar and the
84
EV–T100 Motor Controller
anode of TR1. If the current flow becomes great will damage power transistors and diodes. Suppressors
enough to damage the traction circuit because of a are included in the controller to prevent electrical noise
short–circuit or electrical overload, the fuse will fail. from entering transistors, diodes and the control card
and damaging the parts. The suppressors can be a vari-
Current Limit ation of diodes, resistors and capacitors in a small plas-
tic block.
TR1 will become damaged from heat unless the cur-
rent flow has limits. A current sensor is installed in the
TRUCK MANAGEMENT MODULE (TMM1)
traction circuit between the armature and battery nega-
tive. The current sensor sends a voltage signal to the The Truck Management Module is a multi–function
control card. The control card compares the adjustment accessory card that can be used to give additional sta-
C/L with the signal from the current sensor. If the cur- tus codes or operator warnings on the instrument panel
rent flow reaches the limit, the control card overrides display. If a lift truck has brush wear indicators and
the other signals to the oscillator. The pulse width and motor temperature switches and does not have a tran-
frequency are decreased to decrease the average motor sistor controller for the hydraulic pump motor, a
current. TMM1 card is added to the controller. The TMM1 re-
ceives the signals from the brush wear sensors and mo-
Thermal Protection tor temperature switches and sends the signals through
the traction controller to the instrument panel display.
The parts of the traction circuit will be damaged by too
much heat. A heat sensor is connected to the TR1 heat
sink. When the temperature increases towards the de-
sign limit [85°C (185°F)], the resistance in the sensor
increases. This increase in resistance decreases the
TR1 ON time by decreasing the the pulse width and
frequency to TR1. The average motor current is de-
creased to prevent damage. When the heat sink cools,
the thermal protection will return the control to normal
operation. This input signal overrides all other input
signals (except the 1A signal) to the oscillator during
lift truck operation.
Suppressors
Electrical noise is high voltage pulses caused by other FIGURE 35. TRUCK MANAGEMENT
electric parts operating momentarily. Electrical noise MODULE (TMM1)
85
EV–T100 Motor Controller
NOTES
86
EV–T100 Motor Controller
87