Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

n°150

development of
LV circuit
breakers to
standard IEC 947-
2
Etienne Blanc

Having graduated as an IEG


Engineer in 1968, he joined
Merlin Gerin in 1970.
For three years he was in charge of
LV technical literature in the
Communication Department, which
he left to join the Research,
Development and Quality
Department where he was engaged
in network research (dynamic
stability, protection, discrimination,
harmonic currents and security...).
He moved to the Industrial
Circuit-breaker Department in 1983
where he now works as a Product
Manager.

E/CT 150 first published november 1991


Cahier Technique Merlin Gerin n° 150 / p.2
development of LV circuit breakers to
standard IEC 947-2

summary

1. Introduction Publication IEC 947-2 p. 4


Stages of its application p. 5
The main new features p. 6
2. The circuit breaker, a Performance and new tests to
multi-function safety device ensure better protection
against overcurrents p. 6
Dielectric strengh for p. 9
"insulation co-ordination"
Disconnection and residual p. 10
current protection: two extra
functions now recognised
3. A test standard based on reality Sequence tests p. 13
Very wide sampling of circuit p. 13
breakers tested
4. Practical consequences for the Fundamental selection criteria p. 13
installation designer for circuit breakers are
unchanged
Use of p. 13
"service breaking capacity" Ics
Two devices in one: p. 14
the circuit breaker-disconnector
All risks insurance: p. 15
conformity to IEC 947-2
5. Appendices Definitions and symbols p. 16
according to IEC 947-2
Calculation of probable p. 16
Isc on load side of a circuit
breaker installed as outgoer
Main differences between p. 17
standards IEC 157-1 and
IEC 947-2
Standard IEC 898 for domestic p. 18
circuit breakers

Cahier Technique Merlin Gerin n° 150 / p.3


1. introduction

As with all electrical devices, industrial


Low Voltage circuit breakers are In the electrotechnical field there are two different types of standards which the various participants have to
designed, manufactured and verified consider:
according to rules collected in the 1. "product" standard
standards known as "product These standards exist for each component in an electrical installation.That a product conforms to its
standards" (see fig.1). Each country standard is, for the user, an assurance of quality and reliability.
■ distribution boards,
has it own standards: UTE for France, ■ power supplies (transformers, generators, etc),
BSI for the UK, VDE for Germany, etc. ■ devices (circuit breakers, isolators, contactors, etc),
Whatever the country, in addition to ■ cables,
■ loads (motors, lighting, etc).
their standardising function the IEC
publications (IEC: International 2. installation standards
These bring together the various rules concerning the design, construction and use of an electrical
Electrotechnical Commission) serve as installation to ensure:
reference and the conformity of ■ correct supply to loads (voltage, frequency, etc);
products to these texts is very often a ■ safety of personnel and equipment;
requisite in the specifications of a ■ maintenance of these requirements throughout the life of the installation.
In France, NF C 15-100 comes into this category.
contract (see fig. 2).
Also, the standards covering Product Standards Installation Standards
These are rules concerning the manufacture and These are rules for the use of
LV industrial circuit breakers are today, control of products, for example: products, taking into account the
in Europe as in a large number of other following main parameters:
■ power sources; G G
countries, based on the standard ■ neutral system;
IEC 157-1 published in 1973. ■ current-carrying capacity;
■ short-circuit current;
■ main distribution board ■ earth leakage current;
publication IEC 947-2 (devices and enclosures); ■ temperature;
■ type and method of installation
An extra step towards an of cables;
■ cables; ■ maximum permissible volt-drop;
international standard. ■ particular risks (fire, vibration,
The desire for a still wider international ■ secondary distribution explosion), discrimination;
recognition of IEC recommendations, board (devices and enclosures); ■ limits on use;
as well as the technical and ■ cables; ■ etc.

technological progress achieved since ■ loads.


M
1973 by the manufacturers, have
prompted IEC sub-committee 17B to fig. 1: product standards.
work on a revision of publication 157-1.
This sub-committee, made up of
representatives from more than 40
countries (of which the expert for
France is from Merlin Gerin), resulted
in the publication in 1989 of standard
IEC 947-2. CSA
IEC
After a vote of approval, this gained IEC
UL JIS
considerable world-wide agreement
(Europe, United States, Canada, IEC
Australia, South Africa) with the sole IEC
exception of ... Japan! (see fig. 3). IEC
IEC 947-2 is part of a much more
comprehensive work IEC 947. UL
This work comprises seven documents
IEC IEC
which constitute the IEC standards for IEC
all Low Voltage electrical switchgear for
industrial use:
■ IEC 947-1: General rules
(published in 1989);
■ IEC 947-2: Circuit breakers fig. 2: map showing the influence of various standards bodies.
(formerly IEC 157-1);

Cahier Technique Merlin Gerin n° 150 / p.4


■ IEC 947-3: Switches, disconnectors, ■ a first one named "General rules" 18 countries of Western Europe.
switch-disconnectors, and use- (IEC 947-1) which gathers together the From the basic text, CENELEC
combinations (formerly IEC 408); definitions, instructions and tests establishes whether:
■ IEC 947-4: Contactors and starters common to all industrial LV material; ■ it is a European Norm "EN..." which is
(formerly IEC 158-1 and IEC 292); ■ a second one named "Products" then ratified as a national standard by
■ IEC 947-5.1: Control circuit devices (IEC 947-2 to 7) which deals with the all the member countries;
and switching elements (formerly instructions and tests specific to the ■ it is, in the event of differences, a
IEC 337); product concerned. harmonisation document "HD..." which
■ IEC 947-5.2: Proximity sensors Thus the texts applicable to industrial is then transformed into a national
(published in 1989); LV circuit breakers are IEC 947-1 and standard with the incorporation of
■ IEC 947-6.1: Automatic transfer IEC 947-2. points specific to each country.
switching equipment (published in As far as publications IEC 947-1 and 2
1989); are concerned, no notable differences
■ IEC 947-7.1: Terminal blocks for stages of its application have emerged to date. Further, in 1991
copper conductors (published in 1989). CENELEC should publish two EN
This structuring allowed In Europe European Norms which by end 91/
homogenisation of the vocabulary and The texts published by the IEC are first beginning 92 will find their way into the
general rules of the various product of all studied at the level of the national standards of the various
fields; but in order to determine all the European Committee for member countries.
rules relating to one category of device, Electrotechnical Standardisation
one has to consult two documents: (CENELEC) which brings together the

IEC
Worldwide representation

standard
IEC 947-2

text approved text approved text rejected


and applied but not applied and not applied

CENELEC
Western Europe

UTE
(France)
VDE
(Germany)
BSI
(UK)
AS CEI UL JIS
(Australia) (Italy) USA Japan
SABS UNE CSA
(South Africa) (Spain) Canada

fig. 3: worldwide adoption of IEC 947–2.

Cahier Technique Merlin Gerin n° 150 / p.5


In the USA and Canada Each country can ratify the IEC text as provides for the user a better
Although favourable comment has a national standard after studying it and assurance of quality and performance,
been expressed, the standards in force making any modifications necessary. introducing extra requirements which
(UL in the USA and CSA in Canada) Considering the very wide approval take into account more fully the actual
are very different from IEC 947-2 and a achieved by IEC 947-2, it could well be operating conditions of a circuit breaker
reaction of conservatism, even a that most countries will adopt it with in use.
certain protectionism, has meant that very few modifications. Moreover, this standard recognises a
these two countries will probably retain circuit breaker's ability to fulfil other
their specific standards for a long time functions, in addition to the usual ones
yet.
the main new features of overcurrent protection, isolation, or
First of all it is very important to note personal protection by residual current
In Japan
that the new text does not change the device.
The only country to have voted in the fundamental circuit breaker selection
negative, Japan will not adopt the IEC criteria, which are still its breaking
text. capacity and its rated current.
In other countries of the world On the other hand, the new text

2. the circuit breaker, a multi-function safety device

performances and new Icu corresponds, in practice, to occurs (already a very rare occurence),
breaking capacity P1 in the former its value is much lower than the
tests to ensure better standard and it is defined in the same assumed Isc.
protection against way: On the other hand, it is important that
overcurrents Icu (947-2) = breaking capacity P1 (157- those currents of higher probability be
1). disconnected under very good
What the user of a circuit breaker
It is this characteristic which, from the conditions so that after elimination of
requires, above all else, is that it fulfils,
design of a network, is to be compared the fault, the return to service is sure to
without fail, its main purpose: in all
with the three phase short-circuit be quick, and safe for the entire
circumstances and completely safely to
current value at the point of installation installation.
protect electrical installations against
of the circuit breaker. It is for this reason that IEC 947-2
overcurrents whatever their values,
between In and the breaking capacity Icu (of the device) ≥ Ics three phase (of introduces a new characteristic Ics,
the system) known as "service breaking capacity",
of the device. generally expressed as a percentage of
In view of this need, IEC 947-2 has Service breaking capacity: Ics
Icu (value to be chosen by the
taken the main well-known Icu represents the maximum short- manufacturer from 25, 50, 75 or 100 %)
characteristics of a circuit breaker, circuit current which a circuit breaker defined in the following way:
already defined in the former 157-1 can break. The Isc calculation normally ■ the circuit breaker carries out three
(breaking capacity, rated current, assumes the worst case with all successive disconnections of Ics
operating voltage, etc); but it clarifies parameters applied in the direction of current;
them and complements them with new safety, in particular: ■ the ability of the device to fulfil all its
principles and new performances ■ the short-circuit is three-phase; functions is then verified by a series of
(ref.appendix 1) which constitute a ■ it is said to be "bolted", i.e. without measurements (temperature rise,
better guarantee of its ability to break arc; insulation level, trip operation, etc).
any value of current. ■ resistance of connections is not taken This establishes Ics as a performance
Clarification of breaking capacity into account; which can be considered not simply as
■ the short-circuit is considered to breaking capacity (as was the breaking
With IEC 157-1, for any one circuit
breaker there existed two breaking occur at the load side terminals of the capacity P2 of 157-1), but as the ability
capacities called "P1" and "P2" defined circuit breaker without intervening of the circuit breaker to ensure
both by the test cycle and the post- cables; completely normal service, even after
■ cable resistances are calculated at having disconnected several short-
break requirements.
IEC 947-2 dispels this ambiguity. normal operating temperatures (in circuit currents (see fig. 4).
From now on, each circuit breaker has short-circuit, these resistances are
only one breaking capacity called Icu greater because they increase at the
(ultimate breaking capacity) expressed same time as the cables heat up).
in kA. The result is that, when a short-circuit

Cahier Technique Merlin Gerin n° 150 / p.6


The short-time withstand current Icw
(for category B circuit breakers)
IEC 157-1 new standard IEC 947-2
IEC 947-2 defines two categories of
breaking capacity 2 breaking capacities ultimate breaking capacity
P1 (O-CO) Icu O-CO circuit breakers:
P2 (O-CO-CO) ■ those of category A for which no
in-service performance nothing service breaking capacity Ics short-circuit trip delay is
O-CO-CO provided.These are generally moulded
+serviceable condition afterwards case circuit breakers, such as
Compact C250N;
■ those of category B for which, in
Icu Isc 3 phase order to achieve chronometric
short-circuit very low
discrimination, it is possible to delay
1 on load side probability tripping during short-circuit conditions
terminals of breaker with values lower than Icw. These are
generally air circuit breakers
(Masterpact type) and some of the
short-circuit with low probability higher rated moulded case circuit
2 arc at the load but greater breakers such as Compact C1250N.
end of the supply than 1 For the latter, the new IEC imposes an
extra test to verify their ability to
withstand, thermally and
electrodynamically, the Icw current
during the associated delay, without
repulsion of the contacts which would
give rise to excessive wear and tear
fig. 4: IEC 947-2 better approaches the needs of installations. (see fig. 5).
Co-ordination between circuit
breakers
short time withstand required for Icw associated delay The term co-ordination concerns the
∆t (secs) behavious of two devices C1 and C2
In 2,500 A In > 2,500 A placed in series in an electrical
values for Icw 12 In Icw 30 kA 0.05 minimun value distribution circuit, with a short-circuit
IEC 947-2 (mini. 5 kA) 0.1 downstream of C2 (see fig. 6).
0.25 preferred
0.5 values It covers two principles:
1 ■ the first is well known: discrimination,
example which is researched more and more in
Masterpact Icw = 75 kA 1 modern low voltage electrical
M20H2 distribution systems;
■ the other is less well known (although
t recognised in installation standards):
cascading, which consists of installing a
device C2, whose breaking capacity

C1

max.delay
∆t.
C2

Ir I cw I cs I cu I
fig. 6: two circuit breakers C1 and C2 placed
fig. 5: supplementary test for category B circuit breakers. in series in one circuit

Cahier Technique Merlin Gerin n° 150 / p.7


Icu2 is less than the three-phase short-
circuit current at its terminals Isc2 and
which is protected or "helped" by C2 opens only C1 and C2 open
device C1 for any current between Icu2
and Isc2 (see fig. 7). The main I
advantage of this technique is to be Is Icu2 Isc2 Icu1
able to install at C2 a device of a lesser
performance, thus more economical,
without endangering the safety of the discrimination zone cascading
zone
installation.
To determine and guarantee co-
ordination between two circuit breakers,
fig. 7: the principle of cascading between 2 circuit breakers, breaker C2, having a breaking
it is necessary to carry out a preliminary
capacity less than the three phase short circuit level at its terminals (Isc2), is protected or
theoretical approach, and to confirm the
assisted by breaker C1.
results by means of suitable tests.This
is how it has been done by Merlin
Gerin, to draw up tables of
discrimination and cascading which are
at present ratified in appendix A of Y Y
IEC 947-2.
The theoretical methods are: C2 circuit breaker C1 circuit breaker
■ for discrimination, comparing the limitation curve limitation curve
limitation characteristics of the loadside
circuit breaker with the non-tripping C1 circuit breaker
tripping curve C2 circuit breaker
characteristics of the lineside device
maximun withstand
(see fig. 8). This method is very precise
and requires little in the way of
confirmation testing;
■ for cascading, comparing the
cascading
limitation characteristics of the lineside Is prospective Isc zone
device with the maximum withstand of Icu1
the loadside device (see fig. 9). This discrimination
limit Icu2 Is prospective Isc
method is much less precise, also
IEC 947-2 requires that the results are
cascading limit
verified by more numerous tests.
It should be noted that the SELLIM Depending on which type of circuit
technique (see fig. 10), developed by breaker C1 is, Y is expressed in:
■ I 2t (energy) for a thermal magnetic In this case determination is done using
Merlin Gerin and which connects
circuit breaker. energy in I2t and kA peak current.
discrimination and cascading, is
■ kA peak for an electronic circuit breaker.
officially recognised by 947-2. It is in
fact stated that during the tests, C1
contacts might separate momentarily fig. 8: theoretical determination of fig. 9: theoretical determination of cascading
when the fault is cleared, to close again discrimination between two circuit breakers. limit between two circuit breakers.
immediately after breaking of the
current.

C1 (SELLIM)
opens momentarily
C2 opens only C2 open

Icu2 Isc2 Icu1 I

cascading

discrimination zone

fig. 10: application of the Sellim technique.

Cahier Technique Merlin Gerin n° 150 / p.8


dielectric strength for (see fig. 12) are carried out on the In this table, note:
switchgear. ■ that for the value Uimp to be valid up
"insulation co-ordination" Thus for industrial circuit breakers of to 2,000 m altitude, the tests which are
What is insulation co-ordination? Uimp = 8 kV, the tests detailed in the generally carried out at sea level are
Every electrical installation is subject to table in figure 13 are carried out. raised by 23 %;
occasional overvoltages of various
origins such as:
■ atmospheric overvoltage; nominal system applications
■ operational overvoltage; voltage
■ overvoltages arising from faults;
■ overvoltages following MV/LV
flashover;
■ etc.
The study of these overvoltages (origin,
value, location, etc) and the rules
applied in order to achieve protection
against them, are known as insulation
co-ordination (see "Cahier Technique"
no 151).
In industrial LV systems, overvoltage at the main system main and final loads
protection is considered to be achieved incomer or distribution
when the equipment can withstand the LV transformer circuits
following two types of test without 230 / 400 V 6 4 2.5
suffering damage: 400 / 690 V 8 6 4
■ the familiar dielectric tests at 50 Hz,
e.g. withstand at (2 Ui + 1000 V)/1 min,
which simulates the risk of installation
faults at higher voltages;
■ impulse voltage tests (1.2/50 µs) of overvoltage levels
value Uimp (imp as in impulse) variable chosen for Merlin Gerin devices
according to location of the installation; 6 kV = Multi 9
newly introduced, these are 8 kV = Compact and Masterpact
representative of atmospheric and
operational overvoltages.
The performance Uimp, which the
switchgear must withstand, is defined in fig. 11: assumed overvoltage levels (source: IEC publication 38 and NF C 15-100 1990, at
the installation standards according to 2,000 m altitude).
the table in figure 11.
Impulse voltage tests
Publications IEC 947 take into account
the rules of insulation co-ordination and Since Uimp must be valid for altitudes, up to 2,000 metres, while testing is done generally
at sea level, the test impulse level is increased by 23 % (or 9.8 kV for Uimp = 8 kV)
require that impulse voltage tests
impulse voltage impulse voltage levels
applied circuit breakers switch-disconnectors switch-disconnectors
(see below) (with class II front face)
kV
between phases 9.8 kV 9.8 kV 9.8 kV
between upstream 9.8 kV 12.3 kV 12.3 kV
and downstream,
9.8 kV contacts open
between phases 9.8 kV 9.8 kV 14.7 kV
50 % and earth

tests relevant
to Compact and
1.2 50 µs Masterpact

fig. 12: impulse wave for industrial circuit fig 13: voltage impulse withstand test for industrial circuit breakers: during the tests, no
breakers 1.2 / 50 µs. breakdown shall occur between phases, between open contacts, or between phase and earth.

Cahier Technique Merlin Gerin n° 150 / p.9


■ that a specific test is required for disconnection and residual additional block ensuring protection of
devices with class II front face; this persons in the event of an insulation
characteristic, in addition to the extra
current protection: two fault on the loadside.
safety it provides for operators, allows extra functions now These two functions are now taken into
the assembly of class II equipment recognised consideration by IEC 947-2.
while keeping the manual control
For a number of years, certain Disconnector circuit breaker
handle accessible (see fig. 14). All
manufacturers including Merlin Gerin A circuit breaker can be said to be
Compact and Masterpact circuit
have worked within major constraints suitable for disconnection if it has been
breakers have class II front faces.
when proposing suitable circuit successfully subjected to a whole
breakers for disconnection. series of tests described in the table in
Likewise, during the sixties Merlin Gerin figure 15. It will then bear the
was the first manufacturer to propose disconnector circuit breaker symbol
class II enclosure residual current circuit breakers visible on its front face
comprising a circuit breaker plus an (see fig. 16 & 17).

class II front face

1. measurement of leakage currents


Intended to ensure that an open-circuit breaker conducts no leakage current which could
endanger a user.
■ four tests are done at 110% of the maximum rated voltage:
■ new device, leakage current should not be greater than 0.5 mA per pole;
■ after the breaking test at Ics, leakage current must not be greater than 2 mA per pole;
■ after endurance testing, leakage current must not be greater than 6 mA per pole;
■ after the breaking test at Icu, leakage current must not be greater than 6 mA per pole.
■ In the last two cases, the breaker is at the end of its life and we can say, therefore, that a
circuit breaker or isolator will never have a leakage current greater than 6 mA (a very low
current which is not dangerous).
fig. 14: class II equipment with circuit 2. voltage impulse withstand
breaker having class II front face. This test involves applying an impulse voltage between the incoming and outgoing terminals
with the contacts open; this impulse voltage is greater for an "isolating" circuit breaker than for
a non-isolating circuit breaker.
Thus for a device which is considered to be "isolating", with Uimp = 8 kV, then the value of
impulse voltage applied across open contacts at sea level will be 12.3 kV instead of 9.8 kV.

3. mechanical strength test


This test, often called "welded contact test", consists in holding the contacts closed while
applying a force, of 3 times the normal force, to the handle for 10 secs.
During this test, the position indicator must not indicate open and no locking-off device may be
engaged.

fig. 15: three tests to demonstrate isolation.

a b
fig. 16:
a: circuit breaker symbol fig. 17: front face of a Compact circuit
b: disconnector circuit breaker symbol breaker (Merlin Gerin)

Cahier Technique Merlin Gerin n° 150 / p.10


Residual current circuit breakers At the request of French breaking at Icu and Ics;
Numerous manufacturers have again representatives, and based upon a ■ absence of unwanted tripping in
made use of Merlin Gerin technology project set up in France, IEC 947-2 the event of:
(see fig. 18). Today the industrial has devoted an appendix (appendix ■ balanced overcurrent
residual current circuit breaker is a B) to this type of product. Among the ■ impulse current wave (being
very widely-used device for which important points covered, the studied)
there is no construction standard, the following verifications should be ■ impulse voltage
quality of which might therefore vary noted: ■ operation under severe
considerably from one manufacturer ■ non degradation of residual current environmental conditions: 28 day
to another. protection units (Vigi blocks) after cycle of moist heat (see fig. 19).

percentage
relative humidity
100

95

90

0 3 12 14h30 24 duration (h)


temperature
deg C
55

25

period of cooling
temperature period
increase
1st 2nd
constant constant
temperature temperature
phase phase
fig. 18: Vigicompact, industrial residual
current circuit breaker fig. 19: test cycle for humidity/heat endurance, repeated over 28 consecutive days

3. a test standard based on reality

The life of a circuit breaker in an ■ overload tripping; constraints to which they may be
electrical installation is punctuated with ■ exceptional tripping on short-circuit or subjected during use.
a certain number of successive events fault; It is with this in mind that the type tests
such as: ■ locking in the OPEN position for required in IEC 947-2 have been
■ opening/closing: manual or remote circuit maintenance; grouped in sequences and that they are
with electronic control, idle or at ■ etc. to be repeated on a specified number
current ≤ In; It is therefore usual for a test standard of devices.
■ tripping by undervoltage release or relating to protective devices such as
shunt trip; circuit breakers, not only to guarantee
■ overvoltage impulses (atmospheric or all the published performances but also
operational); to simulate more closely the successive

Cahier Technique Merlin Gerin n° 150 / p.11


test sequence type of circuit breaker tests to be done successively supplementary tests
on one circuit breaker for isolating circuit breakers
Cat. A Cat. B
Icw Icw Icw
< Ics = Ics = Ics
= Icu

Sequence 1 1. verification of disconnection limits 1. ditto


General X X X X 2. dielectric properties 2. dielectric properties
operating Uimp between phases ditto
characteristics Uimp between phase and earth ditto
Uimp between incoming & outgoing terminals Uimp + 25 % between I/O + leakage
current test
(< 0.5 mA per pole at 110 % Ue)
3. mechanical endurance 3. ditto
4. electrical endurance 4. ditto
5. operation of overcurrent release at 6 In 5. ditto
6. dielectric withstand at 2 Ui (50 Hz - 1 min) 6. ditto
+ leakage current test
(< 6 mA per pole at 110 % Ue)
7. temperature rise at In 7. ditto
8. verify overcurrent release calibration 8. ditto

Sequence 2 1. 3 successive breaks 1. ditto


service X X at Ics with cycle 0 - 3 min - CO - 3 min - CO
short-circuit 2. dielectric withstand at 2 Ui (50 Hz, 1 min) 2. ditto
breaking + leakage current test
capacity Ics (≤ 2 mA per pole at 110 % Ue)

3. temperature rise at In 3. ditto


4. verify the calibration of the overcurrent releases 4. ditto

Sequence 3 1. verify the overcurrent releases at 2 Ir 1. ditto


Ultimate X X X 2. two successive breaks at Icu, 2. ditto
breaking (1) (1) (1) cycle 0 - 3 min - CO
capacity Icu 3. dielectric withstand at 2 Ue (50 Hz, 1 min) 3. ditto
+ leakage current test
(≤ 6 mA per pole at 110 % Ue)
4. verify the calibration of the overcurrent releases 4. ditto

Sequence 4 1. verify the overcurrent releases at 2 Ir


short-time X 2. short-time withstand test for the
withstand test, time duration indicated by the manufacturer
Icw 3. temperature rise test at In
4. two successive breaks at the highest value of voltage
for the required Icw, cycle 0 - 3 min - CO
5. dielectric withstand at 2 Ui (50 Hz, 1 min)
6. verify the calibration of the overcurrent releases

Combined X X 1. verify the overcurrent releases at 2Ir 1. ditto


test 2. short-time current withstand at Icw during 2. ditto
sequence the time indicated by the manufacturer
3. three successive breaks at Ics, cycle 3. ditto
0 - 3 min - CO - 3 min - CO
4. dielectric withstand at 2Ui (50 Hz, 1min) 4. ditto + leakage current test
(≤ 2 mA per pole at 110 % Ue)
5. temperature rise at In 5. ditto
6. verify the calibration of the overcurrent releases 6. ditto

(1) if Ics = Icu this test sequence is not necessary

fig. 20: IEC 947-2 test sequences.

Cahier Technique Merlin Gerin n° 150 / p.12


sequence tests with different configurations
Ultimate breaking capacity sequence Icu. (see fig. 21):
With IEC 157-1 each test was carried
Applied to a circuit breaker, eg, ■ three pole and four pole;
out on a new device.
Compact C250, the sequence has to be ■ fitted with different trips;
From now on, with IEC 947-2, the same
repeated on six devices : ■ at different voltages;
device is subjected to a series of
■ sample 1: test Icu at Ue max: 690 V on a ■ with different settings;
cumulative tests grouped in sequence.
device fitted with the smallest trip unit ■ with loadside and lineside supply if
Five sequences are defined and each
(D160) set to its minimum 112 A. Supply via the circuit breaker is suitable;
type of circuit breaker must be
upstream terminals. ■ with or without residual current
subjected to two, three or four of these
■ sample 2: test Icu at Ue min: 230 V on a protection, if provided;
sequences according to its
device fitted with the largest trip unit (D250) ■ etc.
characteristics (see the table in
adjusted to its maximum 250 A. Supply via Thus the certification report covers all
figure 20). Without a doubt, one of the
downstream terminals. the published performances and
most significant is sequence 1: the
■ sample 3: test Icu at intermediate voltage guarantees to the user that the device
exceptional constraints imposed on the
Ue = 415 V with a device fitted with the will correctly fulfil its function,
devices under test are well illustrated.
smallest rated trip unit adjusted to its regardless of:
minimum value 112 A. Supply via down- ■ characteristics of the network;
stream terminals.
very wide sampling of ■ circuit breaker equipment;
■ sample 4, 5, 6: same test cycle but with ■ settings chosen.
using a device fitted with a residual current circuit breakers tested
block (Vigi) For the purpose of covering all of the
published possibilities, the preceding
figure 21: example of an IEC 947-2 test
sequences are repeated on several
sequence.
circuit breakers of the same type but

4. practical consequences for the installation designer

fundamental selection with load and its breaking capacity Icu device whose performance Ics is such
with the assumed Isc (see fig. 22). that Ics ≥ prospective Ics.
criteria for circuit breakers These two comparisons, or basic a) high rated circuit breakers
are unchanged rules, are included in the installation (Masterpact):
To determine the circuit breaker to be standard NF C 15-100 and remain
These devices are usually installed as
installed for protection of an outgoer in unchanged.
general incomers, connecting up the
an electrical installation, it is primarily switchboard, etc with the result that
necessary to know two parameters: use of "service breaking their field of protection is often limited
■ the load current Is;
■ the value of the three phase short-
capacity" Ics to the switchboard itself.
A short-circuit of value equal to the In these conditions, the prospective
circuit current (assumed Isc) at the short-circuit currents will be only slightly
origin of the wiring system. assumed Isc is extremely rare, one
might say almost impossible to achieve. less in comparison with the assumed
The circuit breaker is selected, as Isc theoretical value; it is therefore
always, by comparing its setting current For this reason, IEC 947-2 has defined
the new characteristic Ics, service important to select devices whose Ics
breaking capacity (see chapter 2), performance is close to or equal to Icu.
which refers to the ability of a device to It is logical therefore that the whole
provide completely normal service, Masterpact range has Ics = 100 % Icu.
Isc prospective
after short-circuit breaking at a b) lower rated circuit breakers
"probable" value. (Compact):
Although there may be no regulations These devices, usually installed as
Ir Is in the installation standards (IEC 364 or outgoers, protect cabling between
load current Icu Isc prospective NF C 15-100) corresponding to the use switchboards, or between switchboards
Is of performance Ics, it is important, and and receptors.
wise, in order to gain optimum In this case, the prospective
fig 22: basic parameters governing the continuity of service, to choose a short-circuits are greatly diminished
selection of an outgoing circuit breaker.

Cahier Technique Merlin Gerin n° 150 / p.13


because when they occur they are
nearly always single phase or two
Imperatives Characteristics of a network Characteristics
phase, and located at the extremity of
supplied from a 400 kVA transformer of the C630N
the protected wiring system. Various
calculations (see appendix 2) show Icu > Isc prospective Isc prospective = 14.5 kVA Icu = 35 kA
that the prospective short-circuit Ics > Isc probable Isc probable = 14 kA Ics = 50 % Icu
current is: = 17.5 kA
■ usually less than 25 % of assumed
figure 23: it is possible to install a Compact C630N circuit breaker as the main incomer from a
Isc at the origin of the wiring system;
400 kVA transformer.
■ and in almost all cases less than
50 % of that same assumed Isc.
Although this may not be an installation
regulation from the standards point of
view, the use of circuit breakers having
Ics equal to 25 % or, better still, 50 %
for protection of outgoers is a wise
precaution for prolonging the working
life of the installation.
All devices in the Compact range offer
this possibility, with a service breaking
capacity equal to 50 % Icu.
Note: use of a Compact device as
incomer
As explained in the preceding
paragraph, the prospective short-circuit
currents in this case are only lightly less
in comparison with the assumed Isc
theoretical value. On the other hand,
the value of the assumed Isc is low,
since it is related to the short-circuit
power of the associated transformer.
Thus, for example, it is possible to
install a Compact C630N circuit breaker
as a main incomer after a 400 kVA
transformer, according to the table in
figure 23.
Generally speaking, Compact circuit
breakers, with service breaking
capacity equal to 50 % Icu, can be
used with complete safety as an
incoming circuit breaker on the load
side of a transformer.

figure 24: interlocking device on a Masterpact circuit breaker.

two devices in one: The most flexible solution is believed to


be the ability to fit such devices at all
the circuit breaker- stages of distribution.
disconnector Nowadays it is possible at no extra cost
Among the qualities required of an with circuit breaker-disconnectors,
electrical installation, one in particular is of represented by the symbol:
major importance for the user and that is
the capability in the event of a breakdown, All Compact and Masterpact industrial
to take out of service only the absolute circuit breakers manufactured by Merlin
minimum of the installation. Gerin are circuit breaker-disconnectors
figure 25: padlocking device on a Compact
Note:take out of service = isolate + lock in lockable by padlock (see fig. 24) and/or
circuit breaker.
"isolated" position (by padlock or switch- switch-lock (see fig. 25).
lock)

Cahier Technique Merlin Gerin n° 150 / p.14


"all risks insurance":
conformity with IEC 947-2
For the designer, a circuit breaker's
conformity with IEC 947-2, or with the
national standards derived from it,
constitutes the best possible assurance
of quality and reliability in the
environment of LV electrical
installations.
This assurance results from the fact
that the technological progress
achieved by the leading manufacturers
has been taken into consideration by
the standards, together with a
comprehensive test standard which
closely resembles actual operating
conditions.

Cahier Technique Merlin Gerin n° 150 / p.15


appendix 1

definitions and symbols Icu: rated ultimate short-circuit breaking Various definitions and symbols
capacity. symbol for circuit breaker.
according to IEC 947-2 Icw: rated short time withstand current symbol for circuit breaker-
Definitions relating to voltage I∆n: rated residual operating current disconnector.
Ue: rated service voltage(s). (often called residual sensitivity).
Ui: rated insulation voltage (≥ Ue In: rated current = maximum value of Cat A: category of circuit breakers
max.). current used for the temperature rise without time-delay on opening under
Uimp: rated impulse withstand. test (for example, for a Compact short-circuit conditions.
C250N: In = 250 A). Cat B: category of circuit breakers
Definitions relating to current with time-delay on opening under
Is: discriminating current limit.
Icm: rated short-circuit making short-circuit conditions ≤ Icw.
capacity. ∆t: trip delay of residual current
Ics: rated service short-circuit breaking devices.
capacity.

appendix 2

calculation of probable Isc


on load side of a circuit
breaker installed as
outgoer

Formulae : R mΩ X mΩ
400 V - 50 kA

Isc prospective = 50 kA; cos ϕ = 0.2 ⇒ Z upstream = 230 = 4.6 mΩ 0.92 4.5
50 x 103

Compact C400H
connecting cable, 240 mm2 ⇒ RC = 22.5 x 50 = 4.7 mΩ 4.7
240 Icu = 50 kA
Ics : 50 %,
XC = 0.1 x 50 = 5 mΩ 5 or 25 kA

Total 5.62 9.5 50 m 1p 240 mm 2 cable

Isc probable < 0.8 Isc two-phase = 0,8 x 3 x 230 = 14.4 kA ZT = 11.03
2 11,03 probable Isc < 14.4 kA

Cahier Technique Merlin Gerin n° 150 / p.16


appendix 3

main differences between IEC 157-7 and IEC 947-2


IEC 157-1 New standard IEC 947-1/2 Comments

Breaking capacity P1 cycle. Ultimate breaking capacity Equivalent


Icu (sequence 3)

Breaking capacity P2 cycle.

Service breaking capacity Obligatory on all devices and more


Ics (sequence 2) rigorous than P2 in IEC 157-1
because the test includes a
temperature rise test at In

Each test done on a new device Tests are conducted in sequence More severe because of the
(operation, endurance, overloads, cumulative testing on one device,
breaking capacity) but closer to real conditions

Verify (three poles loaded) at Verify (three poles loaded) at with: t


the two points: the two points:
Ind = 1.05 Ir Ind = 1.05 Ir t = 1 h (≤ 63 A)
Id = 1.35 Ir (≤ 63A) Id = 1.30 Ir or
or t = 2 h (> 63 A)
Id = 1.25 Ir (> 63A) Ir Ind Id I

No other verification of Verification of tripping: Better guarantee of operation of


overcurrent releases ■ each pole individually releases
(sequences 3,4,5)
■ all poles loaded (sequence 2)

Nothing Definition of tests for isolation with The circuit breaker-disconnector is


the associated symbol: recognised by installation standards to
ensure the isolating function

Nothing Voltage impulse withstand test Allows insulation coordination


Characteristic Uimp throughout the installation

Co-ordination only between fuse Includes a co-ordination appendix Takes into account two circuit
and circuit breaker breakers in series

Nothing One appendix intended solely for Standardisation of industrial


circuit breakers with residual residual current circuit breakers
current protection

Cahier Technique Merlin Gerin n° 150 / p.17


(1) (4)
appendix 4 ■ standard 947-2 does not provide an EN 60 898 gives a test for the purpose
upper or lower limit. 947-2 circuit of verifying the absence of projection
breakers are used in the range of "a of material towards the front (giving rise
few amps to a few thousand amps". to danger to the skin and eyes).
■ EN 60 898 defines the ratings Possible projections are shown up by a
standard IEC 898 for (assigned current: In): polyethylene film.
domestic circuit breakers paragraph 10,13,16,20,25,32,40,50,63,100 It also gives a test for the purpose of
Industrial circuit breakers covered by and 125 A. verifying that there are insufficient
the standard IEC 947-2 are selected, (2) projections to propagate a flashover.
installed and used by experienced ■ standard 947-2 does not fix the range
professionals.This is not always the of operation and leaves the
case with circuit breakers for final manufacturer to define the magnetic
distribution, particularly where they are trip threshold, which must then fall
used in the domestic field (by within ± 20 %.
inexperienced users), hence the For Merlin Gerin circuit breakers of
standard IEC 898. ratings higher than 250 A, the magnetic
IEC 898 circuit breakers which form thresholds are:
part of "domestic and similar ■ G type adjustable from 2 to 5 Irth
switchgear" are easier to install (for ■ D type adjustable from 5 to 10 Irth
example they do not have an ■ MA type adjustable from 6.3 to
adjustable threshold), guaranteeing a 12.5 Irth
high level of safety. Their use by ■ EN 60 898 modifies standard practice
professionals means that some of them (curves L, U, D) and introduces some
also come under IEC 947-2. new curves:
IEC 898 dates from 1987. It became a ■ curve B: 3 to 5 In (2.6 to 3.85 for L)
European Norm in mid-1990, and in ■ curve C: 5 to 10 In (3.85 to 8.8 for U)
member countries of CENELEC, mid- ■ curve D: 10 to 20 In (10 to 14 for D
1991 will see the issue of national and MA)
standards harmonised with the
(3)
European Norm EN 60 898.
■ standard 947-2 gives an "ultimate
There are some notable differences
breaking capacity" corresponding to an
between IEC 947-2 and EN 60 898. It is
O-CO test and a "service breaking
of interest to be aware of them since
capacity" of which the value, as a
small circuit breakers are often used in
percentage of Icu, is fixed by the
industrial final distribution.
manufacturer and corresponds to an
IEC 947-2 EN 60 898 O-CO-CO test (see table 1 in figure 4).
■ EN 60 898 gives an assigned
Voltage Un (V) < 1,000 < 440
breaking capacity Icn corresponding to
Current (1) In ≤ 125 A
an O-CO test and a service
Thermal 1.05 1.13 performance of which the value, as a
trip to 1.03 In to 1.45 In percentage of Icn, is fixed by the
Magnetic (2) curves standard and corresponds to an O-CO-
trip B-C-D CO test for:
Breaking Icu Icn (3) ■ Icn ≤ 6 kA Ics = Icn
capacity ■ Icn > 6 kA Ics = 0.75 Icn (min 6 kA)
Service Ics Ics (3) ■ Icn ≤ 10 kA Ics = 0.75 Icn (min 6 kA)
capacity ■ Icn > 10 kA Ics = 0.5 Icn (min 7.5
Isolation Yes Under study kA)
External Safety test (4) Moreover this standard limits its field of
Safety perimeters for no application to circuit breakers of
respected emissions breaking capacity ≤ 25 kA: short-circuit
current which there is little chance of
observing in a domestic or commercial
installation.

Cahier Technique Merlin Gerin n° 150 / p.18


Cahier Technique Merlin Gerin n° 150 / p.19
Réal. : E.R.I. - Lyon - Photo. : IPV
Cahier Technique Merlin Gerin n° 150 / p.20 IPV - 12-91 - 2500 - Imprimeur : Léostic

You might also like