Professional Documents
Culture Documents
CT150 Development of LV Circuit Breaker
CT150 Development of LV Circuit Breaker
development of
LV circuit
breakers to
standard IEC 947-
2
Etienne Blanc
summary
IEC
Worldwide representation
standard
IEC 947-2
CENELEC
Western Europe
UTE
(France)
VDE
(Germany)
BSI
(UK)
AS CEI UL JIS
(Australia) (Italy) USA Japan
SABS UNE CSA
(South Africa) (Spain) Canada
performances and new Icu corresponds, in practice, to occurs (already a very rare occurence),
breaking capacity P1 in the former its value is much lower than the
tests to ensure better standard and it is defined in the same assumed Isc.
protection against way: On the other hand, it is important that
overcurrents Icu (947-2) = breaking capacity P1 (157- those currents of higher probability be
1). disconnected under very good
What the user of a circuit breaker
It is this characteristic which, from the conditions so that after elimination of
requires, above all else, is that it fulfils,
design of a network, is to be compared the fault, the return to service is sure to
without fail, its main purpose: in all
with the three phase short-circuit be quick, and safe for the entire
circumstances and completely safely to
current value at the point of installation installation.
protect electrical installations against
of the circuit breaker. It is for this reason that IEC 947-2
overcurrents whatever their values,
between In and the breaking capacity Icu (of the device) ≥ Ics three phase (of introduces a new characteristic Ics,
the system) known as "service breaking capacity",
of the device. generally expressed as a percentage of
In view of this need, IEC 947-2 has Service breaking capacity: Ics
Icu (value to be chosen by the
taken the main well-known Icu represents the maximum short- manufacturer from 25, 50, 75 or 100 %)
characteristics of a circuit breaker, circuit current which a circuit breaker defined in the following way:
already defined in the former 157-1 can break. The Isc calculation normally ■ the circuit breaker carries out three
(breaking capacity, rated current, assumes the worst case with all successive disconnections of Ics
operating voltage, etc); but it clarifies parameters applied in the direction of current;
them and complements them with new safety, in particular: ■ the ability of the device to fulfil all its
principles and new performances ■ the short-circuit is three-phase; functions is then verified by a series of
(ref.appendix 1) which constitute a ■ it is said to be "bolted", i.e. without measurements (temperature rise,
better guarantee of its ability to break arc; insulation level, trip operation, etc).
any value of current. ■ resistance of connections is not taken This establishes Ics as a performance
Clarification of breaking capacity into account; which can be considered not simply as
■ the short-circuit is considered to breaking capacity (as was the breaking
With IEC 157-1, for any one circuit
breaker there existed two breaking occur at the load side terminals of the capacity P2 of 157-1), but as the ability
capacities called "P1" and "P2" defined circuit breaker without intervening of the circuit breaker to ensure
both by the test cycle and the post- cables; completely normal service, even after
■ cable resistances are calculated at having disconnected several short-
break requirements.
IEC 947-2 dispels this ambiguity. normal operating temperatures (in circuit currents (see fig. 4).
From now on, each circuit breaker has short-circuit, these resistances are
only one breaking capacity called Icu greater because they increase at the
(ultimate breaking capacity) expressed same time as the cables heat up).
in kA. The result is that, when a short-circuit
C1
max.delay
∆t.
C2
Ir I cw I cs I cu I
fig. 6: two circuit breakers C1 and C2 placed
fig. 5: supplementary test for category B circuit breakers. in series in one circuit
C1 (SELLIM)
opens momentarily
C2 opens only C2 open
cascading
discrimination zone
tests relevant
to Compact and
1.2 50 µs Masterpact
fig. 12: impulse wave for industrial circuit fig 13: voltage impulse withstand test for industrial circuit breakers: during the tests, no
breakers 1.2 / 50 µs. breakdown shall occur between phases, between open contacts, or between phase and earth.
a b
fig. 16:
a: circuit breaker symbol fig. 17: front face of a Compact circuit
b: disconnector circuit breaker symbol breaker (Merlin Gerin)
percentage
relative humidity
100
95
90
25
period of cooling
temperature period
increase
1st 2nd
constant constant
temperature temperature
phase phase
fig. 18: Vigicompact, industrial residual
current circuit breaker fig. 19: test cycle for humidity/heat endurance, repeated over 28 consecutive days
The life of a circuit breaker in an ■ overload tripping; constraints to which they may be
electrical installation is punctuated with ■ exceptional tripping on short-circuit or subjected during use.
a certain number of successive events fault; It is with this in mind that the type tests
such as: ■ locking in the OPEN position for required in IEC 947-2 have been
■ opening/closing: manual or remote circuit maintenance; grouped in sequences and that they are
with electronic control, idle or at ■ etc. to be repeated on a specified number
current ≤ In; It is therefore usual for a test standard of devices.
■ tripping by undervoltage release or relating to protective devices such as
shunt trip; circuit breakers, not only to guarantee
■ overvoltage impulses (atmospheric or all the published performances but also
operational); to simulate more closely the successive
fundamental selection with load and its breaking capacity Icu device whose performance Ics is such
with the assumed Isc (see fig. 22). that Ics ≥ prospective Ics.
criteria for circuit breakers These two comparisons, or basic a) high rated circuit breakers
are unchanged rules, are included in the installation (Masterpact):
To determine the circuit breaker to be standard NF C 15-100 and remain
These devices are usually installed as
installed for protection of an outgoer in unchanged.
general incomers, connecting up the
an electrical installation, it is primarily switchboard, etc with the result that
necessary to know two parameters: use of "service breaking their field of protection is often limited
■ the load current Is;
■ the value of the three phase short-
capacity" Ics to the switchboard itself.
A short-circuit of value equal to the In these conditions, the prospective
circuit current (assumed Isc) at the short-circuit currents will be only slightly
origin of the wiring system. assumed Isc is extremely rare, one
might say almost impossible to achieve. less in comparison with the assumed
The circuit breaker is selected, as Isc theoretical value; it is therefore
always, by comparing its setting current For this reason, IEC 947-2 has defined
the new characteristic Ics, service important to select devices whose Ics
breaking capacity (see chapter 2), performance is close to or equal to Icu.
which refers to the ability of a device to It is logical therefore that the whole
provide completely normal service, Masterpact range has Ics = 100 % Icu.
Isc prospective
after short-circuit breaking at a b) lower rated circuit breakers
"probable" value. (Compact):
Although there may be no regulations These devices, usually installed as
Ir Is in the installation standards (IEC 364 or outgoers, protect cabling between
load current Icu Isc prospective NF C 15-100) corresponding to the use switchboards, or between switchboards
Is of performance Ics, it is important, and and receptors.
wise, in order to gain optimum In this case, the prospective
fig 22: basic parameters governing the continuity of service, to choose a short-circuits are greatly diminished
selection of an outgoing circuit breaker.
definitions and symbols Icu: rated ultimate short-circuit breaking Various definitions and symbols
capacity. symbol for circuit breaker.
according to IEC 947-2 Icw: rated short time withstand current symbol for circuit breaker-
Definitions relating to voltage I∆n: rated residual operating current disconnector.
Ue: rated service voltage(s). (often called residual sensitivity).
Ui: rated insulation voltage (≥ Ue In: rated current = maximum value of Cat A: category of circuit breakers
max.). current used for the temperature rise without time-delay on opening under
Uimp: rated impulse withstand. test (for example, for a Compact short-circuit conditions.
C250N: In = 250 A). Cat B: category of circuit breakers
Definitions relating to current with time-delay on opening under
Is: discriminating current limit.
Icm: rated short-circuit making short-circuit conditions ≤ Icw.
capacity. ∆t: trip delay of residual current
Ics: rated service short-circuit breaking devices.
capacity.
appendix 2
Formulae : R mΩ X mΩ
400 V - 50 kA
Isc prospective = 50 kA; cos ϕ = 0.2 ⇒ Z upstream = 230 = 4.6 mΩ 0.92 4.5
50 x 103
Compact C400H
connecting cable, 240 mm2 ⇒ RC = 22.5 x 50 = 4.7 mΩ 4.7
240 Icu = 50 kA
Ics : 50 %,
XC = 0.1 x 50 = 5 mΩ 5 or 25 kA
Isc probable < 0.8 Isc two-phase = 0,8 x 3 x 230 = 14.4 kA ZT = 11.03
2 11,03 probable Isc < 14.4 kA
Each test done on a new device Tests are conducted in sequence More severe because of the
(operation, endurance, overloads, cumulative testing on one device,
breaking capacity) but closer to real conditions
Co-ordination only between fuse Includes a co-ordination appendix Takes into account two circuit
and circuit breaker breakers in series