Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

'B'

686
[27]

2080 1830 'A' 'A'


(8x) 75mm[3"] DUCT
TERMINATORS [82] [72]

1002 686 300 125


[5] 686 1269
[39.5] [27] [12]
[27] [50]
200
[8]
'B'
(8x) 450mm[18"] x
450mm[18"] 2440
300 150 KNOCKOUT WINDOWS
[6] [96]
[12]
(8) 25mm[1"] 450 2690
2230 1830
GROUND HOLES [17.5] [106]
[88] [72] 150mm[6"]
BELOW K.O. 450 PLAN VIEW
(FOR PULLING EYES) SWIFT LIFT HOOK
[17.5]
SYSTEM
(AS PER MANUFACTURERS SPECIFICATIONS)

SOLID ALUMINUM (4x)150mm[6"]


200 STEPS(405.02) KNOCK OUT
[8] DRAIN HOLE

2440 1830
125 [96] 125 125 [72] 125
[5] [5] [5] [5]
2690 2080
[106] [82] 2230
[88]

CROSS SECTION 'A' CROSS SECTION 'B'


2690
2080 [106]
[82]

mm
[Inches]
ISOMETRIC VIEW
ALL DIMENSIONS DEFAULT TO MILLIMETRES
CONSTRUCTION DETAILS: PRODUCT DETAILS: PRODUCT CODE:

AS PER OPSD 2111.05


DESIGNED TO CL-625-ONT TRUCK LIVE
LOADING AS PER CSA S6-06
(8) 450mm[18"]x450mm[18"] KNOCKOUT
WINDOWS
(8) WINDOWS WITH (6) 75mm[3"] DUCT TERMINATORS
PER WINDOW
E-25
OPSD MANHOLE
(4) 150mm[6"] KNOCKOUT DRAIN HOLES
INSIDE DIMENSIONS:
CSA 23.4-05 (8) 25mm[1"] GROUND HOLES
UTILITY STRUCTURES INC. - 35 MPa (5000psi) AT 28 DAYS (FOR PULLING EYES) 2.23m(H) X 1830mm x 2440mm
61 BONGARD AVE | OTTAWA, ON | K2E 6V2 - STRIPPING STRENGTH: MIN. 20 MPa(2900psi) TOTAL WEIGHT:
T: 613.225.6398 F: 613.225.1681 TF: 800.267.6466 WEIGHT:
- 5-8% AIR ENTRAINED TOP SLAB: 2,600 kg / 6,300 lbs 10,600 kg / 22,880 lbs
www.utilitystructures.com - EXPOSURE CLASS: F-1 SPACER: 5,200 kg / 9,900 lbs
REVISION DATE:
REINFORCING: STEEL TO CSA CAN A23.1 BASE SLAB: 2,800 kg / 6,700 lbs NOVEMBER 18, 2017 REV. # 10