insulation products
Class Test method(s) Classification criteria Additional classification
ΔT ≤ 30 °C and
EN ISO 1182 a
A1L Δm ≤ 50 % and -
and
tf = 0 s (i.e. no sustained flaming)
PCS ≤ 2,0 MJ/kg a and
PCS ≤ 2,0 MJ/kg b and
EN ISO 1716 -
PCS ≤ 1,4 MJ/m2 c and
PCS ≤ 2,0 MJ/kg d
ΔT ≤ 50 °C and
EN ISO 1182 a
A2L Δm ≤ 50 % and -
or
tf ≤ 20 s
PCS ≤ 3,0 MJ/kg a and
EN ISO 1716 PCS ≤ 4,0 MJ/m2 b and
-
and PCS ≤ 4,0 MJ/m2 c and
PCS ≤ 3,0 MJ/kg d
FIGRA0,2 MJ ≤ 270 W/s and Smoke production e and
EN 13823 LFS < edge of specimen and Flaming droplets/particles f
THR600s ≤ 7.5 MJ
FIGRA0,2 MJ ≤ 270 W/s and Smoke production e and
EN 13823
BL LFS < edge of specimen and Flaming droplets/particles f
and
THR600s ≤ 7.5 MJ
EN ISO 11925-2 h:
Fs ≤ 150 mm within 60 s
Exposure = 30 s
FIGRA0,2 MJ ≤ 460 W/s and Smoke production e and
EN 13823
CL LFS < edge of specimen and Flaming droplets/particles f
and
THR600s ≤ 15 MJ
EN ISO 11925-2 h:
Fs ≤ 150 mm within 60 s
Exposure = 30 s
EN 13823 FIGRA0,4 MJ ≤ 2 100 W/s Smoke production e and
DL
and THR600s ≤ 100 MJ Flaming droplets/particles f
EN ISO 11925-2 :h
Fs ≤ 150 mm within 60 s
Exposure = 30 s
EN ISO 11925-2 h: Fs ≤ 150 mm within 20 s Flaming droplets/particles g
EL
Exposure = 15 s
EN ISO 11925-2 h: Fs > 150 mm within 20 s
FL
Exposure = 15 s
a
For homogeneous products and substantial components of non-homogeneous products.
b
For any external non-substantial component of non-homogeneous products.
c
For any internal non-substantial component of non-homogeneous products.
d
For the product as a whole.
e
s1 = SMOGRA ≤ 105 m2/s2 and TSP600s ≤ 250 m2 ;
s2 = SMOGRA ≤ 580 m2/s2 and TSP600s ≤ 1 600 m2;
s3 = not s1 or s2
f
d0 = No flaming droplets/ particles in EN 13823 within 600 s;
d1 = No flaming droplets/ particles persisting longer than 10 s in EN 13823 within 600 s;
d2 = not d0 or d1.
Ignition of the paper in EN ISO 11925-2 results in a d2 classification.
g
Pass = no ignition of the paper (no classification);
Fail = ignition of the paper (d2 classification).
h
Under conditions of surface flame attack and, if appropriate to the end–use application of the
product, edge flame attack.