Manual de Termostato Hisense Modelo Hyxe-Va01a
Manual de Termostato Hisense Modelo Hyxe-Va01a
3. Model: HYXE-VA01A
3.1 Safety summary
● Please use this product properly after carefully reading this chapter
● Items in this chapter are identified as 「 Warning」
Serious consequences that may result from mis-operation are listed, and important safety related contents are given,
please be sure to observe!
● Please keep this manual properly after reading for reference at any time.
● For installation, please entrust the distributor or the professional installation personnel.
Installation by customers themselves may lead to water leakage, electric shock, a fire, unit falling and other
injuries.
Warning
● Electrical constructors must be qualified for construction. Please entrust qualified distributors for
construction.
Installation by customers themselves may lead to electric shock, a fire and other accidents.
In Operation
● Please do not operate the controller with wet hands, which may lead to electric
shock.
● Please turn off the main power immediately when the safety device starts
repeatedly or the operation key acts abnormally.
Warning
64
Model: HYXE-VA01A
Servicing · Relocation
● Please contact the distributor or our designated service center for servicing of the air conditioner units.
Improper servicing or installation may lead to electric shock, a fire and other accidents.
Warning
● Please contact the distributor or our designated service center for servicing or relocation of the controller.
Improper servicing or installation may lead to electric shock, a fire and other accidents.
● Strictly prohibit the ingress of water during maintenance. Otherwise it may lead to
electric shock.
● Do not alter the electrical wiring without permission, which may lead to major accident.
Warning
● Do not cut off the power supply within 3 minutes after pressing the key of the controller, which
may lead to misoperation.
65
Model: HYXE-VA01A
3.2 Features
Features
Mode Cool/Heat/Auto/Fan/Dry
Back light ●
3.3 Installation
3.3.1 Installation Site Selection
Cable section 0.3 mm2 ≥ 0.75 mm2
Cable length 30 m 500 m
Mounting Screw
2
(M4×16mm)
Installation manual 1
Operation Manual 1
66
Model: HYXE-VA01A
3.3.3 Description of the parts
To proceed with below instructions, all the displays are listed. It is different from actual running.
11
22 23 24 25
26 27 28 29 30
16 15 14 13 12
31 32 33 34
21 20 19 18 17
35
36 37 38 39
1 2 3 4 5
6 7 8 9 10
A. Operation Buttons
1 ON/OFF 4 Timer 7 Louver
2 Fan 5 Function 8 Temperature“-”
3 Temperature“+” 6 Mode 9 Reset
10 OK
B. Display on LED
11 Operation modes: "Fan" "Cool" 20 Centralized controller 30 ECO
"Dry" "Heat" "Auto" 21 No function 31 Electric heater
12 Fan 22 Room/Set temp 32 Self-cleaning
13 Louver 23 Filter 33 Nature wind
67
Model: HYXE-VA01A
3.3.4 Dimension data
23 23
101.80
120
60.30
60
15.70
120 23 23
17
68
Model: HYXE-VA01A
3.3.5 Installation procedure
Bottom View
Groove Part for Removing Contronller
(1) Insert the edge of the slotted screwdriver into the
groove at the bottom of the holding bracket, push
and turn the slotted screwdriver and then remove the
Approx. 6mm
controller from the holding bracket. Groove Part
(2) Attach the controller to the holding bracket and Slotted Screw Driver
connect the cable as follows.
JIS box
(Field-Supplied)
M4 Screws
(Field-Supplied)
(3) Attach the remote control switch to the holding bracket. Be careful not to pinch the cable when attaching it.
(4) Remove the protection film from the liquid crystal display.
69
Model: HYXE-VA01A
3.4 Electrical wiring
ATTENTION:Always make sure to turn off the power of the indoor unit when performing electrical wiring work. Performing electrical
wiring work with the power on can damage the circuit boards of the indoor unit and the remote control switch.
M3.5 Screws
● Use a 0.3 to 0.75mm2 cable for connecting. The maximum total cable length is 30m.If the total cable length
exceeds 30m, use a twist pair cable with shield tube(1P-0.75mm or more).In that case, the maximum total cable
length is up to 500m.If using in combination with the control timer, the allowable total cable length is up to 100m.
The use of a cable other than specified above can cause of malfunction due to the effects of noise.
● Keep a distance more than 30cm between the transmission line (remote control switch cable and transmission
wires) and power source of the indoor units. If not, the air-conditioner may not operate properly or malfunction
may occur due to effect of power source noise.
CAUTION
● In case of simultaneously controlling multiple indoor units, set the refrigerant cycle numbers and addresses of
the indoor units without overlapping.
● Refer to the Technical Catalog provided with each indoor unit when performing electrical wiring work between the
remote control switch and indoor units for setting the refrigerant cycle number and the indoor unit address.
● No gap shall exist between the remote control switch cable and hole of the remote control switch case. If there is
a gap, cover the gap with vinyl tape. If not, malfunction may occur due to entrance of water droplets or insects.
● When installation keep the controller at a distance of at least 0.5m from the lamp.
● When installation remote controller should be located at eye-level. It is suggested at the height of around
1.3~1.5m, with angle of viewing within 30°.
70
Model: HYXE-VA01A
3.5 Checking procedure
□1) Turn ON the power supply for all the indoor units.
A. " " is displayed on the LCD. ← Example when 1 indoor
Note unit is connected, max.16
UNIT
Although a portion of the LCD (liquid crystal units available.
display)of the remote control switch may light B The total number of the indoor units
immediately after the power is turned on, this is not connected is indicated on the LCD.
a malfunction. C In case that the indicated number is not correct, the auto-address
function is not performed correctly due to incorrect wiring, the electric
noise, etc.
Turn OFF the power supply and correct the wiring after checking the
□2) For the models with the auto-address function,
following points;
wait for 3 minutes approximately. The addressing (Do not repeat turning ON and OFF within 10 seconds.)
is automatically performed. (There is a case that 5 1. Power supply for indoor unit is not turned on or incorrect wiring.
minutes is required according to the setting condition.) 2. Incorrect connection of connecting cable between indoor units or
incorrect connecting of controller cable.
71
Model: HYXE-VA01A
3.6 Operation instruction
Operation
Press『 』
Start The operation LED lights up and the unit
starts running.
Press『 』
The operation LED goes out and the unit
Stop stops.
● Once heating operation is stopped, the indoor unit will supply air for around 2 minutes.
Temperature
72
Model: HYXE-VA01A
Temperature
● Room temperature can be displayed after special setting on controller. Please contact the dealer for details.
● Hold 『MODE』 and 『TIMER』for 3s to switch between Celsius and Fahrenheit.
Humidity
● Auto-Dry mode is valid only when such function is available in the indoor unit. Please contact
the dealer for details.
● When connected a dehumidifier with 3-level Dry, the left lower corner shows target humidity value in Dry mode, and only
temperature value can be adjusted. Please contact the dealer for details.
73
Model: HYXE-VA01A
Fan
6-level:
1 (Breeze → SL→ L → M → H → SH → AUTO)
4-level:
( L → M → H → SH → AUTO)
3-level:
( L → M → H → AUTO )
● Air volume is adjustable during Dry operation, but it is defaulted at Low by indoor unit.
● Depending on the types of connected indoor units, Auto mode can display when controlling certain indoor units by wired
remote controller. Please contact the dealers for details.
● AUTO can be set only when this function is available in the indoor unit.
Louver
Attention ● Louver will not display when connected with an indoor unit without louver.
● Louver will not display when connected with an indoor unit without louver.
74
Model: HYXE-VA01A
Louver
● Options of louver setting may vary along with the types of indoor units. Please refer to the manual of indoor unit for
details.
● When the louver is in operation, location display on LCD may not exactly match with the actual location.
● Sometimes the louver may not stop immediately after pressing the key.
2
Press『 』and vertical louver will display in a
reverse manner of the above sequence.
When flashes for 10s, the blades
move and vertical louver starts to swing.
When other icons flash and stop after 10s,
vertical louver stops at set location.
75
Model: HYXE-VA01A
Louver
3
Press『 』and horizontal louver will display
in a reverse manner of the above sequence.
When flashes for 10s, the blades
move and horizontal louver starts to swing.
When other icons flash and stop after 10s,
horizontal louver stops at set location.
76
Model: HYXE-VA01A
Louver
● Louver setting when connected with 1-way cassette type or kitchen indoor units.
2
Press『 』and vertical louver will display in a
reverse manner of the above sequence.
When flashes for 10s, the blades
move and vertical louver starts to swing.
When other icons flash and stop after 10s,
vertical louver stops at set location.
77
Model: HYXE-VA01A
Louver
3
Press『 』and horizontal louver will display
in a reverse manner of the above sequence.
When flashes for 10s, the blades
move and horizontal louver starts to swing.
After other icons flash for 10s and stop,
horizontal louver stops at set location.
78
Model: HYXE-VA01A
Louver
● Louver setting when connected with K3 4-way and K3 2-way cassette type indoor units.
K3 4-way
K3 2-way
2
Press『 』and icons of louvers will display in a reverse
manner of the above sequence.
79
Model: HYXE-VA01A
Additional Functions
● If an indoor unit without any additional functions is connected in,
Attention
"N.A. (non-applicable)" will display when pressing 『FUNCT』 button.
80
Model: HYXE-VA01A
Health
● The icon of Health does not display when connected with an indoor unit without this
Attention
function.
● When the unit is switched from ON to OFF, the Health mode is canceled.
● When operation mode is changed, the Health function does not cancel.
● When the unit is OFF, the User can set if Health function will be auto-on or off when starts up by holding『FUNCT』for
over 5s.
81
Model: HYXE-VA01A
Sleep
Attention ● The icon of Sleep does not display when connected with an indoor unit without this
function. Sleep function invalids when temperature or air volume is restricted.
● When setting to Sleep mode by remote controller, the air volume is at Low, which can be adjusted during Sleep mode.
● Sleep mode is canceled when the air conditioner is switched OFF.
● Sleep mode is canceled when operation mode is changed.
● Sleep mode is canceled when timer power-off is canceled.
● In Sleep mode, timing duration can be adjusted.
82
Model: HYXE-VA01A
Quiet
Attention ● The icon of Quiet does not display when connected with an indoor unit without this
function. Quiet may be invalid when air volume is restricted.
● When setting to Quiet by remote controller, the air volume remains at current level and non-adjustable. Indoor unit will
set volume.
● Quiet mode is canceled when the air conditioner is switched OFF.
● Quite mode is canceled when operation mode is changed.
83
Model: HYXE-VA01A
ECO
Attention ● The icon of ECO does not display when connected with an indoor unit without this
function. ECO is not available when air volume or temperature is restricted, and if
ECO function has been set, the function will be canceled automatically by then.
● When setting ECO function by wired remote controller, set air volume and temperature are non-adjustable. Indoor unit
will set air volume and temperature automatically.
● ECO mode is canceled when the air conditioner is switched OFF.
● ECO mode is canceled when the operation mode is changed.
84
Model: HYXE-VA01A
Electric Heater
Attention ● The icon of Electric Heater does not display when connected with an indoor unit
without this function.
85
Model: HYXE-VA01A
Nature Wind
Attention ● Icon of Nature Wind does not display when connecting with an indoor unit without
this function. Nature Wind may be invalid when air volume is restricted.
86
Model: HYXE-VA01A
Wind Free
Attention ● The icon of Wind Free does not display when connected with an indoor unit without
this function.
● Wind Free is available only in FAN, COOL, HEAT, and DRY modes.
● Wind Free is canceled when the air conditioner is switched OFF.
● Wind Free is canceled when setting of FAN or LOUV is changed.
87
Model: HYXE-VA01A
Human Sense
For indoor units without human sense function, the human sense mode will not be displayed.
88
Model: HYXE-VA01A
Self-cleaning
Attention ● The icon of Self-cleaning does not display when connected with an indoor unit
without this function.
89
Model: HYXE-VA01A
● Self-cleaning is available only in OFF state. And when Self-cleaning is completed, the air conditioner will be OFF
automatically.
● Once in Self-cleaning mode, air volume of indoor unit will decrease or there will be no air supply (cool air drifts out during
operation).
● It gives the preferable effect when there is only one indoor unit in Self-cleaning mode in the whole system, and the rest of
indoor units remain in OFF state.
● During self-cleaning, it may give off the sound of cracking, which is a normal phenomenon and will disappear after
cleaning.
● When Self-cleaning exits, there may be steams occasionally, which is a normal.
● Optimum conditions for frost removal: indoor temp >15°C, humidity >60%, outdoor temp at 0~40°C
● When humidity is less than 20%, frost removal will be affected. It is suggested to perform self-cleaning in the transiting
season with high humidity.
● After self-cleaning, there will be air supply at High for a while, which is a normal phenomenon.
90
Model: HYXE-VA01A
Timer
● Timer power-on: unit operates when timer ends
● Timer power-off: unit stops when timer ends
Timer power-on
● Timer power-on is available only when the air ● When timing range is 0~10h, the adjustment accuracy is 0.5h.
conditioner is OFF. ● When timing range is 10~72h, the adjustment accuracy is 1h.
● Timing range is 0.5~72h.
91
Model: HYXE-VA01A
Timer
Timer power-off
● Timer power-on is available only when the air ● When timing range is 0~10h, the adjustment accuracy is 0.5h.
conditioner is ON. ● When timing range is 10~72h, the adjustment accuracy is 1h.
● Timing range is 0.5~72h.
92
Model: HYXE-VA01A
Lock
● The locked button is determined by values of F8 (Mode), F9 (Temperature), FA (Fan), FB (Louver), FF (Timer) in option
settings, the locking is valid only when all the values of the above items are set to 1.
93
Model: HYXE-VA01A
Other Displays
State
Central Controller
94
Model: HYXE-VA01A
3.7 Alarm indication
Flashing operation LED indicating a communication error. Please contact with the dealer for details.
95
Model: HYXE-VA01A
3.8 Check mode
Normal Mode (When unit is not operating),
Press “FUNCT” +“FAN” simultaneously for more than 5 secs.
There will display the latest alarming code at ① ,
and 00 will be displayed when no alarming.
And then press “ ∨ ” or “ ∧ ” to change to CHECK mode.
96
Model: HYXE-VA01A
3.9 Change indoor unit address
Address of target indoor unit (address number.)
Common mode (when indoor unit stopped)
① Switch to site mode
When stopped, hold 『FUNCT』 and ③ Indoor unit selection
Select address of the indoor unit
『 』for 5s to enter service mode.
to perform auto-addressing
② Site mode selection
Press ∧ ∨ to select indoor unit
address
Press『 』or『 』
to select Service Mode RN The sate of address of target unit
05, and press『OK』to will switch from ON to flashing.
enter address selection
● If an indoor unit without auto-address function is selected, [No
Note
RN
interface.
such function] will display.
④ Change of address
When address of indoor unit is flashing, press ∧ ∨ to change address number (target
address number varies from 00 to 63). Then press OK , the indoor unit address stops
flashing, and the 7- segment display shows AH, indicating a successful change of address.
At this point, the refrigerant system number keeps flashing, press ∧ ∨ to change refrigerant
RN RN
system number (the target system number varies from 00 to 63 and 99). Then press OK ,
the indoor unit refrigerant system number stops flashing, and the 7-segment display shows
AH, indicating a successful change of refrigerant system.
Note:
System "99" is used as a virtual and temporary system number when it runs out of numbers.
It is a must to change it to a number within the normal range.
RN RN
97
Model: HYXE-VA01A
3.10 Address check operation
When one wireless remote controller connects with more than 2 indoor units and the addresses are unknown, appoint the
indoor unit address to perform separate running in order to make sure of the indoor unit address.
Note
● Address check function does not work when there are two
wireless remote controllers.
● During address checking, please do not operate from Confirm the address of target indoor unit
Note
98
Model: HYXE-VA01A
3.11 Address initialization
Use this function to initialize the indoor unit address.
Note
[06] ● If an indoor unit address [AA] is selected, indoor unit without
Flash auto-address initialization function will not clear the address.
④ Address initialization
99