Design Criteria
Design Criteria
ROOF TOP
Design Criteria
PT. DUTA CIPTA KONSULTAMA
JL.Panjang Jiwo 58 Surabaya
Phone : 031-8433166 Fax : 031-8433186
STRUCTURAL ANALYSIS AND DESIGN
FOR SELF SUPPORTING TOWER
I. STANDARD / REFERENCE
a. Steel Structure
- Structure Type = Self Supporting Tower
- Steel Shapes & Plates = ASTM A 36 / JIS G3101 fy = 245 Mpa
c. Anchor Bolt
- Grade of Anchor = ASTM A - 307 fy = 240 Mpa
d. First Coating
- Hot Dipped Galv. = ASTM A - 123 80 microns thickness
e. Concrete
- fc' = 19 Mpa ( 28 days ) / K-225
f. Rebars
- Grade of rebars = Fy 240 MPa for dia. 12 mm < BJTP ; Fy 320 MPa for < dia.13 BJTD
g. Welding Electrodes
- Grade of welding = AWS D1.1 E60XX. fy = 345 Mpa
a. Dead Load
Consist of Weight of Tower structure including antenna, ladder
and appurtenances.
b. Wind Load
Calculated according to TIA / EIA - 222 - F STANDARD : Structural
Standard for Steel Antenna Towers and Antenna Supporting Structures
The design of wind Pressures for the tower structure based on max. wind
velocity = 120 Kph
Where wind force applied to each section of the structure shall be calculated from
the equation :
F = horizontal force applied to a section of the structure ( KN )
qz * GH * [ CF * AE + ΣCA*AA)], but not to exceed 2*qz*GH*AG
qz = Velocity pressure ( Pa )
= .613 Kz V2 for V in m/s
Kz = Exposure Coefficient
[z/10]2/7 for z in meters
1.00 < Kz<2.58
V = basic wind speed for the structure location ( m.s -1)
z = height above average ground level to midpoint of panel of the structure and
appurtenances ( M )
GH = gust response factor
CF = structure force coefficient
e = (AF+AR)/AG
e = solidity ratio
AF = projected area of flat structural component in one face of the section ( m 2 )
AG = gross area of one tower face ( m 2 )
AR = Projected area ( m2 ) of round structural component in one face of the section
AE = efective projected area of structural component in one face ( m 2 )
= DF AF + DR AR RR (m2)
( Note : For tubular steel pole structure, AE shall be the actual projected area based on
diameter or overall width. )
RR = .51e2 + .57 RR<1.0
RR = The reduction factor for round structural component
DF = Wind direction factor
1 for square cross section and normal wind direction
1+ 0.75 e for square cross section and + 45 0 wind direction (1.2 max)
DR = Wind direction factor for round structural components
= 1 ; for square cross section and normal wind direction
= 1+ 0.75 e ; for square cross section and + 45 0 wind direction
(1.2 max)
CA = linear or discrete appurtance force coefficient
AA = projected area of a linear appurtance
CA is depended on Aspect ratio
Aspect Ratio = Overall length/width ratio in plane normal to wind direction
where:
Fa = axial force ( kg )
Fs = side force ( kg )
M = Twisting moment ( kg-m )
Ca = Wind load coeficient
Cs = Wind load coeficient
Cm = Wind load coeficient
V = Wind velocity ( m.p.h )
According to AISC - ASD'89 Standard , only the following load combination shall be
investigated when calculating the maximum member stresses and structure reaction :
COMB 1 = DL
COMB 2 = DL + LL
COMB 3 = DL + LL ± WL
Where ;
DL : Dead Load
LL : Live Load
WL : Wind Load
V. DESIGN TOLERANCES
The unit stresses in the stucture membersdo not aceed the allowable unit stresses
for the materials as specified in the EIA standard EIA - 222 - F.
1. Tension
Ft = 0.60 Fy ( Kg/cm2 )
2. Shear
Fv = 0.40 Fy ( Kg/cm2 )
3. Compression
i ) On the gross section of axial loaded compression members when kl/r is less than Cc :
⎡ kl r ⎤
⎢ 1 − 2 Cc 2 ⎥ Fy
Fa = ⎣ ⎦ ( Kg / cm 2
)
3 3
5 3 ( kl r ) ( kl / r )
+ −
3 8 Cc 8 Cc 3
2π 2 E
where ; Cc =
Fy
ii ) On the gross section of axial loaded compression member, when kl/r exceeds
12 π 2 E
Fa = ( Kg / cm 2 )
Fy
4) Bending
Tension and compression on extreme fibers :
Fb = 0.66 Fy (Kg/cm2)
5) Tension on Bolts
Fv = 0.60 Fy ( kg/cm2 )
6) Shear on Bolts
Fv = 0.30 Fy ( kg/cm2 )
7) Bearing on Bolts
Fp = 1.20 Fv ( kg/cm2)