Harmonic Loss & Overload Loss Calculation for Rectifier Transformers-EN145.00.

01

Job # DA512AB Design # 46015MA58

Winding Temp. rise @ 100% load = 55 °C


Eddy Loss Calculation:
HV LV
Harmonic Eddy Loss factor (FHL-WE) = 4 4
Total Load Loss@15 MVA = 53355 W .@55 ref Harmonic Other Stray Loss factor(FHL-OSL) = 1.34 1.34
at minimum tap p.u RMS current with Harmonics = 1.040 1.040

No Load Loss = 13162 W

A. Total Loss including harmonic Loss for Cooling:

1. Eddy loss shall be estimated using Andersen or FEMM.


at minimum tap

Eddy loss for LV1= A= 1602 LV1 I2R Loss = 19225 W .@15 MVA .@55 ref

Eddy loss for LV2= B= 0 LV2 I2R Loss = 0 W

Eddy loss for HV= C= 1059 HV I2R Loss = 27171 W .@15 MVA .@55 ref

Total Eddy loss=A+B+C= 2661 Total I2R Loss = 46396 W AT MIN TAP

2. Other stray Losses (OSL)= Load Loss -I2R of all windings-(A+B+C)

OSL=D= 53355 - 46396 - 2661 = 4298 W

3. LL of LV1 with harmonics= I2R Loss x (Irms)^2 + Eddy LossLV1 x FHL-WE

E= 19225 X 1.0816 + 1602 X 4 = 27202 W

LL of LV2 with harmonics= I2R Loss x (Irms)^2 + Eddy LossLV2 x FHL-WE

F= 0 X 1.082 + 0 X 4 = 0 W

LL of HV with harmonics= I2R Loss x (Irms)^2 + Eddy LossHV x FHL-WE

G= 27171 X 1.082 + 1059 X 4 = 33624 W

4. OSL (with harmonics) = OSL x FHL-OSL

H= 4298 X 1.34 = 5759

5. Total Loss for Cooling = E + F + G + H + No-load Loss =

= 27202 + 0 + 33624 + 5759 + 13162 = 79747 W

6 Total load loss with Harmonics = 66585


Job # DA512AB Design # 46015MA58

B. Winding Temperature Rise (Dry-Type) or Gradient (Liquid-filled) Correction @KNAN:


0.8
 LLcalculated 
Corrected Temperature Rises =   × Temp.rise computer
 LL 
 computer 

Load Losses from ODE, LV1 = 22655 W LV2 = 0 W HV = 29435 W

Temperature Rise from ODE, LV1 = 15.03 ⁰C LV2 = 0 ⁰C HV = 13.68 ⁰C

0.8 0.8
 27202   0 
LV1 =  22655
 ×15.03 = 17.4 ⁰C LV2 =  0  × 0 = #DIV/0! ⁰C
   
0.8
 33624  Gradients @ W/Harmonics
HV =   × 13.68 = 15.22 ⁰C
29435
 

C. Winding Temperature Rise (Dry-Type) or Gradient (Liquid-filled) Correction @RI-9 LOAD:


0.8
 LLcalculated 
Corrected Temperature Rises =   × Temp.rise computer
 LL 
 computer 

Load Losses from ODE, LV1 = 22655 W LV2 = 0 W HV = 29435 W

Temperature Rise from ODE, LV1 = 24.94 ⁰C LV2 = 0 ⁰C HV = 23.52 ⁰C

0.8 0.8
 27202   0 
LV1 =  22655  ×24.94 = 28.87 ⁰C LV2 =  0  × 0 = #DIV/0! ⁰C
   
0.8
 33624  Gradients @ W/Harmonics
HV =   × 23.52 = 26.16 ⁰C
29435
 

Design: 3NAD Checked by: ___________