Professional Documents
Culture Documents
High Impedance Technical Report
High Impedance Technical Report
2.4 Thermal Rating of Resistors The nlr must be chosen to match the relay circuit
The resistors incorporate in the scheme must be setting voltage (i.e. its characteristic must not change
capable of withstanding the associated thermal significantly until beyond the relay setting Vs) and it
conditions. must be capable of passing the maximum prospective
fault current that can be transformed by the CT.
2.4.1 Continuous Power Rating
The continuous power rating of a resistor is defined The type of Metrosil required (the nlr used by
as: Reyrolle) is chosen by its thermal rating as defined by
the formula:
Pcon = (Icon)² R ...(5)
P = 4/π x Ifs x Vk ...(9)
where,
Pcon = resistor continuous power rating. There are two types of Metrosil available the 3 inch
Icon = continuous resistor current i.e. the type with a maximum rating of 11kJ/s and the 6 inch
operating current of the relay type with a maximum rating of 35kJ/s.
R = resistance.
2.6 Fault Setting
2.4.2 Half-second Power Rating The primary operating current or fault setting may be
The rms voltage developed across a resistor for calculated from:
maximum internal fault conditions is defined as:
If = (nIe + Is + Inlr)/T ...(10)
Vf = (Vk³ x R x Ifs)¼ x 1.3 ...(6)
where,
where, If = primary fault setting.
Vf = rms voltage across resistor. n = number of CTs in parallel.
Ifs = maximum secondary fault current which Ie = exciting current of each CT at the relay
can be calculated from the circuit breaker circuit setting voltage (assuming all CTs
rating, Icb, if the maximum internal fault are identical).
current is not given. The maximum Inlr = current in non linear resistor at the relay
internal fault current is usually the same circuit setting voltage.
as the maximum through fault current.
This current, If, should fall within the recommended fault
Thus the half-second power rating is given by: setting given by the relevant ESI standard, the clients
specification or in the absence of these good engineering
practice, and be significantly greater than a specified
Phalf = Vf² /R ...(7)
minimum, Im, (where Im is a percentage of the minimum
primary fault current, Imin).
If the calculated If is lower than a specified minimum (i.e. it is 3.2 Relay Setting Voltage
too sensitive) then a shunt setting resistor is required in Primary through-fault current:
order to raise the fault setting. The current following through Itf = 35000MVA / (√3 x 400kV)
the shunt resistor is given by:
= 50518A
Ish = ImT - nIe - Is - Inlr ...(11) From eqn (2)
Vstab = (50518A / 2000) x (2 + 1.5)
where, = 89V
Ish = current through shunt resistor.
From eqn (3)
Therefore, the shunt setting resistance is: Vs < 600V / 2 = 300V
Rsh = Vs/Ish ...(12) Thus to maintain stability for maximum through fault
current the relay needs to be set at a voltage in the
3. WORKED EXAMPLE range 89V to 300V.
The following worked example is based on the 3.3 Stabilising Resistor
application of a Reyrolle DAD relay to a single phase Using eqn (4) and assuming the relay voltage to be
to earth busbar fault (Figure 1). negligible.
Thus,
Rsh = 100V / 0.11A
= 909