Professional Documents
Culture Documents
Line Differantial
Line Differantial
Line Differantial
4th Edition
All rights with respect to this document, including applications for patent and
registration of other industrial property rights, are reserved. Unauthorised use, in
particular reproduction or making available to third parties without our explicit consent
in writing, is prohibited.
The use is only allowed for the purpose laid down in the contract.
This document has been carefully prepared and reviewed. Should in spite of this the
reader find an error, he is requested to inform us at his earliest convenience.
The data contained herein purport solely to describe the product and are not a
warranty of performance or characteristic. It is with the best interest of our customers
in mind that we constantly strive to improve our products and keep them abreast of
advances in technology. This may, however, lead to discrepancies between a product
and its “Technical Description” or “Operating Instructions”.
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Contents
1. INTRODUCTION ........................................................................ 3
1.1. Reference documents................................................................. 3
1.2. Scope.......................................................................................... 3
1.2.1. Software version ......................................................................... 3
1.2.2. Contents of IEC60870-5-103 ...................................................... 3
1.2.3. RE.316*4 configuration requirements ......................................... 3
2. INTEROPERABILITY.................................................................. 4
2.1. Compatibility level ....................................................................... 4
2.2. Identification string ...................................................................... 4
2.3. Physical layer.............................................................................. 4
2.3.1. Electrical interface ...................................................................... 4
2.3.2. Optical interface.......................................................................... 4
2.3.3. Transmission speed.................................................................... 4
2.4. Application layer ......................................................................... 5
2.4.1. Basic application functions.......................................................... 5
2.4.2. Measurands rated value ............................................................. 5
2.4.3. Measurands ASDUs ................................................................... 6
1
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
2
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
1. INTRODUCTION
1.2. Scope
3
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
2. INTEROPERABILITY
A B B D x y y
optical; plastic
x 19200 bit/s
4
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
x Disturbance Data
Private Data
current L1 x
current L2 x
current L3 x
voltage L1-E x
voltage L2-E x
voltage L3-E x
active power P x
reactive power Q x
frequency f x
voltage L1 - L2 x
5
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
x ASDU 9 measurands II
6
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Characteristics 316BM61b
connector F-SMA
cable type graded index 62.5/125 µm
optical wavelength 850 nm
temperature range -5...+55°C
transmission power in fibre -18.2...-11.2 dBm
minimal receiving power -24.0...-10.0 dBm
budget worst case 5.8 dB
budget typical 12.8 dB
typical distance 1000…3000 m (*)
Consumption +12 V < 21 mA
Consumption -12 V < 42 mA
7
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
3.3.1. General
In the tables below the signals of the RE.316*4 distance protec-
tion are listed. The tables have the following columns:
INF The information number according to [1].
GI An x means: the signal is a part of the general in-
terrogation.
Description Textual description of the signal according to [1].
Function The RE.316*4 function according to the table in
Section 5.1.
Signal RE.316*4 signal designation.
The combination ‘Function’ and ‘Signal’ uniquely defines the ori-
gin of each information number in the RE.316*4. Some signals
are generated by the communication interface or the diagnostic
software and have no direct coupling to a function or signal in
the RE.316*4. These signals are marked ‘Internal’ in the ‘Func-
tion’ column.
The function type of all public signals is 192 (Line Differential
Protection).
8
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
9
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
10
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
The group warning and group error signals are derived from the
diagnostic of the RE.316*4. They are not possible to be forced
for test purposes.
2) In the event that a breaker failure protection is configured, then their signals ‘TRIP t1
L1’, ‘TRIP t1 L2’ and ‘TRIP t1 L3’ are also transmitted, provided that their event re-
cording is switched on
11
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
3.3.8. Commands
The following table describes which general commands are sup-
ported.
Caution:
• To be able to switch the characteristic by command
the parameter “Rem. Setting” of the system function
must be T (ON) (from SW V5.1c).
• Switching the characteristic restarts the unit
12
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
AnalogInp 2 - 75
AnalogInp 3 - 76
AnalogInp 4 - 77
AnalogInp 5 - 78
AnalogInp 6 - 79
AnalogInp 7 - 80
AnalogInp 8 - 81
AnalogInp 9 - 82
13
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
BinInp 8 -
BinInp 9 -
BinInp 10 -
BinInp 11 -
BinInp 12 -
BinInp 13 -
BinInp 14 -
BinInp 15 -
BinInp 16 -
14
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
4.1. General
The RE.316*4 supports the transmission of generic events (bi-
nary signals) and generic measurands. For this “VDEW6EKZ”
must be selected as project directory (see Section 5.2). General
interrogation is also supported, but not general write and read
commands, however (see Section 4.4). Generic data are always
transmitted in the format of an ASDU 10 (ASDU = Application
Service Data Unit) (see Section 7.3.1.9 in [1]. Thereby the in-
formation number 244 is always used, i. e. only single values
are transmitted. The termination of the general interrogation is
signalled by an ASDU with the information number 245. In the
other fields of the ASDU there are defined the data for the group
numbers and the entry, as specified in the following chapters.
15
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
16
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
5. CONFIGURATION GUIDE
System functions
1 System_Vers -
2 SigToSCS -
3 System -
6 BinInp Card -
7 TripOut Hold -
10 Analog Outpu -
17
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
11 LBIO’s -
12 RBIO’s -
13 Analog Input -
Parameter Setting
1.Prim/sec Ratio… All Prim Ratios from 1…9 must be set to the
9.Prim/sec Ratio ratios of the CTs and VTs actually installed.
18
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
5.1.2. System IO
These signals generate fault and status indications.
Editor / System Parameters
Parameter Setting
GenStart
Test active
HMI is on
19
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Parameter Setting
Trip-S
Trip-T
5.1.5. Autoreclosure
Editor / Configure Prot Func / Autoreclosure / Binary inputs
Parameter Setting
Parameter Setting
20
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
5.1.6. IEC60870-5-103
Parameters in the sub-menus ‘General’, ‘Binary Inp’ and ‘Binary
Out’ have to be configured for the IEC60870-5-103 function,
which has more parameters than described here. The additional
parameters are intended for future generic services (see Section
5.2).
Path:
Editor / Configure Prot Func / IEC60870-5-103 / General
If the generic services are being used, select the file ‘PRO-
JECT1 BIN’ in the subdirectory ‘VDEW6EKZ’ of the HMI direc-
tory, otherwise ‘PROJECT1.BIN’ in the subdirectory ‘VDEW6’.
The project directory then appears as ‘VDEW6EKZ’ resp.
‘VDEW6’.
Editor / Configure Prot Func / IEC60870-5-103 / Binary Inp
There are four alternative procedures for configuring the
IEC60870-5-103 binary inputs:
1. Direct setting via the HMI to ‘always off’ resp. ‘always ON’
2. Configure binary input
3. Configure the output of a protection function.
4. Configure an SCS signal (mandatory for the command in-
puts).
The procedure chosen depends on the settings of the protection
unit.
Parameter Setting
IN_HILFSEING_3
IN_HILFSEING_4
21
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Parameter Setting
Parameter Setting
22
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Parameter Setting
Remaining signals Must all be left with the default setting <blank>
i.e. not configured to anything.
Parameter Setting
23
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Parameter Setting
BinInp 1…16 (BinaryAddr) For interoperable use the following must apply:
• Assign GenStart to one BinInp (any).
• Assign GenTrip to one BinInp (any).
• Any signal may be assigned to any of the
remainder (see Section 3.4.2 for addressing
of the tags).
• Unused BinInp’s must be set to ‘always
OFF’ (default).
BinInp 1…16 (Select) Must all be set to “no trig”.
24
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Parameter Setting
25
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
Parameter Setting
5.2.2. Measurands
There are 16 freely configurable generic measurands available.
They can be assigned to any measurement output of any
RE.316*4 function. In the MW Inputs menu the source of the
measurand in RE.316*4 is selected and in the MW Outputs
menu a value is set in order to activate the measurand for the
communication interface.
Parameter Setting
Parameter Setting
26
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
6. TEST GUIDE
27
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
28
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
29
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
30
IEC60870-5-103 1MRB520229-Uen / Rev. B ABB Switzerland Ltd
LINE DIFFERENTIAL PROTECTION IN RE.316*4
31
ABB Switzerland Ltd IEC60870-5-103 1MRB520229-Uen / Rev. B
LINE DIFFERENTIAL PROTECTION IN RE.316*4
32
Notification Form for Errors in this Document
Dear User,
We constantly endeavour to improve the quality of our technical publications and
would like to hear your suggestions and comments. Would you therefore please fill in
this questionnaire and return it to the address given below.
Do you find the publication readily understandable and logically structured? Can you
make any suggestions to improve it?
Is the information sufficient for the purpose of the publication? If not, what is missing
and where should it be included?
Name: Date:
Company:
Remarks/Description of fault:
Customer: Date:
Address:
Customer: Date:
Address:
___________________________________________________________________
ACTION (internal use of ABB Switzerland Ltd, Dept. PTUSX only)
Received by: Date:
Answered by: Date:
www.abb.com/substationautomation