Professional Documents
Culture Documents
Distance PRD
Distance PRD
Distance PRD
Distance Protection
in RE.316*4
p
Operating Instructions
1998 ABB Switzerland Ltd
Baden
4th Edition
All rights with respect to this document, including applications for patent and
registration of other industrial property rights, are reserved. Unauthorised use, in
particular reproduction or making available to third parties without our explicit consent
in writing, is prohibited.
The use is only allowed for the purpose laid down in the contract.
This document has been carefully prepared and reviewed. Should in spite of this the
reader find an error, he is requested to inform us at his earliest convenience.
The data contained herein purport solely to describe the product and are not a
warranty of performance or characteristic. It is with the best interest of our customers
in mind that we constantly strive to improve our products and keep them abreast of
advances in technology. This may, however, lead to discrepancies between a product
and its “Technical Description” or “Operating Instructions”.
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Contents
1. INTRODUCTION ........................................................................ 3
1.1. Reference documents................................................................. 3
1.2. Scope.......................................................................................... 3
1.2.1. Software version ......................................................................... 3
1.2.2. Contents of IEC60870-5-103 ...................................................... 3
1.2.3. RE.316*4 configuration requirements ......................................... 3
2. INTEROPERABILITY.................................................................. 4
2.1. Compatibility level ....................................................................... 4
2.2. Identification string ...................................................................... 4
2.3. Physical layer.............................................................................. 4
2.3.1. Electrical interface....................................................................... 4
2.3.2. Optical interface.......................................................................... 4
2.3.3. Transmission speed.................................................................... 4
2.4. Application layer ......................................................................... 5
2.4.1. Basic application functions.......................................................... 5
2.4.2. Measurands rated value ............................................................. 5
2.4.3. Measurands ASDUs ................................................................... 6
1
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
2
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
1. INTRODUCTION
1.2. Scope
3
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
2. INTEROPERABILITY
A B B L x y y
optical; plastic
x 19200 bit/s
4
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
x Disturbance Data
Private Data
current L1 x
current L2 x
current L3 x
voltage L1-E x
voltage L2-E x
voltage L3-E x
active power P x
reactive power Q x
frequency f x
voltage L1 - L2 x
5
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
x ASDU 9 measurands II
6
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Characteristics 316BM61b
connector F-SMA
cable type graded index 62.5/125 µm
optical wavelength 850 nm
temperature range -5...+55°C
transmission power in fibre -18.2...-11.2 dBm
minimal receiving power -24.0...-10.0 dBm
budget worst case 5.8 dB
budget typical 12.8 dB
typical distance 1000…3000 m (*)
Consumption +12 V < 21 mA
Consumption -12 V < 42 mA
7
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
3.3.1. General
In the tables below the signals of the RE.316*4 distance protec-
tion are listed. The tables have the following columns:
INF The information number according to [1].
GI A x means: the signal is a part of the general inter-
rogation.
Description Textual description of the signal according to [1].
Function The RE.316*4 function where the signal originates
from according to the table in Section 5.1.
Signal The signal of the RE.316*4 function from which the
information number origins.
The combination ‘Function’ and ‘Signal’ uniquely defines the ori-
gin of each information number in the RE.316*4. Some signals
are generated by the communication interface or the diagnostic
software and have no direct coupling to a function or signal in
the RE.316*4. These signals are marked ‘Internal’ in the ‘Func-
tion’ column.
The function type of all public signals is 128 (distance protection).
8
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
9
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
10
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
The signal "I>> backup operation" is only set when the distance
function is blocked. The backup function, however, can only be
blocked by the inverted signal "Dist Blocked" and is otherwise
always active (see Section 5.1.4.).
The group warning and group error signals are derived from the
diagnostic of the RE.316*4. They are not possible to force for
test purposes.
11
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
12
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
2) In the event that a breaker failure protection is configured, then their signals ‘TRIP t1
L1’, ‘TRIP t1 L2’ and ‘TRIP t1 L3’ are also transmitted, provided that their event re-
cording is switched on.
13
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
3.3.8. Measurements
All measurements have a deadband supervision based on a delta
and a time-out. If the measurand changes more than 5% of nominal
value the measurand is updated. If no changes are detected the
measurand is updated every x seconds. The x seconds are con-
figurable and can range between 10...1000 seconds (see parame-
ter ‘EventTxDelay’ in Section 5.1.3).
14
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
3.3.9. Commands
The following table describes which general commands are sup-
ported.
Caution:
• To switch the characteristic by command the parameter
“Rem. Setting” of the system function must be T (ON)
(from SW V5.1c).
• Switching the characteristic restarts the unit.
15
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
16
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
17
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
BinInp 12 -
BinInp 13 -
BinInp 14 -
BinInp 15 -
BinInp 16 -
18
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
4.1. General
The RE.316*4 supports the transmission of generic events (bi-
nary signals) and generic measurands. For this “VDEW6EKZ”
must be selected as project directory (see Section 5.2). General
interrogation is also supported, but not general write and read
commands, however (see Section 4.4). Generic data are always
transmitted in the format of an ASDU 10 (ASDU = Application
Service Data Unit) (see Section 7.3.1.9 in [1]. Thereby the in-
formation number 244 is always used, i. e. only single values are
transmitted. The termination of the general interrogation is sig-
nalled by an ASDU with the information number 245. In the other
fields of the ASDU there are defined the data for the group num-
bers and the entry, as specified in the following Chapters.
19
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
20
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
5. CONFIGURATION GUIDE
1 System_Vers -
2 SigToSCS -
3 System -
6 BinInp Card -
7 TripOut Hold -
11 LBIO’s -
21
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
12 RBIO’s -
13 Analog Input -
18 Check-U3ph ChU3
19 EarthFaultsIsolated EFForw
(Fward), resp. Earth- resp.
FaultGrounded2 *) EF
20 EarthFaultsIsolated EFBack
(Bward) *)
21 Measurement Meas 1
22 Measurement Meas 2
27 DisturbanceRec DistRec
*) From Version V6.4 onwards, an earth fault function for grounded systems
may also be chosen instead of the two earth fault functions for un-
grounded systems
The two earth fault functions for ungrounded systems must al-
ways be configured so that the first function is for the forwards
22
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
direction and the second is for the backward direction. Any num-
ber of extra earth fault functions may follow but not precede
these two functions.
The measurement functions must not follow in a strict sequence
but other functions may be configured in between.
If one or several functions are not configured, then the corre-
sponding information numbers (see Section 3.3) will also be
missing.
Parameter Setting
1. Prim/sec Ratio… All Prim Ratios must be set to the ratios of the
9. Prim/sec Ratio CTs and VTs actually installed.
5.1.2. System IO
These signals generate fault and status indications.
Editor / System Parameters
Parameter Setting
GenStart
Test active
HMI is on
Parameter Setting
23
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
Parameter Setting
24
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
Overcurrent Protection
Parameter Setting
25
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
Binary Inputs
Parameter Setting
26
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Signalling Outputs
Parameter Setting
Start S
Start T
Start E
Trip CB R
Trip CB S
Trip CB T
Delay 4
Delay Def
Meas Bward
27
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
5.1.5. Autoreclosure
Editor / Configure Prot Func / Autoreclosure / Binary inputs
Parameter Setting
Parameter Setting
28
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
5.1.6. IEC60870-5-103
Parameters in the sub-menus ‘General’, ‘Binary Inp’ and ‘Binary
Out’ have to be configured for the IEC60870-5-103 function,
which has more parameters than are described here. The addi-
tional parameters are intended for the future generic services
(see Section 5.2).
Path:
Editor / Configure Prot Func / IEC60870-5-103 / General
If the generic services are being used, select the file ‘PROJECT1
BIN’ in the subdirectory ‘VDEW6EKZ’ of the HMI directory, oth-
erwise ‘PROJECT1.BIN’ in the subdirectory ‘VDEW6’. The pro-
ject directory then appears as ‘VDEW6EKZ’ resp. ‘VDEW6’.
Editor / Configure Prot Func / IEC60870-5-103 / Binary Inp
There are four alternative procedures for configuring the VDEW6
binary inputs:
1. Direct setting via the HMI to ‘always off’ resp. ‘always on’
2. Configure binary input
3. Configure the output of a protection function
4. Configure an SCS signal (mandatory for the command in-
puts).
The chosen possibility depends on the settings of the protection
unit.
Parameter Setting
IN_HILFSEING_3
IN_HILFSEING_4
29
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
Parameter Setting
OUT_HILFSEING_4
OUT_HF_GESTOERT
OUT_HF_EMPFANG
30
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
31
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
5.1.7. Check-I3ph
Editor / Configure Prot Func / Check-I3ph
Parameter Setting
5.1.8. Check-U3ph
Editor / Configure Prot Func / Check-U3ph
Parameter Setting
Parameter Setting
Parameter Setting
32
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Parameter Settings
5.1.12. Measurement
The communication interface uses the first five measuring func-
tions it finds in the set file for the publicly defined measurands. It
is important that these first five measuring functions are config-
ured as described below. If you need further measuring functions
they must be configured after these five measuring functions.
The five functions need not be configured strictly after each
other, but other functions may be configured inbetween.
From Version V6.2 onwards, a three-phase measuring function
is included with the designation “MeasureModule”, which can be
used instead of the third, fourth and fifth ‘Measurement’ function.
The communication interface uses the first function it finds in the
list of configured functions. It is not permissible to configure the
“MeasureModule” function between the third and fourth or fourth
and fifth ‘Measurement’ functions as this would produce invalid
results.
The first ‘Measurement’ function supplies the values I, U, P and
Q for the data unit 3.3 according to [1]. It is important that the
angle is set to compensate for the difference between the RS
delta voltage and the phase S current.
33
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
PN 1.00
Parameter Setting
Angle Irrelevant
PN Irrelevant
34
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
Angle 0 degree
PN 1.00
Parameter Setting
Angle 0 degree
PN 1.00
Parameter Setting
Angle 0 degree
PN 1.00
35
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
5.1.13. MeasureModule
From Version V6.2 onwards, a three-phase measuring function
is included with the designation “MeasureModule”, which can be
used instead of the third, fourth and fifth ‘Measuring’ functions.
The communication interface uses the first function in the list of
configured functions, i.e. the “MeasureModule” function is used if
it is configured first, but if five ‘Measuring’ functions are config-
ured first, the results generated by the third, fourth and fifth
‘Measuring’ functions are used for transferring the three-phase
measurements. The “MeasureModule” function can be config-
ured at any position excepting between the third and fourth or
fourth and fifth ‘Measuring’ functions as this would produce inva-
lid results.
Editor / Configure Prot Func / MeasureModule
Parameter Setting
PN 1.000
Parameter Setting
23310 Trip t2
23325 Trip t1 L3
36
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
37
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
BinInp 1…16 (BinaryAddr) For interoperability use the following must ap-
ply:
• Assign GenStart to one BinInp (any).
• Assign GenTrip to one BinInp (any).
• Any signal may be assigned to any of the
remainder (see Section 3.4.2 for addressing
of the tags).
• Unused BinInp’s must be set to ‘always
OFF’ (default).
BinInp 1…16 (Select) Must all be set to “no trig”.
38
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
39
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
Parameter Setting
5.2.2. Measurands
There are 16 freely configurable generic measurands available.
They can be assigned to any measurement output of any
RE.316*4 function. In the MW Inputs menu the source of the
measurand in RE.316*4 is selected and in the MW Outputs
menu a value is set in order to activate the measurand for the
communication interface.
Parameter Setting
Parameter Setting
40
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
6. TEST GUIDE
41
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
42
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
43
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
44
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
45
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
<51> x Earth fault forward, i.e. line Cause the forward (first) earth
fault protection function to trip
and check:
• the GI status and events.
46
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
47
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
<73> - Fault location X in Ohm Make a fault for the distance pro-
tection function so that it trips and
check:
• that the fault location (in pri-
mary ohms) is correct.
<74> - Fault forward/line Make a fault for the distance pro-
tection function so that it trips in
the forward direction and check:
• the events.
48
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4
<129> - “Close CB” by slow AR Inject a fault that excites the auto-
reclosure function two or more
times if configured, and check:
• the events.
49
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4
6.3.6. Measurements
For all measurands configured:
Inject currents and voltages to the RE.316*4, let the values stay
stable and check:
• that the values are sent with the time interval defined for the
deadband supervision.
• that the values are correct in sign and magnitude.
Change the injected values a few times and check:
• that the values are sent immediately upon a change of at least
5% of an injected value.
50
Notification Form for Errors in this Document
Dear User,
We constantly endeavour to improve the quality of our technical publications and
would like to hear your suggestions and comments. Would you therefore please fill in
this questionnaire and return it to the address given below.
Do you find the publication readily understandable and logically structured? Can you
make any suggestions to improve it?
Is the information sufficient for the purpose of the publication? If not, what is missing
and where should it be included?
Name: Date:
Company:
Remarks/Description of fault:
Customer: Date:
Address:
Customer: Date:
Address:
___________________________________________________________________
ACTION (internal use of ABB Switzerland Ltd, Dept. PTUSX only)
Received by: Date:
Answered by: Date:
www.abb.com/substationautomation