Distance PRD

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

IEC60870-5-103 1MRB520226-Uen

Edition August 2003

Distance Protection
in RE.316*4
p
Operating Instructions
 1998 ABB Switzerland Ltd
Baden

4th Edition

Applies from software version V6.x up to V7.x

All rights with respect to this document, including applications for patent and
registration of other industrial property rights, are reserved. Unauthorised use, in
particular reproduction or making available to third parties without our explicit consent
in writing, is prohibited.
The use is only allowed for the purpose laid down in the contract.

This document has been carefully prepared and reviewed. Should in spite of this the
reader find an error, he is requested to inform us at his earliest convenience.

The data contained herein purport solely to describe the product and are not a
warranty of performance or characteristic. It is with the best interest of our customers
in mind that we constantly strive to improve our products and keep them abreast of
advances in technology. This may, however, lead to discrepancies between a product
and its “Technical Description” or “Operating Instructions”.
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

Contents

1. INTRODUCTION ........................................................................ 3
1.1. Reference documents................................................................. 3
1.2. Scope.......................................................................................... 3
1.2.1. Software version ......................................................................... 3
1.2.2. Contents of IEC60870-5-103 ...................................................... 3
1.2.3. RE.316*4 configuration requirements ......................................... 3

2. INTEROPERABILITY.................................................................. 4
2.1. Compatibility level ....................................................................... 4
2.2. Identification string ...................................................................... 4
2.3. Physical layer.............................................................................. 4
2.3.1. Electrical interface....................................................................... 4
2.3.2. Optical interface.......................................................................... 4
2.3.3. Transmission speed.................................................................... 4
2.4. Application layer ......................................................................... 5
2.4.1. Basic application functions.......................................................... 5
2.4.2. Measurands rated value ............................................................. 5
2.4.3. Measurands ASDUs ................................................................... 6

3. PUBLIC PART SIGNALS AND FUNCTIONS ............................. 7


3.1. Physical connection .................................................................... 7
3.2. Supported application functions.................................................. 8
3.3. Supported public signals............................................................. 8
3.3.1. General ....................................................................................... 8
3.3.2. System functions ........................................................................ 9
3.3.3. Status indications...................................................................... 10
3.3.4. Supervision indications ............................................................. 11
3.3.4. Earth fault indications................................................................ 12
3.3.6. Fault indications........................................................................ 13
3.3.6. Auto-reclosure indications......................................................... 14
3.3.8. Measurements .......................................................................... 14
3.3.9. Commands ............................................................................... 15
3.4. Transfer of disturbance data ..................................................... 16
3.4.1. CT/VT inputs supported ........................................................... 16
3.4.2. Supported tags ......................................................................... 17

4. GENERIC PART SIGNALS AND FUNCTIONS ........................ 19


4.1. General ..................................................................................... 19
4.2. Generic events and general interrogation ................................. 19
4.3. Generic measurements............................................................. 19
4.4. Generic read and write.............................................................. 20

1
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

5. CONFIGURATION GUIDE ....................................................... 21


5.1. System and Protection functions .............................................. 21
5.1.1. CT/VT channels ........................................................................ 23
5.1.2. System IO ................................................................................. 23
5.1.3. IBB configuration ...................................................................... 23
5.1.4. (High-voltage) Distance Protection ........................................... 25
5.1.5. Autoreclosure............................................................................ 28
5.1.6. IEC60870-5-103 ....................................................................... 29
5.1.7. Check-I3ph ............................................................................... 32
5.1.8. Check-U3ph.............................................................................. 32
5.1.9. Earth fault ungrounded system forward .................................... 32
5.1.10. Earth fault ungrounded system backward................................. 32
5.1.11. Earth fault grounded ................................................................. 33
5.1.12. Measurement............................................................................ 33
5.1.13. MeasureModule ........................................................................ 36
5.1.14. Breaker failure protection.......................................................... 36
5.1.15. Disturbance recorder ................................................................ 37
5.2. Generic signals ......................................................................... 39
5.2.1. Binary Inp.................................................................................. 39
5.2.2. Measurands .............................................................................. 40

6. TEST GUIDE ............................................................................ 41


6.1. Test of the physical connection................................................. 41
6.2. Test of the link connection ........................................................ 42
6.3. Signals test ............................................................................... 43
6.3.1. Status indications...................................................................... 44
6.3.2. Supervision indications ............................................................. 46
6.3.3. Earth fault indications................................................................ 46
6.3.4. Fault indications........................................................................ 47
6.3.5. Auto-reclosure indications......................................................... 49
6.3.6. Measurements .......................................................................... 50
6.4. Checking disturbance data ....................................................... 50
6.5. Testing generic signals ............................................................. 50

2
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

1. INTRODUCTION

1.1. Reference documents


The following references serves as a base for this description.
[1] IEC60870-5-103, TELECONTROL EQUIPMENT AND
SYSTEMS, PART 5-103 Transmission Protocols, First
Edition, December 1997
[2] RE.316*4 Operating Instructions

1.2. Scope

1.2.1. Software version


The following description is valid for the „VDEW“ variant of the
RE.316*4 firmware.

1.2.2. Contents of IEC60870-5-103


IEC60870-5-103 defines the four types of protection distance,
transformer differential, overcurrent and line differential protec-
tion. These Operating Instructions only concern distance protec-
tion.
The functions described in IEC60870-5-103 are divided into the
three categories “Public Defined Signals”, “Disturbance Data
Transfer” and “Generic Services”. This paper describes the parts
“Public Defined Signals” and “Disturbance Data Transfer”.

1.2.3. RE.316*4 configuration requirements


The RE.316*4 is only configured as a distance protection in the
sense of IEC60870-5-103 when all conditions listed below are
fulfilled:
• The distance protection function is configured once.
• Neither a transformer differential nor a line differential function
may be configured.
• The IEC60870-5-103 function is configured.
• When operating with several parameter sets, the IEC60870-5-
103 function may not be configured a second time, but must
be copied from the first parameter set.

3
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

2. INTEROPERABILITY

2.1. Compatibility level


Level 3
With reduced generic functionality. Read and write commands
are accepted but not executed. No directory is implemented.

2.2. Identification string

A B B L x y y

Manufacturer ID is: ABB


Version ID is: Lxyy,
where x.yy is the SW version of the RE.316*4.

2.3. Physical layer

2.3.1. Electrical interface


EIA RS-485

number of loads ........ for one protection equipment

Electrical interface is not supported.

2.3.2. Optical interface


x optical; glass fibre

optical; plastic

x F-SMA type connector

BFOC/2,5 type connector

2.3.3. Transmission speed


x 9600 bit/s

x 19200 bit/s

4
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

2.4. Application layer

2.4.1. Basic application functions


Test Mode

x Blocking of Monitoring Direction

x Disturbance Data

x Generic Services, partly

Private Data

2.4.2. Measurands rated value


Measurands are transmitted with ASDU 3 as well as with ASDU 9.
As defined in [1], paragraph 7.2.6.8 "Measurands with Quality
descriptor", the maximum MVAL can either be 1.2 or 2.4 the
rated value. No different rating shall be used in ASDU 3 and
ASDU 9, i.e. for each measurand is only one choice.

Measurand rated value


1.2 or 2.4

current L1 x

current L2 x

current L3 x

voltage L1-E x

voltage L2-E x

voltage L3-E x

active power P x

reactive power Q x

frequency f x

voltage L1 - L2 x

5
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

2.4.3. Measurands ASDUs


ASDU 3.1 measurands I

ASDU 3.2 measurands I

x ASDU 3.3 measurands I

x ASDU 3.4 measurands I

x ASDU 9 measurands II

6
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

3. PUBLIC PART SIGNALS AND FUNCTIONS

3.1. Physical connection


The RE.316*4 has an RS232C electrical interface at the rear for
the IEC60870-5-103. This is converted to an optical glass fibre
link with the electrical/optical converter 316BM61b. The charac-
teristics of this interface are shown in the table below.

Characteristics 316BM61b

connector F-SMA
cable type graded index 62.5/125 µm
optical wavelength 850 nm
temperature range -5...+55°C
transmission power in fibre -18.2...-11.2 dBm
minimal receiving power -24.0...-10.0 dBm
budget worst case 5.8 dB
budget typical 12.8 dB
typical distance 1000…3000 m (*)
Consumption +12 V < 21 mA
Consumption -12 V < 42 mA

(*) Based on optical fibres with 1.0...5.5 dB/km attenuation.

7
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

3.2. Supported application functions


The functions supported in this version are described in the table
below.

Application function Supported Remark

Station initialisation Yes


General interrogation Yes
Clock synchronisation Yes
Command transmission Yes
Test mode Yes
Blocking of monitoring direction Yes
Transmission of disturbance Yes
data
Generic services Partly Events, GI and measure-
ments only

3.3. Supported public signals

3.3.1. General
In the tables below the signals of the RE.316*4 distance protec-
tion are listed. The tables have the following columns:
INF The information number according to [1].
GI A x means: the signal is a part of the general inter-
rogation.
Description Textual description of the signal according to [1].
Function The RE.316*4 function where the signal originates
from according to the table in Section 5.1.
Signal The signal of the RE.316*4 function from which the
information number origins.
The combination ‘Function’ and ‘Signal’ uniquely defines the ori-
gin of each information number in the RE.316*4. Some signals
are generated by the communication interface or the diagnostic
software and have no direct coupling to a function or signal in
the RE.316*4. These signals are marked ‘Internal’ in the ‘Func-
tion’ column.
The function type of all public signals is 128 (distance protection).

8
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

3.3.2. System functions


Below are tables defining which of the IEC60870-5-103 informa-
tion numbers that are supported. For each information number is
defined from what RE.316*4 protection/system function and sig-
nal the information number is derived.

INF GI Description Function Signal

<0> - End of general interrogation Internal Generated by the communication


software
<0> - Time synchronisation Internal Generated by the communication
software
<2> - Reset FCB Internal Generated by the communication
software
<3> - Reset CU Internal Generated by the communication
software
<4> - Start/Restart Internal Warmstart

<5> - Power on Internal Coldstart

Internally generated signals from the communication software


are for communication co-ordination purposes and do not have
any equivalent protection/system functions or signals.
No configuration is necessary for any of the signals above.

9
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

3.3.3. Status indications

INF GI Description Function Signal Remark

<16> x Auto-recloser active IEC 103 ARCOM

<17> x Teleprotection active IEC 103 HFCOM

<18> x Protection active IEC 103 PROT_COM

<19> - LED reset IEC 103 RESLEDCOM

<20> x Monitor direction IEC 103 MELDE_MW_SP


blocked
<21> x Test mode SysIO Test active

<22> x Local parameter setting SysIO MMI is on

<23> x Characteristic 1 SysIO ParSet1 from SW V5.1b

<24> x Characteristic 2 SysIO ParSet2 from SW V5.1b

<25> x Characteristic 3 SysIO ParSet3 from SW V5.1b

<26> x Characteristic 4 SysIO ParSet4 from SW V5.1b

<27> x Auxiliary input 1 IEC 103 HILFSEING_1

<28> x Auxiliary input 2 IEC 103 HILFSEING_2

<29> x Auxiliary input 3 IEC 103 HILFSEING_3

<30> x Auxiliary input 4 IEC 103 HILFSEING_4

The characteristics (information numbers 23 through 26) up to


and including version V5.1a are only present in the GI. This is
due to restarting the protection following a change of a parame-
ter set (characteristic) in the RE.316*4. From V5.1b events are
also created.

10
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

3.3.4. Supervision indications

INF GI Description Function Signal Remark

<32> x Measurand supervision I ChI3 Trip

<33> x Measurand supervision U ChU3 Trip

<35> x Phase sequence super- - - NOT SUPPORTED


vision
<36> x Trip circuit supervision - - NOT SUPPORTED

<37> I>> backup operation Dist DelDistBlk From SW V6.3

<37> x I>> backup operation Dist Dist Blocked Up to SW V6.2b

<38> x VT fuse failure IEC 103 AUTO_FALL

<39> x Teleprotection disturbed IEC 103 HF_GESTOERT

<46> x Group warning Internal - Sent when the diag-


nostic status is ‘non-
urgent error’
<47> x Group alarm Internal - Sent when the diag-
nostic status is ‘ur-
gent’ or ‘fatal error’

The signal "I>> backup operation" is only set when the distance
function is blocked. The backup function, however, can only be
blocked by the inverted signal "Dist Blocked" and is otherwise
always active (see Section 5.1.4.).
The group warning and group error signals are derived from the
diagnostic of the RE.316*4. They are not possible to force for
test purposes.

11
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

3.3.5. Earth fault indications

INF GI Description Function Signal Remark

<48> x Earth fault L1 - - NOT SUPPORTED

<49> x Earth fault L2 - - NOT SUPPORTED

<50> x Earth fault L3 - - NOT SUPPORTED

<51> x Earth fault forward, i.e. in EFForw Trip resp.


direction of line resp. EF *) Meas. Forw *) From SW V6.4
<52> x Earth fault reverse, i.e. in EFBack Trip resp
direction of busbar resp. EF *) Meas. Back *) From SW V6.4

No phase information is available from the earth fault functions.

12
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

3.3.6. Fault indications

INF GI Description Function Signal Remark

<64> x Start /pickup L1 Dist Start R 1)

<65> x Start /pickup L2 Dist Start S 1)

<66> x Start /pickup L3 Dist Start T 1)

<67> x Start /pickup N Dist Start E


<68> - General trip SysIO GenTrip
<69> - Trip L1 Dist Trip CB R 2)

<70> - Trip L2 Dist Trip CB S 2)

<71> - Trip L3 Dist TripCB T 2)

<72> - Trip I>> (backup opera- Dist Trip O/C


tion)
<73> - Fault location X in Ohm Dist Internal Always in primary
side Ohm
<74> - Fault forward/line Dist Meas Fward 1)
<75> - Fault reverse/busbar Dist Meas Bward 1)
<76> - Teleprot. signal transmit- Dist Com Send
ted
<77> - Teleprotection signal re- IEC 103 HF_EMPFANG
ceived
<78> - Zone 1 Dist Delay 1
<79> - Zone 2 Dist Delay 2
<80> - Zone 3 Dist Delay 3
<81> - Zone 4 Dist Delay 4
<82> - Zone 5 Dist Delay Def Final step (start)
<83> - Zone 6 - - NOT SUPPORTED
<84> x General start/pickup SysIO GenStart
<85> - Breaker failure protection BFP 23305 Trip t1 Supported from
23310 Trip t2 SW V6.4
1) In the event that a directional overcurrent function (‘CurrentDir.’ or ‘CurrentInvDir.’) is
configured as back-up protection, then their signals ‘Start R’, ‘Start S’, ‘Start T’,
‘MeasVorward’ and ‘MeasBackward’ are also transmitted, provided that their event
recording is switched on.

2) In the event that a breaker failure protection is configured, then their signals ‘TRIP t1
L1’, ‘TRIP t1 L2’ and ‘TRIP t1 L3’ are also transmitted, provided that their event re-
cording is switched on.

13
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

3.3.7. Auto-reclosure indications


INF GI Description Function Signal Remark

<128> - CB "on" by AR AutoRec First AR If it is the first AR only


completed

<129> - CB "on" by long-time AR AutoRec 2nd…4th At the second, third and


AR com- fourth AR.
pleted

<130> x AR blocked AutoRec AR Blocked

3.3.8. Measurements
All measurements have a deadband supervision based on a delta
and a time-out. If the measurand changes more than 5% of nominal
value the measurand is updated. If no changes are detected the
measurand is updated every x seconds. The x seconds are con-
figurable and can range between 10...1000 seconds (see parame-
ter ‘EventTxDelay’ in Section 5.1.3).

INF GI Description Function Signal Remark

<144> - Measurand I NOT SUPPORTED

<145> - Measurands I, V NOT SUPPORTED

<146> - Measurands I, V, P, Q Measurand 1 I, U, P, Q ASDU 3.3

<147> - Measurands IN, VEN Measurand 2 I, U ASDU 3.4

<148> - Measurands IL1,2,3, Measurand 3 *) I, U, P, Q, f For L1 in ASDU 9


VL1,2,3, P, Q, f

Measurand 4 *) I, U, P, Q For L2 in ASDU 9

Measurand 5 *) I, U, P, Q For L3 in ASDU 9

*) From version V6.2 the three-phase function MeasureModule


can be used instead of these three functions which generates all
the measureands needed by ASDU 9.
All measurands are represented by a 13 bit floating comma
number in a range of ±2.4 times the primary system ratings.

14
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

3.3.9. Commands
The following table describes which general commands are sup-
ported.

INF Description Function Signal Remark

<16> Auto-recloser active IEC 103 ARCOM

<17> Teleprotection active IEC 103 HFCOM

<18> Protection active IEC 103 PROT_COM

<19> LED reset IEC 103 RESLEDCOM

<20> Monitor direction IEC 103 MELDE_MW_SP No command, local op-


blocked eration only
<23> Characteristic 1 SysIO ParSet1 from SW V5.1b

<24> Characteristic 2 SysIO ParSet2 from SW V5.1b

<25> Characteristic 3 SysIO ParSet3 from SW V5.1b

<26> Characteristic 4 SysIO ParSet4 from SW V5.1b

Caution:
• To switch the characteristic by command the parameter
“Rem. Setting” of the system function must be T (ON)
(from SW V5.1c).
• Switching the characteristic restarts the unit.

15
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

3.4. Transfer of disturbance data

3.4.1. CT/VT inputs supported


The disturbance recorder supports all the publicly defined ana-
logue values, as described in the table below. Please note that
the ninth channel must not be configured.
Explanation to the table:
Signal The channel in the RE.316*4 disturbance re-
corder.
Value The process signal according to [1].
Channel No The DDT channel number according to [1].
Remark All publicly defined channels are supported.

Signal Value Channel No Remark

AnalogInp 1 IL1 1 Publicly defined

AnalogInp 2 IL2 2 Publicly defined

AnalogInp 3 IL3 3 Publicly defined

AnalogInp 4 IN 4 Publicly defined

AnalogInp 5 UL1 5 Publicly defined

AnalogInp 6 UL2 6 Publicly defined

AnalogInp 7 UL3 7 Publicly defined

AnalogInp 8 UN 8 Publicly defined

AnalogInp 9 - 64 Private channel

16
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

3.4.2. Supported tags


Any binary signal can be selected for the disturbance recorder.
The signals listed with information numbers above will be trans-
ferred with these information numbers and the function type dis-
tance protection (128). The binary signals outside the publicly
defined range will be transferred with the private function type
130 and a private information number. The private information
number is the ordinal value of the private signal in the configura-
tion of the disturbance recorder.
Explanation to the table:
Signal The channel in the RE.316*4 Disturbance
recorder.
Value The binary signal in RE.316*4.
Function Type No The function type with which this signal is
addressed during the disturbance data
transfer.
Information Number The information number with which this
signal is addressed during the disturbance
data transfer.
Publicly defined signals have function type 128 (bold). Not all
possible signals are configured in this example.

Signal Value Function Information


Type No Number

BinInp 1 Start R from Dist 128 64

BinInp 2 Start S from Dist 128 65

BinInp 3 Start T from Dist 128 66

BinInp 4 General Trip from SysIO 128 68

BinInp 5 Start R Aux from Dist 130 1

BinInp 6 Start S Aux from Dist 130 2

BinInp 7 Start T Aux from Dist 130 3

BinInp 8 Trip from EFForw 128 51

BinInp 9 Start from EFForw 130 4

BinInp 10 Trip from EFBward 128 52

17
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Signal Value Function Information


Type No Number

BinInp 11 Start from EFBward 130 5

BinInp 12 -

BinInp 13 -

BinInp 14 -

BinInp 15 -

BinInp 16 -

18
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

4. GENERIC PART SIGNALS AND FUNCTIONS

4.1. General
The RE.316*4 supports the transmission of generic events (bi-
nary signals) and generic measurands. For this “VDEW6EKZ”
must be selected as project directory (see Section 5.2). General
interrogation is also supported, but not general write and read
commands, however (see Section 4.4). Generic data are always
transmitted in the format of an ASDU 10 (ASDU = Application
Service Data Unit) (see Section 7.3.1.9 in [1]. Thereby the in-
formation number 244 is always used, i. e. only single values are
transmitted. The termination of the general interrogation is sig-
nalled by an ASDU with the information number 245. In the other
fields of the ASDU there are defined the data for the group num-
bers and the entry, as specified in the following Chapters.

4.2. Generic events and general interrogation


There are altogether 64 generic events that can be configured to
an arbitrary binary signal in the RE.316*4. Of the 64 events, 32
are status indications with status and time stamp (DATATYPE
18 in [1], 7.3.6.32), and 32 are fault indication with status, time
stamp, relative time and fault number (DATATYPE 19 in [1],
7.2.6.32). All events that are configured are also sent during a
generic general interrogation.

For group and entry addresses see table below:

Group Entry GI DATATYPE Remark

101 1…32 Yes 18 Time tagged message for status


indications
102 1…32 Yes 19 Time tagged message with rela-
tive time for fault indications

4.3. Generic measurements


There are 16 freely configurable measurands in the generic part.
They all have the range ±2.4 times nominal value. All measure-
ments have a tolerance, which is determined by a delta and a
timeout . Measurements are updated at changes exceeding 5%.
If there are no changes, updating follows at intervals of x sec-

19
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

onds. For x a setting of 10…1000 seconds is foreseen (Parame-


ter “EventTXDelay” ; see Chapter 5.1.3).

Group Entry GI DATATYPE Remark

141 1…16 No 12 Measurand with quality descriptor

4.4. Generic read and write


All generic read and write commands are accepted by the link
but rejected by the application. The present version does not
contain any directory or other generic data.

20
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

5. CONFIGURATION GUIDE

5.1. System and Protection functions


In the RE.316*4 there are 13 system functions (inserted by the
system automatically) followed by a number of protection func-
tions as selected by the user. In the tables below a configuration
is shown that will generate all available signals listed in 3.3. If
one or several functions are not needed, they may be excluded.
The signals generated by the excluded functions will then also
be missing. If more functions are needed in a configuration they
may be added to the configuration. Please see below for con-
straints on the sequence of the configured functions.
Func No. The number the functions have in the set file. Sub-
tract 13 to obtain the numbers configured by the
user using the HMI.
Name The name the functions have in the set file.
Abbr. Function designation in the tables in Section 3.3.
HMI The path in the HMI to access the functions pa-
rameters.
System functions

Func No Name Abbr. HMI

1 System_Vers -

2 SigToSCS -

3 System -

4 AD Channels ADCh Editor /


Relay configuration /
A/D config. K
5 Signal Hold -

6 BinInp Card -

7 TripOut Hold -

8 System IO SysIO Editor /


System parameters
9 IBB Config. IBBConf Editor /
Edit IBB/PB configuration
10 Analog Output -

11 LBIO’s -

21
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Func No Name Abbr. HMI

12 RBIO’s -

13 Analog Input -

User configured functions

Func No Name Abbr. HMI

14 (HV-) Distance Dist Editor / connfigure protection


functions
15 Autoreclosure Autorec

16 IEC60870-5-103 IEC 103 Select with or without generic


signals
17 Check-I3ph ChI3

18 Check-U3ph ChU3

19 EarthFaultsIsolated EFForw
(Fward), resp. Earth- resp.
FaultGrounded2 *) EF
20 EarthFaultsIsolated EFBack
(Bward) *)
21 Measurement Meas 1

22 Measurement Meas 2

23 Measurement **) Meas 3 See Section 5.1.12


(or MeasureModule) (or Section 5.1.13)
24 Measurement **) Meas 4 See Section 5.1.12

25 Measurement **) Meas 5 See Section 5.1.12

26 Breaker faillure BFP Supported from SW6.4 onw.

27 DisturbanceRec DistRec

*) From Version V6.4 onwards, an earth fault function for grounded systems
may also be chosen instead of the two earth fault functions for un-
grounded systems

**) From Version V6.2 onwards, the three-phase function MeasureModule


can be configured instead of the 3rd., 4th. and 5th. function “Measrue-
ment”.

The two earth fault functions for ungrounded systems must al-
ways be configured so that the first function is for the forwards

22
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

direction and the second is for the backward direction. Any num-
ber of extra earth fault functions may follow but not precede
these two functions.
The measurement functions must not follow in a strict sequence
but other functions may be configured in between.
If one or several functions are not configured, then the corre-
sponding information numbers (see Section 3.3) will also be
missing.

5.1.1. CT/VT channels


These ratios are used by the diturbance recorder to calculate the
primary values.
Editor / Relay Configuration / Edit A/D Configuration

Parameter Setting

1. Prim/sec Ratio… All Prim Ratios must be set to the ratios of the
9. Prim/sec Ratio CTs and VTs actually installed.

5.1.2. System IO
These signals generate fault and status indications.
Editor / System Parameters

Parameter Setting

GenTrip Event recording on (ER) always.

GenStart

Test active

HMI is on

Rem. Setting Set to ON should a command be used to switch


characteristics.

5.1.3. IBB configuration


Communication parameters for the link and measurement filter.
Editor / IBB/BP Configuration / General Parameters

Parameter Setting

SlaveNodeAddr Slave address of this RE.316*4. Permissible


range 2...254
TimeSynchr Whether during summer time the time is syn-
chronised to standard or summer time

23
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Editor / IBB/BP Configuration / SPA Parameters

Parameter Setting

Baudrate Effective baudrate used. Permissible settings


are 9600 or 19200 Baud.
Initializing Event recording ‘on’. This enables the HMI to
determine when the communication interface is
ready after initialisation.

Editor / IBB/BP Configuration / LON Parameters

Parameter Setting

EventTxDelay Time required to refresh the measurands, i.e.


interval in seconds between refresh operations
when measurands have not changed. Range:
10…1000 seconds. This parameter is needed
by the tolerance supervision function.

24
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

5.1.4. (High-voltage) Distance Protection


All settings in menu: Editor / Configure Prot Func / (HV) Dis-
tance.
Only the sub-menu within the distance function is referred to be-
low.
General Parameters

Parameter Setting

Ref Length Ref Length must be set to a value that transforms


the fault location from secondary side to primary
side. The formula for this is:
Ref Length = Prim Sec Ratio I / Prim Sec Ratio U
Example: Prim Sec Ratio I = 1200, Prim Sec
Ratio U = 100 => Ref Length = 1200 / 100 = 12
ResetEvents Must be set to ‘All’, otherwise some events re-
ceived will not be signalled.

The fault location must be represented in primary side Ohms ac-


cording to [1]. For more information on Ref. Length see [2].

Overcurrent Protection

Parameter Setting

I O/C I O/C = 0 means backup protection is inactive


I O/C > 0 means backup protection is active.

25
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Binary Inputs

Parameter Setting

Ext Blk Dist To be configured as follows if used:


Output of a prot. function – IEC60870-5-103 –
OUT_PROT COM (12) inverted
Ext Blk O/C If the I>> backup function is only required to be
active when the distance function is blocked, the
following has to be configured:
Output of a prot. function – (HV) Distance -
Dist Blocked (40)
inverted
Com Rec Source of PLC signal. Usually allocated to a bi-
nary input if used.
Com Fail Source of the signal ‘PLC failure’. Usually allo-
cated to a binary input if used.
Ext Block HF To be configured as follows if used:
Output of a prot. function - IEC60870-5-103 -
OUT_HFCOM (10) inverted

26
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

Signalling Outputs

Parameter Setting

Start R Event recording on (ER) always.

Start S

Start T

Start E

Trip CB R

Trip CB S

Trip CB T

Trip O/C Event recording on (ER) if I O/C is > 0 i.e. backup


overcurrent protection is active.
Delay 1 Event recording on (ER) always.

Delay 2 Event recording on (ER) if the corresponding


zones are used.
Delay 3

Delay 4

Delay Def

Meas Fward Event recording on (ER) always.

Meas Bward

DelDistBlk Event recording on (ER) if it is used.

Com Send Event recording on (ER) if the HF trip schemes are


used.

27
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

5.1.5. Autoreclosure
Editor / Configure Prot Func / Autoreclosure / Binary inputs

Parameter Setting

Ext. Blk. AR To be configured as follows if used:


Output of a prot. function - IEC60870-5-103 -
OUT_ARCOM (9) inverted

Editor / Configure Prot Func / Autoreclosure / Signal Out-


puts

Parameter Setting

AR blocked Event recording on if used


First AR terminated Event recording always on
2nd…4 nd AR terminated Event recording always on

28
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

5.1.6. IEC60870-5-103
Parameters in the sub-menus ‘General’, ‘Binary Inp’ and ‘Binary
Out’ have to be configured for the IEC60870-5-103 function,
which has more parameters than are described here. The addi-
tional parameters are intended for the future generic services
(see Section 5.2).
Path:
Editor / Configure Prot Func / IEC60870-5-103 / General
If the generic services are being used, select the file ‘PROJECT1
BIN’ in the subdirectory ‘VDEW6EKZ’ of the HMI directory, oth-
erwise ‘PROJECT1.BIN’ in the subdirectory ‘VDEW6’. The pro-
ject directory then appears as ‘VDEW6EKZ’ resp. ‘VDEW6’.
Editor / Configure Prot Func / IEC60870-5-103 / Binary Inp
There are four alternative procedures for configuring the VDEW6
binary inputs:
1. Direct setting via the HMI to ‘always off’ resp. ‘always on’
2. Configure binary input
3. Configure the output of a protection function
4. Configure an SCS signal (mandatory for the command in-
puts).
The chosen possibility depends on the settings of the protection
unit.

Parameter Setting

IN_MELDE_MW_SP Source of the blocking signal for signals and


measurands. An ‘always on’ disables them and
an ‘always off’ enables them.
Normally assigned to a binary channel, but can
also be set to ‘always on’ or ‘always off’ using the
HMI.
IN_AUTO_FALL VT fuse failure input. assigned to a binary input
when used.
IN_HILFSEING_1 Always assigned to a binary channel or to an
output of a protectin function when used.
IN_HILFSEING_2

IN_HILFSEING_3

IN_HILFSEING_4

29
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Parameter Setting

IN_HF_GESTOERT Source of the PLC failure signal. If used, this


must be assigned to the same binary input as the
distance function signal ‘Com Fail’ of the distance
protection function, if used. See distance protec-
tion / binay inputs.
IN_HF_EMPFANG Source of the PLC signal. If used, this must be
assigned to the same binary input as the distance
function signal ‘Com Rec ’ of the distance protec-
tion function. If used. See distance protection /
binay inputs
IN_ARCOM SCS input, Group 1, Signal 1 Æ SCS 1/1

IN_HFCOM SCS input, Group 1, Signal 2 Æ SCS 1/2

IN_RESLEDCOM Leave at default setting ‘always off’

IN_PROTCOM SCS input, Group 1, Signal 4 Æ SCS 1/4

Remaining inputs Leave at default setting ‘always off’

Editor / Configure Prot Func / IEC60870-5-103 / Binary Out-


puts

Parameter Setting

OUT_MELDE_MW_SP Cannot be configured for event recording, but


may be configured as an indication via a LED
and/or signal relay.
OUT_AUTO_FALL When used,

OUT_HILFSEING_1 • set to ‘on’ for event recording


• can be assigned as an indication to a LED
OUT_HILFSEING_2
and/or signal relay.
OUT_HILFSEING_3

OUT_HILFSEING_4

OUT_HF_GESTOERT

OUT_HF_EMPFANG

30
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

Parameter Setting

OUT_ARCOM When it is used, it:


• may be configured as an indication to LED
and/or signal relay.
• may not be configured as an event.
• must be assigned to the inverted input
Ext.Blk. AR of the autoreclosure function (see
Autoreclosure / Binary inputs).
OUT_HFCOM When it is used, it:
• may be configured as an indication to LED
and/or signal relay.
• may not be configured as an event.
• must be assigned to the inverted input Ext Blk
HF of the distance function (see Distance /
Binary Inputs).
OUT_RESLEDCOM Not assigned to a function.

OUT_PROT_COM When it is used, it:


• may be configured as an indication to LED
and/or signal relay.
• may not be configured as an event.
• must be assigned to the inverted blocking
input of all functions. This has to be done for
each individual function.
Remaining signals Must all be left with the default setting <blank>
i.e. not configured to anything.

31
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

5.1.7. Check-I3ph
Editor / Configure Prot Func / Check-I3ph

Parameter Setting

Trip Must be to event recording ‘on’.

5.1.8. Check-U3ph
Editor / Configure Prot Func / Check-U3ph

Parameter Setting

Trip Must be to event recording ‘on’.

5.1.9. Earth fault ungrounded system forward


This must be the first Earthfault Isolated function in the set file.
Editor / Configure Prot Func / EarthfaultIsol

Parameter Setting

BlockInp To be configured as follows if used:


Output of a prot. function – IEC60870-5-103 –
OUT_PROT COM (12) inverted.
Trip Must be to event recording ‘on’.

5.1.10. Earth fault ungrounded system backward


This must be the second “EarthFaultIsol” function in the set file.
After this any number of earth fault functions for ungrounded
power systems may be configured.
Editor / Configure Prot Func / EarthfaultIsol

Parameter Setting

BlockInp To be configured as follows if used:


Output of a prot. function – IEC60870-5-103 –
OUT_PROT COM (12) inverted.
Trip Must be to event recording ‘on’.

32
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

5.1.11. Earth fault grounded


From Version V6.4 onwards, an earth fault function for grounded
systems ‘EarthFaultGround2’ may also be used instead of the
two earth fault functions specified above.
Editor / Configure Prot Func / EarthFaultGround2

Parameter Settings

BlockInp Configure the following, if used:


Output of a protection function - IEC60870-5-103-
OUT_PROT_COM (12) inverted
Meas Fward Event recorder always on.

Meas Bward Event recorder always on.

5.1.12. Measurement
The communication interface uses the first five measuring func-
tions it finds in the set file for the publicly defined measurands. It
is important that these first five measuring functions are config-
ured as described below. If you need further measuring functions
they must be configured after these five measuring functions.
The five functions need not be configured strictly after each
other, but other functions may be configured inbetween.
From Version V6.2 onwards, a three-phase measuring function
is included with the designation “MeasureModule”, which can be
used instead of the third, fourth and fifth ‘Measurement’ function.
The communication interface uses the first function it finds in the
list of configured functions. It is not permissible to configure the
“MeasureModule” function between the third and fourth or fourth
and fifth ‘Measurement’ functions as this would produce invalid
results.
The first ‘Measurement’ function supplies the values I, U, P and
Q for the data unit 3.3 according to [1]. It is important that the
angle is set to compensate for the difference between the RS
delta voltage and the phase S current.

33
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Editor / Configure Prot Func / Measurement (1)

Parameter Setting

Current Inp Configured for phase S

Angle Compensate for the current inphase S and the volt-


age from phase to phase RS so that the power val-
ues are correct. Typical setting: +150°.
Voltage Inp Configured for phase R

PN 1.00

Voltage mode Phase-to-phase (RS)

The second ‘Measurement’ function supplies the values I0 and


U0 for the data unit 3.4 according to [1]. Only make sure that the
correct transformers are configured here. If one of the I0 or U0 is
missing, connect the input to transformer in any case.
Editor / Configure Prot Func / Measurement (2)

Parameter Setting

Current Inp Configured for I0

Angle Irrelevant

Voltage Inp Configured for U0

PN Irrelevant

Voltage mode Direct

The third to fifth ‘Measuring’ functions supplies the communica-


tion with the values I, U, P, Q and f for the data unit 9 according
to [1]. The frequency is taken from the third function and the P
and Q are added together from all the three functions.

34
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

Editor / Configure Prot Func / Measurement (3)

Parameter Setting

Current Inp Configured for phase R

Angle 0 degree

Voltage Inp Configured for phase R

PN 1.00

Voltage mode Direct

Editor / Configure Prot Func / Measurement (4)

Parameter Setting

Current Inp Configured for phase S

Angle 0 degree

Voltage Inp Configured for phase S

PN 1.00

Voltage mode Direct

Editor / Configure Prot Func / Measurement (5)

Parameter Setting

Current Inp Configured for phase T

Angle 0 degree

Voltage Inp Configured for phase T

PN 1.00

Voltage mode Direct

35
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

5.1.13. MeasureModule
From Version V6.2 onwards, a three-phase measuring function
is included with the designation “MeasureModule”, which can be
used instead of the third, fourth and fifth ‘Measuring’ functions.
The communication interface uses the first function in the list of
configured functions, i.e. the “MeasureModule” function is used if
it is configured first, but if five ‘Measuring’ functions are config-
ured first, the results generated by the third, fourth and fifth
‘Measuring’ functions are used for transferring the three-phase
measurements. The “MeasureModule” function can be config-
ured at any position excepting between the third and fourth or
fourth and fifth ‘Measuring’ functions as this would produce inva-
lid results.
Editor / Configure Prot Func / MeasureModule

Parameter Setting

CurrentInp Configured for phase R

AngleComp 000.0 deg

VoltageInp Configured for phase R

PN 1.000

PulseInp1 Do not assign if not needed.

5.1.14. Breaker failure protection


Editor / Configure Prot Func / BreakerFail

Parameter Setting

13205 BlockInp Configure the following, if used:


Output of a protection function - IEC60870-5-103-
OUT_PROT_COM (12) inverted
23305 Trip t1 Event recorder always on.

23310 Trip t2

23315 Trip t1 L1 When the event recorder is switched on, a trip of


the breaker failure protection also generates the
23320 Trip t1 L2 signals ‘Trip L1’, ‘Trip L2’ and ‘Trip L3’ (69…71).

23325 Trip t1 L3

36
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

5.1.15. Disturbance recorder


The disturbance recorder must be configured as described be-
low to assure an interoperable mode of operation. It is important
that “GenStart” is used as the trigger and that “GenTrip” is re-
corded as a tag. “GenStart” as trigger guarantees that the fault-
number of events and disturbances remains the same. “GenTrip”
is used to evaluate if a recorded disturbance has also led to a
trip.

Editor / Configure Prot Func / DisturbanceRec

Parameter Setting

preEvent Choose values that are multiples of 30. To get


a disturbance record status “with trip”, the re-
Event cording period must be set longer than the
maximum tripping time.
postEvent

recMode Must be “A”.

TrigMode Must be “TrOnStrt&Bin”.

StorageMode Must be “Overwrite”.

AnalogInp 1 Phase R CT input, otherwise empty.

AnalogInp 2 Phase S CT input, otherwise empty.

AnalogInp 3 Phase T CT input, otherwise empty.

AnalogInp 4 Neutral current CT input, otherwise empty.

AnalogInp 5 Phase R VT input, otherwise empty.

AnalogInp 6 Phase S VT input, otherwise empty.

AnalogInp 7 Phase T VT input, otherwise empty.

AnalogInp 8 Neutral voltage VT input, otherwise empty.

AnalogInp 9 Any CT/VT input.

AnalogInp 10…12 May not be configured, always 0.

37
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Parameter Setting

BinInp 1…16 (BinaryAddr) For interoperability use the following must ap-
ply:
• Assign GenStart to one BinInp (any).
• Assign GenTrip to one BinInp (any).
• Any signal may be assigned to any of the
remainder (see Section 3.4.2 for addressing
of the tags).
• Unused BinInp’s must be set to ‘always
OFF’ (default).
BinInp 1…16 (Select) Must all be set to “no trig”.

MWAInp 1…12 May not be connected (default).

MWAScale 1…12 Must all be set to ‘1’ (default).

38
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

5.2. Generic signals


Signals not defined as public are transferred as generic signals.
All generic signals that are configured are automatically included
when general polling of generic signals takes place.
Generic signals are defined as IEC60870-5-103 function signals
via
Editor / Configure Prot Func / IEC60870-5-103 / General
Where generic services are required, enter the file ‘PRO-
JECT1.BIN’ in the subdirectory ‘VDEW6EKZ’ of the HMI direc-
tory. The ‘Project Sub Dir’ then appears as ‘VDEW6EKZ’.

5.2.1. Binary Inp


Editor / Configure Prot Func / IEC60870-5-103 / Binary Inp

Parameter Setting

IN_BI1…IN_BI32 These are status signals. On change they generate


events with new status and a time stamp
(DATATYPE = 18 in [1]).
They may be configured as:
• Binary channel
• Output from function
• Always off

IN_BI33…IN_BI64 These are fault signals. On change they generate


events with new status, fault number, relative time
and a time stamp (DATATYPE = 19 in [1]).
They may be configured as:
• Binary channel
• Output from function
• Always off

All signals defined as generic signals in “Binary Inp” as de-


scribed above, must also be configured for event recording in
“Binary Out”. If not they will not generate events and will not par-
take in the generic general interrogation.

39
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

Editor / Configure Prot Func / IEC60870-5-103 / Binary Out

Parameter Setting

OUT_BI1…OUT_BI32 If defined as generic signals in the Binary Inp they:


and • must be configured with event recording on
(ER)
OUT_BI33…OUT_BI64
• may be configured as indication to LED and/or
signal relay.

5.2.2. Measurands
There are 16 freely configurable generic measurands available.
They can be assigned to any measurement output of any
RE.316*4 function. In the MW Inputs menu the source of the
measurand in RE.316*4 is selected and in the MW Outputs
menu a value is set in order to activate the measurand for the
communication interface.

Editor / Configure Prot Func / IEC60870-5-103 / MW Inputs

Parameter Setting

IN_ME1…IN_ME16 Sixteen freely configurable measurands with


quality descriptor (DATATYPE = 12 in [1]
7.2.6.32).
They may be configured with outputs from func-
tions only.

Editor / Configure Prot Func / IEC60870-5-103 / MW Outputs

Parameter Setting

OUT_ME1…OUT_ME16 All measurands used (i.e. where there is an input


in the MW input menu) must have a value other
than 0 in “MW Outputs”. Setting the value the
same as the measurand’s number is recom-
mended, e.g.
OUT_ME1 set to 1, OUT_ME10 set to 10 etc.

40
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

6. TEST GUIDE

6.1. Test of the physical connection


a) Connect the converter 316BM61b to the rear of the RE.316*4
and turn on the power. Do not connect any optical fibres to the
316BM61b.
b) Look into the transmitter (Tx) and receiver (Rx) diodes alter-
natingly. There must be a small spot of red light out from the
transmitter diode.
Possible problems and solutions:
• The RE.316*4 has no power. Check that the power is on to
the RE.316*4 and that the green Led on the front of the
RE.316*4 is either lit or blinking.
• The 316BM61b has no power. Measure with a voltmeter on
the following pins of the 9 pin sub-D connector at the rear.
View from rear.
Pin 4 +12V
Pin No1
6
2
Pin 5 Ground 3 7
8
4 9
5
Pin 9 -12 V

If the above voltages are not present the 316VC61a/b must be


changed.
• The 316BM61b is not OK. Try with another 316BM61b.

41
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

6.2. Test of the link connection


The following steps will test the start up procedures and the time
synchronisation. Both cold and warm starts are tested.
a) Before starting the HMI from the PC set the time and/or date
to an incorrect value e.g. change the year to 1960. This is for
the test of the time synchronisation later. Then start the HMI.
b) Start the RE.316*4 and load a set file from the HMI. The set
file must at least include the Distance function and the
IEC60870-5-103 function. Make sure the baudrate and the
slave address are correct and that the initiating event is set
for event recording (ER).
c) Connect the optical fibres from the 316BM61b to the control
system.
d) Wait until the RE.316*4 has started and the link is initialised,
this takes approximately 1 minute and is signalled on the
HMI with the event „initiating“.
e) The control system is now able to establish the link connec-
tion. Check in the control system that the RE.316*4 is com-
municating and that the identification string is correct.
f) The control system will normally as a first action try to syn-
chronise the RE.316*4. Select the display of the CT and VT
inputs in “Measurement Values” on the HMI. Check that the
time is changed from the incorrect time set under point a) to
the time used in the control system.
g) Turn off the power to the RE.316*4 for at least 10 seconds
and then turn it on again. Wait until the communication is es-
tablished again, see under d).
h) When the communication is established the control system
must have registered a cold start from the RE.316*4.
i) Press the button on the front until the green led blinks i.e. the
RE.316*4 performs a restart. Wait until the communication is
established again, see under d).

42
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

Possible problems and solutions.


• The initialisation is not yet finished. Wait until you see the ini-
tiating event on the HMI.
• The optical fibres are not connected properly. Check the con-
nections at either end.
• The optical fibres or connectors are damaged. Try with other
optical fibres.
• There are no functions loaded in the RE.316*4 or the
IEC60870-5-103 function is missing. Check that at least the
Distance and IEC60870-5-103 functions are loaded.
• There are other problems in the software or hardware. Check
the diagnostics of the RE.316*4, see [2].

6.3. Signals test


All signals described above (public as well as generic but except
the group warning and the group error) can be tested with injec-
tion tests.
a) Connect an injection test system e.g. XS92b to the RE.316*4.
b) Connect the HMI to the RE.316*4 and make sure the correct
set file is loaded.
c) Make sure that the optical fibrers are connected and that the
connection with the control system is working.
Test all signals and measurands configured. Below is a list of
the signals with a comment on how to test them. Compare all
events displayed on the HMI with the events received by the
control system. Compare the measurands displayed on the
HMI with the measurands received by the control system.

43
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

6.3.1. Status indications

INF GI Description Test

<16> x Auto-recloser active Send commands (on/off) from


control station and check that:
• the status of GI is correct.
• the AR is blocked resp. un-
blocked.
• the command procedure is
OK in the control station.
<17> x Teleprotection active Send commands (on/off) from
control station and check that:
• the status of GI is correct.
• the teleprotection (distance
function HF) is blocked resp.
unblocked
• the command procedure is
OK in the control station
<18> x Protection active Send command (on) from con-
trol station and check that:
• the status of GI is correct.
• the protection is enabled or
disabled.
• the command procedure is
OK in the control station.
<19> - LED reset Send command (on) from con-
trol station and check that:
• the leds goes off (must be lit
previously).
• the command procedure is
OK in the control station
<20> x Monitor direction blocked Turn on and off and check that:
• the status of GI is correct.
• no events, GI or meas-
urands comes through and
no commands from control
station are accepted when
the information blocking is
on.

44
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

INF GI Description Test

<21> x Test mode Switch the RE.316*4 to the test


mode and check:
• the GI status and events

<22> x Local parameter setting Connect (on) and disconnect


(off) the HMI and check:
• the GI status and events
N.b. it takes some time for the
RE.316*4 to notice when the
HMI is disconnected.
<23> x Characteristic 1 Send a ‘close’ command via the
control system and check that:
• the GI status is correct
• Characteristic 1 is active
• the command sequence
issued by the control system
is correct
<24> x Characteristic 2 • as <23> but for Char. 2

<25> x Characteristic 3 • as <23> but for Char. 3

<26> x Characteristic 4 • as <23> but for Char. 4

<27> x Auxiliary input 1 Assert input and check:


• the GI status and events

<28> x Auxiliary input 2 As above <27>

<29> x Auxiliary input 3 As above <27>

<30> x Auxiliary input 4 As above <27>

45
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

6.3.2. Supervision indications

INF GI Description Test

<32> x Measurand supervision I Trip by the Check-I3ph function


and check:
• the GI status and events.

<33> x Measurand supervision V Trip by the Check-U3ph func-


tion and check:
• the GI status and events.

<38> x VT fuse failure Assert the configured input and


check:
• the GI status and events.
<39> x Teleprotection disturbed Assert the configured input and
check:
• the GI status and events.
<46> x Group warning Cannot be simulated.

<47> x Group alarm Cannot be simulated.

6.3.3. Earth fault indications

INF GI Description Test

<51> x Earth fault forward, i.e. line Cause the forward (first) earth
fault protection function to trip
and check:
• the GI status and events.

<52> x Earth fault reverse, i.e. Cause the backward (second)


busbar earth fault protection function
to trip and check:
• the GI status and events.

46
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

6.3.4. Fault indications

INF GI Description Test

<64> x Start /pickup L1 Make a fault for the distance pro-


tection function so that it picks up
in phase R and check:
• the GI status and events.

<65> x Start /pickup L2 Make a fault for the distance pro-


tection function so that it picks up
in phase S and check:
• the GI status and events.
<66> x Start /pickup L3 Make a fault for the distance pro-
tection function so that it picks up
in phase T and check:
• the GI status and events.
<67> x Start /pickup N Make a fault for the distance pro-
tection function so that it picks up
in phase N and check:
• the GI status and events.
<68> - General trip Cause a trip in any function and
check:
• the events.

<69> - Trip L1 Make a fault for the distance pro-


tection function so that it trips in
phase R and check:
• the events.
<70> - Trip L2 Make a fault for the distance pro-
tection function so that it trips in
phase S and check:
• the events.

<71> - Trip L3 Inject a fault so that the protection


trips in phase T and check:
• the events.
<72> - Trip I>> (backup opera- Block the distance protection func-
tion) tion. Inject a fault in the distance
protection function so that its O/C
stage trips and check:
• the events.

47
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

INF GI Description Test

<73> - Fault location X in Ohm Make a fault for the distance pro-
tection function so that it trips and
check:
• that the fault location (in pri-
mary ohms) is correct.
<74> - Fault forward/line Make a fault for the distance pro-
tection function so that it trips in
the forward direction and check:
• the events.

<75> - Fault reverse/busbar Make a fault for the distance pro-


tection function so that it trips in
the backward direction and check:
• the events.
<76> - Teleprot. signal transmit- Configure the HF logic. Make a
ted fault for the distance protection
function so that it send the HF
signal and check:
• the events.
<77> - Teleprotection signal re- Configure the HF logic. Assert the
ceived configured input and check:
• the events.

<78> - Zone 1 Inject a fault in the distance protec-


tion function so that it trips in the
first zone and check:
• the events.
<79> - Zone 2 Inject a fault in the distance protec-
tion function so that it trips in the
second zone and check:
• the events.

<80> - Zone 3 Inject a fault in the distance protec-


tion function so that it trips in the
third zone and check:
• the events.
<81> - Zone 4 Inject a fault in the distance protec-
tion function so that it trips in the
fourth zone and check:
• the events.

48
IEC60870-5-103 1MRB520226-Uen / Rev. B ABB Switzerland Ltd
DISTANCE PROTECTION IN RE.316*4

INF GI Description Test

<82> - Zone 5 Inject a fault in the distance protec-


tion function so that it trips in the
end zone and check:
• the events.

<84> x General start/pickup Inject a fault in the distance protec-


tion function so that it picks up and
check:
• the GI status and events.

<85> - Breaker failure protection Inject a fault that excites the


breaker failure protection function
and check:
• the GI status and events.

6.3.5. Auto-reclosure indications

INF GI Description Test

<128> - “Close CB” by AR Inject a fault that excites the auto-


reclosure function once and check:
• the events.

<129> - “Close CB” by slow AR Inject a fault that excites the auto-
reclosure function two or more
times if configured, and check:
• the events.

<130> x AR blocked Block the autoreclosure function


and check:
• the GI status and events.

49
ABB Switzerland Ltd IEC60870-5-103 1MRB520226-Uen / Rev. B
DISTANCE PROTECTION IN RE.316*4

6.3.6. Measurements
For all measurands configured:

Inject currents and voltages to the RE.316*4, let the values stay
stable and check:
• that the values are sent with the time interval defined for the
deadband supervision.
• that the values are correct in sign and magnitude.
Change the injected values a few times and check:
• that the values are sent immediately upon a change of at least
5% of an injected value.

6.4. Checking disturbance data


Test with injection test.
a) Inject a fault that triggers the disturbance recorder.
b) Wait until the control system has read the complete distur-
bance and acknowledged it positively.
c) Check that the disturbance is no longer presented to the con-
trol system.
d) Check that the disturbance data presented on the control sys-
tem is correct with respect to the injected fault and generated
events.

6.5. Testing generic signals


Test the generic events and their statuses by activating the con-
figured signals and check the GI status and events sent.
Test the generic measurands in the same way as described
above for public measurands.

50
Notification Form for Errors in this Document
Dear User,
We constantly endeavour to improve the quality of our technical publications and
would like to hear your suggestions and comments. Would you therefore please fill in
this questionnaire and return it to the address given below.

ABB Switzerland Ltd


Utility Automation Systems
Betreuung Dokumentation, PTU-BD1
Bruggerstrasse 72
CH-5401 Baden
Telefax +41 58 585 35 82
---------------------------------------------------------------------------------------------------------------
Concerns publication: 1MRB520226-Uen (IEC60870-5-103 DI RE. 316*4
V6.x to V7.x)
Have you discovered any mistakes in this publication? If so, please note here the
pages, sections etc.

Do you find the publication readily understandable and logically structured? Can you
make any suggestions to improve it?

Is the information sufficient for the purpose of the publication? If not, what is missing
and where should it be included?

Name: Date:

Company:

Postal code: Town: Country:


Notification Form for Equipment Faults and Problems
Dear User,
Should you be obliged to call on our repair service, please attach a note to the unit
describing the fault as precisely as possible. This will help us to carry out the repair
swiftly and reliably, which after all is to your own advantage.
Please attach a completed form to every unit and forward them to the address below.

Place of delivery Baden/Switzerland:

ABB Switzerland Ltd


Utility Automation Systems
Repair Center
Warenannahme PT-EG
Bruggerstrasse 72
CH-5401 Baden
---------------------------------------------------------------------------------------------------------------
Equipment data:
Unit type:
Serial No.: ……….....................................
In operation since:

Reason for return: (tick where applicable)


❑ Overfunction
❑ No function
❑ Outside tolerance
❑ Abnormal operating temperature
❑ Sporadic error
❑ Unit for checking

Remarks/Description of fault:

Customer: Date:

Address:

Please contact: Phone: Fax:


Notification Form for Software Errors and Problems
Dear User,
As we all know from practice, software does not always function as expected for all
applications. A precise description of the problem and your observations will help us
to improve and maintain the software. Please complete this form and send it together
with any supporting information or documents to the address below.

ABB Switzerland Ltd


Utility Automation Systems
Betreuung Software, Abt. PTUSX
Bruggerstrasse 72
CH-5401 Baden
Telefax +41 56 205 02 53
e-mail: SA-LEC-Support@ch.abb.com
---------------------------------------------------------------------------------------------------------------
Unit/ ❑ REC 316*4 SW Version: ❑ REC 216 SW Version:
System: ❑ REG 316*4 SW Version: ❑ REG 216 SW Version:
❑ REL 316*4 SW Version: ❑ HMI SW Version:
❑ RET 316*4 SW Version: ❑ other: SW Version:
❑ XS92a / XS92b SW Version:

Problem: ❑ Program error (unit/system) ❑ Program error (HMI /PC)


❑ Error in manual ❑ Suggestion for improvement
❑ other:

Can the error be reproduced at will? ❑ yes ❑ no

Particulars of hardware and software (unit/system configuration including jumper


positions, type of PC etc.):

Problem located? ❑ yes ❑ no


Suggested changes enclosed? ❑ yes ❑ no
The following are enclosed (floppy with settings etc.):
❑ Floppy ❑ Unit/system settings, file name:
❑ other:
Description of problem:

Customer: Date:

Address:

Please contact: Phone: Fax:


DESCRIPTION OF PROBLEM: (continuation)

___________________________________________________________________
ACTION (internal use of ABB Switzerland Ltd, Dept. PTUSX only)
Received by: Date:
Answered by: Date:

Problem solved? ❑ yes ❑ no

Week: Name: Position: Consequence:


---------------------------------------------------------------------------------------------------------------
IMPORTANT NOTICE!

Experience has shown that reliable operation of our products is


assured, providing the information and recommendations con-
tained in these Operating Instructions are adhered to.

It is scarcely possible for the instructions to cover every eventu-


ality that can occur when using technical devices and systems.
We would therefore request the user to notify us directly or our
agent of any unusual observations or instances, in which these
instructions provide no or insufficient information.

In addition to these instructions, any applicable local regulations


and safety procedures must always be strictly observed both
when connecting up and commissioning this equipment.

Any work such as insertion or removal of soldered jumpers or


setting resistors, which may be necessary, may only be per-
formed by appropriately qualified personnel.

We expressly accept no responsibility for any direct damage,


which may result from incorrect operation of this equipment,
even if no reference is made to the particular situation in the
Operating Instructions.
ABB Switzerland Ltd
Utility Automation Systems
Bruggerstrasse 72
CH-5400 Baden / Switzerland
Telefon +41 58 585 77 44
Telefax +41 58 585 55 77
e-mail substation.automation@ch.abb.com

www.abb.com/substationautomation

Printed in Switzerland (0308-0000-0)

You might also like