Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller

Adaptive Power Module 369583f 1 07.23.18

The Adaptive Power Module family is a group of modular


products for the control of permanently installed lighting 800 W Max 500 W Max 500 W Max 500 W Max

fixtures. This document describes the following product: CCI


Zone 1 Zone 2 Zone 3 Zone 4

Adaptive Power Module (model LQSE-4A-D)


Option

DIN Rail Power Module


Input Def H

LQSE-4A-D
Hi Temp Opt1 M

Prog Opt2 L

Features
Power Opt3

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

• Adaptive Power Modules can be used in a


HomeWorks QS system.
• An auto-detect mode is available to detect and LQSE-4A-D
configure leading edge or trailing edge dimming for
incandescent/halogen, electronic/magnetic low voltage • RTISS-TE operates on the trailing edge of the AC
and neon / cold cathode light sources. sine wave. This allows for true instantaneous voltage
• Controls dimmable CFL / LED loads. Refer to Lutron compensation.
P/N 048478 on www.lutron.com for compatibility with • Unit is 12 DIN modules (216 mm) wide.
dimmable CFL / LED light sources. • Provides air gap off (when all zones are off).
• RTISS Equipped technology compensates for incoming • LEDs on front of unit provide diagnostic information.
line-voltage variations (up to ± 2% change in frequency / • Includes QS link for seamless integration of lights
second) such as changes in Root Mean Square (RMS) and controls.
voltage, frequency shifts, harmonics and line noise.

System Example Emergency Contact Closure Input

HomeWorks QS HomeWorks
Power Module QS Panel QS Contact
seeTouch Closure
QS Wallstation Interface GRAFIK
CCI QS Zone 1 Zone 2 Zone 3 Zone 4

Eye QS
COM

COM
MUX
MUX

Zones
CCI

0,5 N•m 0-10 V-


All Others 50 mA

Input
Def H
Z096
Hi Temp 0-10 V Power Module Opt1
Option M
Program LQSE-4T10-D Opt2
230 V~ 50/60 Hz 50 mA µ Up
Power www.lutron.com +44.(0)20.7680.4481 Opt3 L
1,2 N•m
L N 8 mm Mains Only Outputs 230 V~ 10 AX each 1 2 3 4

Adaptive Power Up to 100


Module QS Link total QS
devices

800 W Max 500 W Max 500 W Max 500 W Max

CCI
Zone 1 Zone 2 Zone 3 Zone 4

Option
DIN Rail Power Module

Input Def H
LQSE-4A-D

Hi Temp Opt1 M

Prog Opt2 L

Power Opt3

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

220–240 V~ Control Power

800 W Adaptive load1

500 W Adaptive load1

500 W Adaptive load1

500 W Adaptive load1


Notes:
1
See "Output Zone Ratings" in “Specifications” section, for specific load types ratings.

® S P E C I F I C AT I O N S U B M I T TA L Page 1
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 2 07.23.18

Specifications
Adaptive Power Module Output Zone Ratings (continued)
• Each zone has no minimum load requirement.
Power
• When programmed to "auto" mode, the unit starts in
• 220–240 V~ 50/60 Hz
trailing edge and if an incompatible load is detected, it
• 10 A maximum total input current will convert to leading edge.
• Lightning strike protection meets ANSI/IEEE standard
• Internal relay provides an air gap off when all zones
62.31-1980. Can withstand voltage surges of up to
are off.
6 000 V and current surges of up to 3 000 A.
• One load type per zone.
Standards • Output must not be used to control receptacles,
• RoHS Compliant including plug-in lamps.
• IEC/EN 60669-2-1 • Output must be directly connected to the load.
• CE marked Output breakers or switches must not be used.
• Lutron Quality Systems registered to ISO 9001.2015 • Run a separate neutral for each load circuit. A
common neutral connection is not recommended.
Environment
• Maximum wire length between the Energi Savr Node
• See Mounting on page 4 for thermal specifications
unit and the load must be less than 30.5 m.
• Relative humidity: less than 90% non-condensing
• Unit may be powered by Ground Fault Interrupter (GFI)
• For indoor use only
or Residual Current Circuit Breaker with Overload
Output Zone Ratings (RCBO) protected circuit if required. Load circuit wiring
(from breaker to unit to load) must be run in its own
• No Derating is required if all the conditions below are met:
non-metallic conduit, or nuisance tripping may occur.
– Calibration point maximum is 70 ºC
– Room ambient temperature is between 0 ºC and 30 ºC • For applications requiring 0–10 V- control, use Ten
– Panel ambient temperature is between 0 ºC and 50 ºC Volt Interface (GRX-TVI) or the LQSE-4T10-D.
• 100 W Derating is required on all zones for a single • For applications requiring higher wattage ratings, use a
module in a single non-ventilated DIN enclosure if: power booster (NGRX-PB, NGRX-ELVI, NGRX-FDBI).
– The room ambient temperature is between
30 ºC and 40 ºC.
• 200 W Derating is required on all zones for multiple
row non-ventilated DIN enclosure if:
–T he room ambient temperature is between 30 ºC and
40 ºC.

Each zone is rated for the following wattage and load typesA, B:
Zone 1 Rating Zone 2, 3 and 4 Rating (per zone)
Load Type 100 W 200 W 100 W 200 W
No Derating Derating Derating No Derating Derating Derating
Incandescent / Halogen 800 W 700 W 600 W 500 W 400 W 300 W
Electronic Low Voltage 800 W 700 W 600 W 500 W 400 W 300 W
Magnetic Low VoltageD 800 VA (600 WC) 700 VA (525 WC) 600 VA (450 WC) 500 VA (375 WC) 400 VA (300 WC) 300 VA (225 WC)
Neon / Cold CathodeD 800 VA (600 WC) 700 VA (525 WC) 600 VA (450 WC) 500 VA (375 WC) 400 VA (300 WC) 300 VA (225 WC)
A
Additional load type options are available in the HomeWorks QS software suite, some may require an interface. Contact Lutron for details.
B
Refer to Lutron P / N 048478 on www.lutron.com for compatibility with dimmable CFL / LED light sources.
C
Actual lamp wattage.
D
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1

® S P E C I F I C AT I O N S U B M I T TA L Page 2
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 3 07.23.18

Specifications (continued) Out of Box Functionality


Terminals (Torque, wire gauge & type ratings) This section describes the default functionality when
• Mains wiring: 0.6 N•m the unit is first installed.
1.0 mm² to 4.0 mm²
(single wire, solid or stranded) Emergency Contact Closure Input (CCI)
1.0 mm² to 1.5 mm² • When the CCI is open, the Energi Savr Node QS
(two wires, solid or stranded) unit will enter Emergency Mode, which will turn on
• Zone wiring: 0.6 N•m all loads to their emergency level and disable control
1.0 mm² to 4.0 mm² of local zones and QS devices.
(single wire, solid or stranded) • When the CCI is closed or jumpered, Energi Savr
• CCI wiring: 0.6 N•m Node QS unit zones will return to the settings or lev-
0.5 mm² to 4.0 mm² els they were at prior to entering emergency mode.
(single wire, solid or stranded) Note: Unit will process any sensor events received
• QS Link: 0.6 N•m
while in emergency mode after it exits emergency
0.5 mm² to 4.0 mm²
mode.
(single wire, solid or stranded) Normal Mode Operation
0.5 mm² to 1.0 mm²
• By default each zone is set to an unassigned/Non-
(two wires, solid or stranded)
Dim load type. Each zone will switch load on or off
until it is configured via unit programming. Once
configured, the load type cannot be changed back
to unassigned / Non-Dim.
• Zone and raise/lower buttons on the unit can be
used to:
– turn loads on and off.
– dim loads up and down.
• Input and sensor status LEDs (‘Occ’, ‘Photo’, ‘IR’,
and ‘Switch’) verify connections to dry contact
switches and sensors.

® S P E C I F I C AT I O N S U B M I T TA L Page 3
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 4 07.23.18

Mounting

• See Lutron P / N 048466 at www.lutron.com for more


information on mounting and installation in panels with
integrated DIN rail. CCI
800 W Max 500 W Max 500 W Max 500 W Max

Zone 1 Zone 2 Zone 3 Zone 4

• Mount in IP20 (minimum) rated consumer panel or Option

DIN Rail Power Module


Input Def H

LQSE-4A-D
breaker panel with integrated DIN rail.
Hi Temp Opt1 M

Prog Opt2 L

Power Opt3

• Mount unit in orientation shown. 230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

• Unit may be mounted by unlocking the four mounting


clips on the back of the unit. Clips must be locked
once unit to securely attached the unit to the DIN rail.
• Mount in an accessible and serviceable location.
• Unit generates heat, maximum 75 BTUs / Hour
• Mount unit such that all the conditions below are met: Locked Unlocked

– Room ambient temperature is between 0 ºC and 30 ºC


– Temperature inside mounting panel, within 20 mm of 4 mounting clips on unit
unit, is between 0 ºC and 50 ºC
– Calibration point maximum: 70 ºC

Mechanical Dimensions
Left Side View Front View

Calibration
point 800 W Max 500 W Max 500 W Max 500 W Max

CCI
Zone 1 Zone 2 Zone 3 Zone 4
90 mm

90 mm
Option
DIN Rail Power Module

Input Def H
LQSE-4A-D

Hi Temp Opt1 M

Prog Opt2 L

Power Opt3

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

55 mm 216 mm

70 mm

76 mm

® S P E C I F I C AT I O N S U B M I T TA L Page 4
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 5 07.23.18

Overview of Wiring Terminals


LQSE-4A-D
Emergency-
Contact
Closure QS
Input Link

800 W Max 500 W Max 500 W Max 500 W Max

CCI
Zone 1 Zone 2 Zone 3 Zone 4

Option
DIN Rail Power Module

Input Def H
LQSE-4A-D

Hi Temp Opt1 M

Prog Opt2 L

Power Opt3

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

L L N N N N N DL1 DL2 DL3 DL4

Mains Load Zone Zone


Input Neutrals 1 3
Zone Zone
Mains 2 4
Wiring Phase Adaptive Outputs

® S P E C I F I C AT I O N S U B M I T TA L Page 5
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 6 07.23.18

Verify Wiring
LQSE-4A-D
• Unit ships with bypass connector pre-installed for load • To verify wiring:
wiring verification. Bypass connector is used to apply 1. Turn off power.
power to loads to identify any load or wiring faults prior 2. Wire loads to provided connector.
to wiring loads to unit. 3. Apply power, ensure the desired loads are
• Load wiring must be verified before wiring loads to unit. powered and properly wired.
4. Turn off power and wire loads to DL terminals
on unit.

800 W Max 500 W Max 500 W Max 500 W Max

CCI
Zone 1 Zone 2 Zone 3 Zone 4

Option
DIN Rail Power Module

Input Def H
LQSE-4A-D

Hi Temp Opt1 M

Prog Opt2 L

Power Opt3

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

L L N N N N N DL1 DL2 DL3 DL4

c
Earth
Distribution
b
Panel
Live
(220–240 V~)

Neutral

® S P E C I F I C AT I O N S U B M I T TA L Page 6
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 7 07.23.18

Mains Voltage Wiring

800 W Max 500 W Max 500 W Max 500 W Max

CCI
Zone 1 Zone 2 Zone 3 Zone 4

Option
DIN Rail Power Module

Input Def H
LQSE-4A-D

Hi Temp Opt1 M

Prog Opt2 L
800
PowerW Max 500 W Max
Opt3
500 W Max 500 W Max
230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

CCI
Zone 1 Zone 2 Zone 3 Zone 4

Option
DIN Rail Power Module

Def H
LQSE-4A-D

Opt1 M
Zone 1 Example
Opt2 L

Opt3

0 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

L L N N N N N DL1 DL2 DL3 DL4

Dim Live
Earth
Distribution (220-240 V~)
Panel Live
Neutral Load
(220–240 V~) Neutral

Wiring from Distribution to Adaptive Power Module


• Turn off all circuit breakers or isolators feeding the
Adaptive Power Module at distribution panel.
• Run live, neutral, and earth ( ) wires from a
220-240 V~ 50/60 Hz feed to the DIN Rail Power
Module unit.
• Run a separate neutral for each load circuit. A
common neutral connection is not recommended.

Mains Wiring and IEC PELV Separation


• Follow appropriate local and national codes to avoid
violating required separation guidelines.

® S P E C I F I C AT I O N S U B M I T TA L Page 7
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 8 07.23.18

Wiring: Emergency Contact Closure IEC PELV Emergency Contact Closure Input
Input • Contact Closure Input (CCI) wiring is
IEC PELV / NEC® Class 2.
Follow all applicable national and local codes for
Input
800
800 W
W Max
Max 500
500WWMax
Max 500
500WWMax
Max 500
500W
WMax
Max
proper circuit separation and protection.
S1 S2 S3 S4 CCI
CCI Zone 11 Zone
Zone 22 Zone
Zone 33 Zone
Zone44

• Turn off all breakers or isolators feeding the


Type
IR Photo Occ Switch
Option
Option
Module
PowerModule

Input
Input Def
Def HH
QSNE-4A-D

Energi Savr Node QS unit at distribution panel be-


LQSE-4A-D

Hi T
Hi Temp
emp Opt1
Opt1 M
M
RailPower

Prog
Prog Opt2
Opt2 LL
DINRail

Power
Power Opt3

fore servicing unit.


Opt3
DIN

230 V~
230 V~ 50
50 // 60
60 Hz
Hz 10
10 A
A www.lutron.com +44.(0)20.7702.0657
www.lutron.com +44.(0)20.7702.0657

• The CCI is a local control only and cannot control


other Energi Savr Node QS units over the QS link.
A maximum of 32 Energi Savr Node QS units may
be connected in parallel to an Emergency or Manual
Common override device if the event is intended to affect
CCI multiple devices.
Note: Shown with • When in emergency mode, all zone outputs will be
pre-installed jumper. at their programmed emergency light level
(configurable for each zone, default is 100%).
All sensors and controls are locked out.
CCI COM
• Emergency contact closure input is normally closed
00 W Max 500 W Max 500 W Max 500 W Max
(NC). The Energi Savr Node QS unit is shipped with
a jumper pre-installed.
Zone 1 Zone 2 Zone 3 Zone 4

Note: The Energi Savr Node QS unit will default to


Option
Def H Emergency Mode if the CCI is left open. If no Emergency
Contact Closure Input is required, please leave the wire
Opt1 M
jumper in the CCI terminals.
Opt2 L

Opt3

www.lutron.com +44.(0)20.7702.0657

)Lutron, Lutron, HomeWorks, RTISS Equipped, GRAFIK Eye, seeTouch, and Quantum are registered trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries.
RTISS-TE, Energi Savr Node are trademarks of Lutron Electronics Co., Inc.

® S P E C I F I C AT I O N S U B M I T TA L Page 8
Job Name: Model Numbers:

Job Number:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 9 07.23.18

Wiring: QS Link
QS Link IEC PELV Wiring

800 W Max 500 W Max 500 W Max 500 W Max


• Link communicates using IEC PELV / NECR Class 2 wiring.
• Turn off all breakers or isolators feeding the Adaptive
CCI
Zone 1 Zone 2 Zone 3 Zone 4

Option
DIN Rail Power Module

Power Module at distribution panel before servicing unit.


Input Def H
LQSE-4A-D

Hi Temp Opt1 M

Prog Opt2 L

• Follow all applicable national and local codes for proper


Power Opt3

230 V~ 50 / 60 Hz 10 A www.lutron.com +44.(0)20.7702.0657

circuit separation and protection.


• Wiring may be daisy chained or t-tapped.
• Total length of QS link must not exceed 600 m.
• For lengths under 150 m, use two 1,0 mm2
conductors for control power (24 V-, COM).
• For lengths over 150 m, use two 4,0 mm2 conductors
for control power (24 V-, COM).
• Use one, twisted-shielded pair of 1,0 mm2 conductors
W Max
(1) COM for data link (MUX, _).
ne 4 (2) Do Not Connect Teminal 2
1

(3) MUX
(4) MUX
H

M Daisy-Chain Wiring Example


seeTouch QS QSE-CI-DMX
wallstations
L

02.0657

T-Tap Wiring Example


seeTouch QS
wallstations

1
QSE-CI-DMX  nit does not consume or supply PDUs on
U
the QS link. Do not connect the 24 V- wire
to unit.
Note: 24 V- wire must bypass the unit if other
devices on the link consume PDUs.

® S P E C I F I C AT I O N S U B M I T TA L Page 9
Job Name: Model Numbers:

Job Number: